Spec. No. 582136600 (Model 211
List 1 and List 2 with Side AC Input Connectors
(List 1 shown)
List 1 and List 2 with Rear AC Input Connectors
(List 2 shown)
Front
* Rectifiers are numbered left to
right as viewed from the front.
Rear
AC input connections are
made using the supplied AC
input cable assemblies/
line cords connected here.
AC input connections are
made using the supplied AC
input cable assemblies/
line cords connected here.
Front View
Nominal 120/208/240V
AC Input for Rectifier Module:
List 1 (19”
Shelf): #1 and #2
List 2 (23” Shelf): #1, #2, and # 3
Blue*
Green/Yellow*
Brown*
White*
Green*
Black*
L2-N
Ground
L1
* color of AC Input Cable
Assembly/Line Cord lead.
AC Input
Cable Assembly
AC Input
Line Cord
ENSURE THE PROPER VOLTAGE AC
BRANCH CIRCUIT AND LINE CORDS
WITH THE APPROPRIATE PLUG
ARE USED FOR YOUR APPLICATION.
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input
“WARNING - HIGH LEAKAGE CURRENT.”
An industrial style plug is required when
providing power to three (3) or more Rectifier
Modules with a flexible cord. Plug and
outlet types 1
-15, 2-15, 2-20, 5-15, and 5-20
as specified in IEC 60083 are considered
to be NON-INDUSTRIAL within the meaning
of this standard.
* AC Input Cable Assembly / Line Cords
Part Number Customer End
535232 unterminated (List 1 & 2)
540946 L6-30P (List 1 & 2)
545252 L5-30P (List 1 & 2)
545478 5-15P (List 1 w/ R48-500)
545479 L5-15P (List 1 w/ R48-500)
545480 L6-15P (List 1; List 2 w/ R48-500)
545481 L5-20P (List 1; List 2 w/ R48-500)
545553 L6-20P (List 1 & 2)
545616 L6-30P (List 1 & 2)
547525 L5-30P (List 1 & 2)
548457 5-15P (List 1 w/ R48-500)
548196 IEC320 C20 (List 1 120/208/240V & List 2 208/240
w/ R48-500 or R48-1000;
List 2 120V w/ R48-500 only.)
Rear View
Nominal 120/208/240V
AC Input for Rectifier Module:
List 1 (19” Shelf): #1 and #2
List 2 (23” Shelf): #1, #2, and # 3