Y695VR Series
3
!
WARNING
!
WARNING
Equipment operation within ratings does not preclude
the possibility of damage from debris in the lines
or from external sources. This equipment should
be inspected for damage periodically and after any
overpressure condition.
Note
If this equipment is shipped mounted on
another unit, install that unit according
to the appropriate instruction manual.
1. Only personnel qualied through training and
experience should install, operate, and maintain
this equipment. For Y695VR Series equipment
that is shipped separately, make sure that there is
no damage to or foreign material in it. Also
ensure that all tubing and piping have been
blown free.
2. This equipment may be installed in any position
as long as the ow through the body is in the
direction indicated by the arrow attached to
the body. If continuous operation is required
during inspection or maintenance, install a
threeway bypass valve around the equipment.
This equipment may vent some gas
to the atmosphere. In hazardous or
ammable gas service, vented gas may
accumulate and cause personal injury,
death, or property damage due to re or
explosion. Vent equipment in hazardous
gas service to a remote, safe location
away from air intakes or any hazardous
area. The vent line or stack opening
must be protected against condensation
or clogging.
Principle of Operation
The Y695VR Series vacuum regulators (Figure 2)
are used to maintain a constant vacuum at the
regulator inlet. A decrease in this vacuum (increase
in absolute pressure) beyond this value registers on
the diaphragm and opens the disk. This permits a
downstream vacuum of lower absolute pressure than
the upstream vacuum to restore the upstream vacuum
to its original pressure setting. On the Type Y695VR,
pressure registers underneath the diaphragm. The
Type Y695VRM has a control line connecting the
diaphragm casing to the vacuum line and an O-ring
stem seal blocking the throat.
Startup and Adjustment
All Y695VR Series equipment can be placed in
operation by slowly introducing inlet vacuum or
pressure. This equipment takes control when control
vacuum is established. This equipment is suitable for
the pressure range stamped on the nameplate
(key 46).
Shutdown
First close the nearest upstream shutoff valve and then
close the nearest downstream shutoff valve to vent
the equipment properly. Next, open the vent valve
between the equipment and the downstream shutoff
valve nearest to it. All pressure between these shutoff
valves is released through the open vent valve.
Maintenance
Equipment parts are subject to normal wear and must
be inspected and replaced as necessary. The
frequency of inspection and replacement of parts
depends on the severity of service conditions and
upon applicable codes and government regulations.
To avoid personal injury, property
damage, or equipment damage caused
by sudden release of pressure or
explosion of accumulated gas, do not
attempt any maintenance or disassembly
without rst isolating the regulator from
system pressure and relieving all internal
pressure from the equipment.
Body Area
These procedures are for gaining access to the disk
assembly, and body gasket. All pressure must be
released from the diaphragm case before the following
steps can be performed.
Key numbers are referenced in Figures 3 and 4.
1. To inspect and replace the disk holder assembly
(key 13), remove the body cap assembly (key 43).
2. If it is necessary to replace the disk holder
assembly (key 13), remove it from the disk spacer
(key 44).
3. To inspect and replace the orice (key 5) or throat
seal (key 31) and machine screw (key 33),
remove the cap screws (key 2), and separate the
diaphragm casing (key 4) from the body (key 1).