Rosemount 3051
September 2014
www.rosemount.com
Europe
E8 ATEX Flameproof and Dust
Certificate: KEMA00ATEX2013X; Baseefa11ATEX0275X
Standards Used: EN60079-0:2012, EN60079-1:2007,
EN60079-26:2007, EN60079-31:2009
Markings: II 1/2 G, Ex d IIC T6/T5 Ga/Gb, T6(-50°C
Ta
+65°C), T5(-50°C
Ta +80°C);
II 1 D Ex ta IIIC T95°C T
500
105°C Da (-20°C Ta +85°C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will be
subjected. The manufacturer’s instructions for installation
and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints
the manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
I1 ATEX Intrinsic Safety and Dust
Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-11:2012,
EN60079-31:2009
Markings: HART: II 1 G Ex ia IIC T5/T4 Ga
T5(-60°C Ta
+40°C), T4(-60°C Ta +70°C)
Fieldbus/PROFIBUS: II 1 G Ex ia IIC Ga
T4(-60°C Ta +60°C)
DUST: II 1 D Ex ta IIIC T95°C T
500
105°C Da
(-20°C
Ta +85°C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by EN60079-11. This must be
taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however care should
be taken to protect it from impact or abrasion if located in
Zone 0.
3. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
IA ATEX FISCO
Certificate: BAS97ATEX1089X
Standards: EN60079-0:2012, EN60079-11:2009
Markings: II 1 G Ex ia IIC Ga T4(-60°C Ta +60°C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by EN60079-11. This must be
taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however care should
be taken to protect it from impact or abrasion if located in
Zone 0.
N1 ATEX Type n and Dust
Certificate: BAS00ATEX3105X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-15:2010,
EN60079-31:2009
Markings: II 3 G Ex nA IIC T5 Gc (-40°C
Ta +70°C);
II 1 D Ex ta IIIC T95°C T
500
105°C Da (-20°C
Ta
+85°C)
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500V
insulation test that is required by EN60079-15. This must
be taken into account when installing the apparatus.
2. Some variants of the equipment have reduced markings
on the nameplate. Refer to the Certificate for full
equipment marking.
Process Temperature
Temperature class Process temperature
T6 -50°C to +65°C
T5 -50°C to +80°C
Input parameters
HART Fieldbus/PROFIBUS
Voltage U
i
30 V 30 V
Current I
i
200 mA 300 mA
Power P
i
0.9 W 1.3 W
Capacitance C
i
0.012 μF 0 μF
Inductance L
i
0 mH 0 mH
Input parameters
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
<5 nF
Inductance L
i
<10 μH