
Basis Weight Actuator
22
WARNING
The valve ball or disk closes and opens
with a shearing, cutting motion. Avoid
personal injury from this motion by
keeping hands, tools, and other objects
away from the valve ball or disk.
3. Loosen the socket–head screws in the valve shaft
clamp (see figure 17). The valve shaft clamp is located
on the actuator where the valve shaft is connected to
the actuator.
4. Remove the cap screws that attach the valve body
to the actuator mounting yoke. If it is desired to re-
move the yoke from the actuator, remove the cap
screws and nuts that attach the mounting yoke to the
actuator.
Mounting the Actuator on the Valve
1. When maintenance is complete, attach the mount-
ing yoke to the actuator if it was removed.
2. Refer to the valve body instruction manual for in-
structions on determining the fully closed position. Ful-
ly close the valve and keep it in that position until this
procedure is complete.
CAUTION
Incorrect valve shaft rotation can dam-
age internal valve parts. To avoid such
damage, be certain that the actuator will
provide the correct rotation direction for
the valve you are using.
Required valve shaft rotation is not the same for all
valves. Design V150 valves require clockwise valve
shaft rotation to open the valve. Before mounting the
valve, check to see that the actuator will provide the
correct rotation to open and close the valve. If the rota-
tion is not correct, change the rotation direction by
changing the switch settings and jumper locations on
the control cards. Refer to the Settings section.
Always use the standard mounting position shown in
figure 17 and check for proper rotation before installing
the actuator on the valve. Other mounting positions
might provide incorrect valve rotation.
3. Use the actuator handwheel to rotate the actuator
mechanism to the closed end of its travel (to the posi-
tion it is to be in when the valve is fully closed).
4. While guiding the valve shaft clamp over the valve
shaft, place the actuator and mounting yoke on the
valve.
5. Check to be sure that the valve is still fully closed.
Then, tighten the socket head cap screws in the valve
shaft clamp. If the valve ball or disk has moved from
the fully closed position, remove the actuator from the
valve, fully close the valve and repeat steps 4 and 5.
6. Attach the mounting yoke to the valve with cap
screws.
Replacing Fuses
1. Remove alternating current power at the external
circuit breaker box.
2. Unlock and open the Stepmotor Interface.
3. Locate fuses. Fuses are in terminal block TB2 and
on the SD13 card.
4. Test the fuses and replace them if needed.
Replacing the Actuator Motor
1. Remove alternating current power at the external
circuit breaker box.
2. Remove the cover plate from the motor. The cable
was sealed to the motor with silicone rubber at the fac-
tory. Remove the seal. Note the wire–terminal connec-
tions so you can re–wire the new motor correctly. Dis-
connect and remove the wires from the motor.
3. Unscrew the four screws and nuts that attach the
motor to the actuator (figure 2). Remove the motor by
separating the two halves of the zero backlash cou-
pler. Inspect the elastomer spider in the coupler; re-
place it if worn or damaged. Keep the coupler as you
may need to use it again during re-assembly.
4. Install the new motor. Make sure the coupling en-
gages both the actuator and the motor output shaft.
Secure the motor with the four screws and nuts.
5. Connect the motor wires to the correct terminals as
you noted in step 2. Re–seal the cable to the motor or
provide another suitable cable connector.
Replacing Modules
1. Remove alternating current power at the external
circuit breaker box.
2. Unlock and open the cover of the Stepmotor Inter-
face.
3. Unlock and open the Stepmotor Interface.
4. Loosen the four captive screws that secure the
module you wish to replace. Pull the module out of the
cabinet.
5. If you are replacing the IC500 or FT100 card, make
the appropriate switch and jumper settings on the re-
placement card. Refer to the Settings section.
Replacing the Transformer
1. If it is necessary to replace the transformer, remove
alternating current power at the external circuit breaker
box. Unlock and open the cabinet.
Kommentare zu diesen Handbüchern