Basis Weight Actuator
15
Figure 11. Limit Switch Connection Schematic, 2 Limit Switches (Standard)
NOTE:
LS1 & LS2 OPEN THE COMMAND CIRCUITS TO STOP THE ACTUATOR
AT THE LIMIT CONDITIONS.
E0016 / IL
(CABLE OD = 9.1mm)
Adjustment
Limit Switches
The Basis Weight Assembly is standardly shipped with
2 limit switches. 4 limit switches can be wired by the
customer.
1. Mark the position of the actuator travel indicator
cover (figure 2) so that you can return it to the same
position after adjustment. Loosen the screws and re-
move the actuator position indicator.
2. Use the handwheel to position the actuator to 0 de-
grees rotation (fully closed). If necessary, refer to the
valve body instruction manual to determine the fully
closed position.
3. Loosen (slightly) the two screws on the limit switch
for 0 degrees rotation (LS2). Move the switch until you
can hear a click, which indicates that the switch has
been actuated.
4. Tighten the limit switch screws.
Note
Check the limit switch when you release,
or close, it. If the mounting screws are