Precision Cooling
For Business-Critical Continuity™
Liebert
®
CW
User Manual–26-181 kW, 7.5-52 Tons, Upflow and Downflow, 50/60Hz
DATA CENTER SOLUTIONS
For More Information:
(866) 787-3271
Sales@PTSdcs.com
Seitenansicht 0
1 2 3 4 5 6 ... 87 88

Inhaltsverzeichnis

Seite 1 - Precision Cooling

Precision CoolingFor Business-Critical Continuity™Liebert® CW™User Manual–26-181 kW, 7.5-52 Tons, Upflow and Downflow, 50/60HzDATA CENTER SOLUTIONSFor

Seite 2 -

Installation Guidelines42.0 INSTALLATION GUIDELINES2.1 Room Preparation• Verify that the floor is level, solid and sufficient to support the unit. See

Seite 3 - TABLE OF CONTENTS

Installation Guidelines52.3 Air Distribution—Upflow UnitsVarious configurations are available:• Front return• Rear return• Bottom return (not availabl

Seite 4

Installation Guidelines62.4 Connections and System Setup• Plan the routing of wiring, piping and ductwork to the unit. See Figures 27 through 33 and F

Seite 5

Liebert CW Dimensions and Weights73.0 LIEBERT CW DIMENSIONS AND WEIGHTSFigure 2 Cabinet and floor planning dimensions for downflow chilled water model

Seite 6

Liebert CW Dimensions and Weights8Figure 3 Cabinet and floor planning dimensions for downflow chilled water models CW106 and CW114 with forward-curved

Seite 7 - SAVE THESE INSTRUCTIONS

Liebert CW Dimensions and Weights9Figure 4 Cabinet and floor planning dimensions for downflow chilled water models CW089, CW106 and CW114 with EC fans

Seite 8

Liebert CW Dimensions and Weights10Figure 5 Cabinet and floor planning dimensions for downflow chilled water models CW146 and CW181 with EC fansModelW

Seite 9 - 026 D C S A 2 1234 A

Liebert CW Dimensions and Weights11Figure 6 Cabinet and floor planning dimensions for upflow chilled water models CW026-CW084Model# ofBlowersDimension

Seite 10 - 2.0 INSTALLATION GUIDELINES

Liebert CW Dimensions and Weights12Figure 7 Cabinet and floor planning dimensions for upflow chilled water models, CW106 and CW114Filter Access(Both E

Seite 11 - Installation Guidelines

Liebert CW Dimensions and Weights13Figure 8 Floor stand dimensions, optional steam, hot water reheat and humidifier piping entrances for CW026 - CW84

Seite 13 - DPN001659

Liebert CW Dimensions and Weights14Figure 9 Floor stand dimensions for CW106 and CW114 models with forward-curved fansHeight, in. (mm)H* Nominal J9 (2

Seite 14 - DPN001660

Liebert CW Dimensions and Weights15Figure 10 Floor stand and floor planning dimensions, downflow models CW026 - CW041 with EC fansDimension A*Height i

Seite 15 - CW114 with EC fans

Liebert CW Dimensions and Weights16Figure 11 Floor stand and floor planning dimensions for downflow models CW051 and CW060 with EC fansPoint Descripti

Seite 16

Liebert CW Dimensions and Weights17Figure 12 Floor stand and floor planning dimensions, downflow models CW076 and CW084 with EC fansDimension A*Height

Seite 17

Liebert CW Dimensions and Weights18Figure 13 Floor stand and floor planning dimensions, downflow models CW089, CW106 and CW114 with EC fansNOTES1. Thi

Seite 18 - MODELS WITH REAR RETURN

Liebert CW Dimensions and Weights19Figure 14 Floor stand and floor planning dimensions, downflow models CW146 and CW181 with EC fansNOTE:1. This floor

Seite 19 - DPN001676

Liebert CW Dimensions and Weights20Figure 15 Plenum dimensions for upflow chilled water models CW026 - CW084Plenum Height in. (mm)HJ20 (508) 1 (25)22-

Seite 20 - DPN001677

Liebert CW Dimensions and Weights21Figure 16 Plenum dimensions for upflow chilled water models CW106 and CW114Plenum Height, in.(mm)KL20 (508) 1 (25)2

Seite 21

Liebert CW Dimensions and Weights22Figure 17 Blower duct and deck dimensions for CW106 and CW114 upflow chilled water modelsModel Blower Supply Motor

Seite 22

Liebert CW Dimensions and Weights23Figure 18 Filter plenum dimensions, downflow models CW146 and CW181 with EC fans24"(610mm)CW146 orCW181 base u

Seite 23

iTABLE OF CONTENTSIMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1SAVE T

Seite 24

Equipment Inspection and Handling244.0 EQUIPMENT INSPECTION AND HANDLINGUpon arrival of the unit and before unpacking it, verify that the labeled equi

Seite 25

Equipment Inspection and Handling25Figure 19 Equipment recommended for handling the Liebert CWIf possible, transport the Liebert CW with a forklift or

Seite 26

Equipment Inspection and Handling264.2.1 Removing the Unit from the Skid With a Forklift1. Align a forklift with either the front or rear side of the

Seite 27

Equipment Inspection and Handling274.2.2 Moving the Unit to the Installation Location with Piano Jacks1. With the Liebert CW elevated, position piano

Seite 28

Equipment Inspection and Handling284.2.4 Removing Liebert CW from Skid Using Rigging1. Locate the center of gravity indicator—the center of gravity va

Seite 29

Equipment Inspection and Handling29Figure 24 Using rigging to lift Liebert CW off skid196713Rev. 0

Seite 30 - SAFETY INFORMATION

EC Fan—Lowering and Removing305.0 EC FAN—LOWERING AND REMOVINGLiebert CW downflow models CW106, CW114 and CW181 can be equipped with EC fans that can

Seite 31 - 4.2 Unpacking the Unit

EC Fan—Lowering and Removing31Figure 25 EC fan lowering procedure211B B54A3"Z" BracketSection B-BTop View of Fan Deck5SectionNot ShownSectio

Seite 32

EC Fan—Lowering and Removing325.2 Removing the EC FansThe EC fans in Liebert CW units can be removed for easier maintenance or for replacement.If the

Seite 33 - 4.2.3 Removing Piano Jacks

EC Fan—Lowering and Removing33Figure 26 EC fan lowering and removal procedure2366758See Steps 1 and 2See Steps 4 - 7See Step 3See Step 8

Seite 34

ii10.0 INITIAL STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6210.1 Additional Considera

Seite 35

Electrical Connections346.0 ELECTRICAL CONNECTIONS6.1 Electrical ConnectionsThree-phase electrical service is required for all models. Electrical serv

Seite 36 - AN—LOWERING AND REMOVING

Electrical Connections35Figure 27 Electrical field connections for downflow chilled water models CW026 - CW084CDElectric service connection blockEarth

Seite 37 - Section B-B

Electrical Connections36Figure 28 Electrical field connections for downflow chilled water models CW089, CW106 and CW114373824505155567778919293CDMonit

Seite 38 - 5.2 Removing the EC Fans

Electrical Connections37Figure 29 Electrical field connections (high voltage) for upflow chilled water models CW026 - CW084Field-supplied disconnect s

Seite 39

Electrical Connections38Figure 30 Electrical field connections (low voltage) for upflow chilled water models CW026 - CW084 373824507778919293575556DPN

Seite 40 - 6.0 ELECTRICAL CONNECTIONS

Electrical Connections39Figure 31 Electrical field connections (high voltage) for upflow chilled water models CW106 and CW114Three-phase electricservi

Seite 41 - Electrical Connections

Electrical Connections40Figure 32 Electrical field connections (low voltage) for upflow chilled water models CW106 and CW114373824505155567778919293CD

Seite 42 - DPN001671

Electrical Connections41Figure 33 Electrical field connections for downflow chilled water models CW146 and CW181Standard Electrical Connections for Do

Seite 43

Electrical Connections42Optional Electrical Connections for Downflow Chilled Water Models CW146 and CW181Refer to Figure 33.9. Factory-installed disco

Seite 44

Electrical Connections43speed loads have on the system voltage. In these instances, an undesirable effect is a difficulty in switching from generator

Seite 45

iiiFigure 11 Floor stand and floor planning dimensions for downflow models CW051 and CW060 withEC fans . . . . . . . . . . . . . . . . . . . . . . .

Seite 46

Electrical Connections44Table 4 shows the Total Current Distortion level as measured on a single CW181 unit and is typical of what can be expected in

Seite 47

Piping457.0 PIPINGAll fluid connections to the unit, with the exceptions of the condensate drain and live steam, are sweat copper. Factory-installed p

Seite 48

Piping46Figure 34 Gravity drain for downflow and upflow unitsCORRECTINCORRECTCORRECTDOWNFLOW CW UNIT UPFLOW CW UNITUNITINTERNALDRAINEXTERNALDRAINCONTI

Seite 49

Piping47Condensate Pump• 1/2" copper sweat connection is provided on units with optional factory-installed condensate pump• Condensate Pump (60Hz

Seite 50 - CW146 and CW181

Piping487.2 Chilled Water Piping7.2.1 Requirements of Systems Using Water or GlycolThese guidelines apply to the field leak checking and fluid require

Seite 51 - 7.0 PIPING

Piping49NOTICERisk of corrosion. Can cause equipment damage.Read and follow individual unit installation instructions for precautions regarding fluid

Seite 52 - INCORRECTINCORRECT

Piping Schematics508.0 PIPING SCHEMATICSFigure 35 Chilled water downflow general arrangement*Components are not supplied by Liebert butare recommended

Seite 53 - Condensate Pump

Piping Schematics51Figure 36 Piping connections for downflow chilled water models CW026 - CW084 with forward-curved fansModelsA(OD Cu)B(OD Cu)C(NPT Ma

Seite 54 - 7.2 Chilled Water Piping

Piping Schematics52Figure 37 Piping connections for downflow chilled water models CW106 and CW114 with forward-curved fansModelNumbersPiping Connectio

Seite 55

Piping Schematics53Figure 38 Primary connection locations, downflow models CW026 - CW041 with EC fansPoint Description X, in (mm) Y, in (mm) Connectio

Seite 56 - IPING SCHEMATICS

ivTABLESTable 1 Unit dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 57

Piping Schematics54Figure 39 Primary connection locations, downflow models CW051 and CW060 with EC fansPoint Description X, in (mm) Y, in (mm) Connect

Seite 58 - Hot Water Reheat Coil

Piping Schematics55Figure 40 Primary connection locations, downflow models CW076 - CW084 with EC FansPoint Description X, in (mm) Y, in (mm) Connect

Seite 59

Piping Schematics56Figure 41 Primary connection locations, downflow models CW089, CW106 and CW114 with EC fansPoint Description X, in. (mm) Y, in. (

Seite 60

Piping Schematics57Figure 42 Primary connection locations, downflow models CW146 and CW181 with EC fansPoint DescriptionXInches (mm)YInches (mm)Connec

Seite 61

Piping Schematics58Figure 43 Chilled water upflow general arrangementChilledWaterSupplyChilledWater SupplyChilledWaterReturnChilledWaterReturnShutoff

Seite 62 - DPN001628

Piping Schematics59Figure 44 Piping connections for upflow chilled water models CW026 - CW084ModelsFactory-Provided Piping Connection Sizes, inchesA,

Seite 63

Piping Schematics60Figure 45 Piping connections for upflow chilled water CW106 and CW114Piping stubbed out inside unit end compartment for fieldconnec

Seite 64 - Piping Schematics

Checklist for Completed Installation619.0 CHECKLIST FOR COMPLETED INSTALLATION9.1 Moving and Placing Equipment___ 1. Unpack and check received materia

Seite 65

Initial Startup Procedure6210.0 INITIAL STARTUP PROCEDURELocate the startup form supplied with the unit documents. Complete the form during startup an

Seite 66 - UNIT FIELD PIPING LOCATIONS

Component Operation and Maintenance, Checks and Adjustments6311.0 COMPONENT OPERATION AND MAINTENANCE, CHECKS AND ADJUSTMENTS11.1 System Testing 11.1.

Seite 67 - 9.4 Other

1IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important safety instructions that should be followed during the installatio

Seite 68 - NITIAL STARTUP PROCEDURE

Component Operation and Maintenance, Checks and Adjustments64FirestatThe optional firestat is a bimetal operated sensing device with a Normally Closed

Seite 69 - 11.1 System Testing

Component Operation and Maintenance, Checks and Adjustments6511.3 Blower Package—Centrifugal FansPeriodic checks of the blower package include: belt,

Seite 70 - 11.2 Filters

Component Operation and Maintenance, Checks and Adjustments6611.4.2 Protective FeaturesMonitoring functions protect the motor against overtemperature

Seite 71 - 11.4 Blower Package—EC Fans

Component Operation and Maintenance, Checks and Adjustments6711.5.2 Cleaning Humidifier Pan and Float SwitchBefore turning off unit:1. With the unit o

Seite 72 - 11.5 Humidifier

Component Operation and Maintenance, Checks and Adjustments6811.5.3 Changing Humidifier Lamps1. Remove the humidifier pan (see 11.5.2 - Cleaning Humid

Seite 73 - Incorrect Switch Orientation

Component Operation and Maintenance, Checks and Adjustments69Operation1. During startup, when the humidity control calls for humidification, the fill

Seite 74 - Infrared Bulbs

Component Operation and Maintenance, Checks and Adjustments70Replacing the CanisterSee Step 5 of Operation in 11.6 - Steam Generating Humidifier for i

Seite 75 - Controls

Component Operation and Maintenance, Checks and Adjustments7113. Replace the canister by reversing the above procedure. Make special note of the follo

Seite 76 - Replacing the Canister

Component Operation and Maintenance, Checks and Adjustments72Circuit Board AdjustmentsHumidifier operation is governed by the humidifier control board

Seite 77

Component Operation and Maintenance, Checks and Adjustments73Figure 49 Steam generating humidifier control boardTable 8 DIP switch settings for steam

Seite 78 - Circuit Board Adjustments

2NOTICERisk of clogged or leaking drain lines. Can cause equipment and building damage.This unit requires a water drain connection. Drain lines must b

Seite 79

Component Operation and Maintenance, Checks and Adjustments7411.7 Condensate Drain and Condensate Pump Systems11.7.1 Condensate DrainCheck and clear o

Seite 80 - 11.7.2 Condensate Pump

Troubleshooting7512.0 TROUBLESHOOTINGNOTICERisk of improper control circuits. Can cause equipment damage. When using jumpers for troubleshooting, alwa

Seite 81 - 12.0 TROUBLESHOOTING

Troubleshooting76Table 11 Humidifier—steam generator troubleshootingSymptom Possible Cause Check or RemedyFalse canister full indicationFoamingCheck d

Seite 82

Troubleshooting77Excessive arcing in the canisterDrain valve clogged or defectiveVerify that drain valve operates freely when activated. Clean valve a

Seite 83

HVAC Maintenance Checklist7813.0 HVAC MAINTENANCE CHECKLISTFilters___ 1. Check/replace filters___ 2. Grille area unrestricted___ 3. Wipe section clean

Seite 84 - AINTENANCE CHECKLIST

HVAC Maintenance Checklist79Drain Piping___ 1. Check for free running drain system___ 2. Clear out obstructions and material buildup on tubing walls__

Seite 85 - Electrical Panel

HVAC Maintenance Checklist80NOTES

Seite 86 - HVAC Maintenance Checklist

COMPLIANCE WITH EUROPEAN UNION DIRECTIVESIlProduttoredichiarache,semunitodimarchioCE,ilprodottoèconformealledirettivedell'Unionee

Seite 87

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Seite 88 - [email protected]

Liebert CW Nomenclature31.0 LIEBERT CW NOMENCLATURECWCW = Liebert CW Floor Mount Chilled WaterUnit026 D C S A 2 1234 ANominal Capacity, kW026038041051