Designing a Liebert XD Solution
13
3.6 Liebert XDV Unit Placement
XDV units should be placed on top of the cabinets that generate the greatest amount of heat. If heat
loads are dispersed evenly throughout the room, the XDV modules may be spread out accordingly.
The XDV must be placed toward the front of the equipment cabinet, so that its front bottom edge is
flush with the front top edge of the cabinet. Placing the unit farther back on the top of the unit will
restrict airflow into the cold aisle. Placing the unit farther to the front will decrease the amount of hot
air drawn into the unit.
Figure 13 Positioning Liebert XDV on top of cabinet
Both of the XDV’s power cords should be connected to power sources. If only one power source is avail-
able, then only the power cord labeled “SECONDARY” should be connected to the power source.
Piping for the XDV is routed upward to the main return and supply pipes to and from the XDP/XDC.
Table 2 below can be used to determine the correct number of XDV modules.
Table 2 Determine required number of XDV modules
Input Information Step Results
Total heat load in the room, kW A
Reserve capacity needed
(10% to 25% of A is recommended)
B
C Required cooling capacity = A + B
Existing/planned Liebert Deluxe/DS
sensible capacity
D
E Required XD system cooling capacity = C – D
F
Number of XDV modules required = E ÷ 8, rounded up (60Hz)
= E ÷ 6.5, rounded up (50Hz)
G
Number of XDP/XDC modules required = F ÷ 20, rounded up (60Hz)
= F ÷ 21.5, rounded up (50Hz)
Room area, square feet H
I Area served by each XDV = H ÷ F
L
Required XD system cooling density = E ÷ H
OK if under 580 for 12-foot cold aisle spacing
OK if under 435 for 16-foot cold aisle spacing
Otherwise, additional Liebert Deluxe or Liebert DS unit capacity is
needed.
INCORRECT
XDV hangs
over front
edge of rack
INCORRECT
XDV is too
far from front
edge of rack
CORRECT
XDV is flush with
front edge of rack
X
XDV is suspended
from roof structure...
X
....the separation
between the rack and
the XDV should be
held to less than 1"
(25mm). If this is not
possible, an air
blocker should be
added to prevent
unwanted airflow
between the hot aisle
and the cold aisle.