Reference Manual
00809-0200-4801, Rev CA
July 2010
6-25
Rosemount 3051S
Figure 6-20. Flow Chart for
Plugged Impulse Line
Diagnostics
CONFIGURATION OF
PLUGGED IMPULSE
LINE DETECTION
This section describes the configuration of the plugged impulse line
diagnostic.
Basic Configuration For some impulse line plugging applications there will be a very significant (>
80%) decrease in standard deviation. Examples of this would include a plug in
the impulse line of a GP/AP measurement in a noisy process, or a plug in both
impulse lines of a DP measurement. In these applications, configuring
plugged impulse line detection requires nothing more than turning it on. To do
this, set
PLINE_ON = Enabled
Once the PIL is enabled, it will automatically start the learning process, and
move to the detection phase if there is sufficient variation and the process is
stable.
Optionally, if, when a plugged impulse line is detected, you want to
automatically have the status quality of the pressure measurement go to
“Uncertain”, set the parameter
PLINE_Affect_PV_Status = True