Basis Weight Actuator
7
Figure 5. IC2000 Control Cabinet Components
1
E0011 / IL
Figure 6. Remote Station
E0012 / IL
CAUTION
Incorrect valve shaft rotation can dam-
age internal valve parts. To avoid such
damage, be certain that the actuator will
provide the correct rotation direction for
the valve you are using.
Required valve shaft rotation is not the same for all
valves. Design V150 and V200 valves require clock-
wise valve shaft rotation to open the valve; valves in
the 8500 Series require counterclockwise rotation to
open the valve. Before mounting the valve, check to
see that the actuator will provide the correct rotation to
open and close the valve. If the rotation is not correct,
change the rotation direction by changing the switch
Settings and jumper locations on the control cards.
Refer to the Settings section.
Always use the standard mounting position shown in
figure 17 and check for proper rotation before installing
the actuator on the valve. Other mounting positions
might provide incorrect valve rotation.
Wiring
WARNING
Never make adjustments to the drive
current or terminal connections while
power is applied. Personal injury or
property damage might result.