OS2 NACE
5
Body Aluminium Chromatation
Cover Aluminium Chromatation
Box
Position indicator Polycarbonate
Self-jamming ring Steel Phosphatation
Cover nut Stainless steel
Circlips Steel Phosphatation
All parts Stainless HR
Brackets Brass
Mechanism
Bolt Brass
Elastic O-ring Steel Phosphatation
Torsion spring Stainless steel
Traction spring Bronze
Yoke Self-jamming ring Steel Phosphatation
Flat EPDM
O-rings Cover Neoprene
Truarc ring Nitrile
Body Bronze
Control rod Stainless steel Chromium plating
Truarc ring Nitrile
Mechanism Box (BM)
Packing gland
MECHANISM BOX (BM) MATERIAL
COMMISSIONING (BM)
Commissioning differs depending on whether the assembly has an
internal or external bypass and whether overpressure releasing
is required or not. See corresponding technical manuals for further
details.
Note: The position of the travel stop (item. 7 drawing 6a)
depends on the type of assembly and it’s size.
Position A, B or C depending on max. travel of slam shut valve:
A = 15 mm travel, B = 35 mm travel, C = 50 mm travel.
• Mechanism box (BM) intervention
To access the box the cover must be removed. When unscrewing
the nut a circlips is used to remove the O-ring.
The cover is held on by one screw which can be unscrewed
manually or using a socket screw key (max. recommended
couple 2.5 N.m).
• Resetting
To reset the slam shut (after the fault has been settled), the 1
st
mechanism stage must be reset by manually turning the 1
st
stage
trigger. If the slam shut has an internal bypass the cam must be
slightly turned using a resetting key to bypass. If the slam shut has
an external bypass, a bypass valve will be used.
In both cases:
Wait for the pressure to be equalized before resetting the 2
nd
mechanism stage.
When resetting the 2
nd
mechanism stage (opening of the valve) a
reset key is used (delate).
Never use an extension pipe with the reset key when resetting
the 2
nd
stage (max. normal couple 16 N.m, never go over 32 N.m).
CLOSED POSITION
TRAVEL STOP
N10
VALVE
8a – Release activation stages
RESET
DETECTION STAGE
VALVE
TRAVEL STOP
N11
RESET
POWER STAGE
VALVE
TRAVEL STOP
N12
WARNING
AUTHORIZED PERSONNEL ONLY
Risk of injury
After rearming, remove the reset key from the stem.
Do not put fingers in or near the reset mechanism area.
! !
Europe, Middle East, and Africa Document Only