Type EZH Relief or Backpressure Regulator
2
M1055
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
SPRING
CASE VENT
PORT B
EXHAUST
PORT A
PORT L
PORT S
Speci cations
Ratings and speci cations for the Type EZH are listed in the Speci cations section below. Speci cations for speci c relief
valve or backpressure regulator constructions are stamped on a nameplate attached to either the main actuator or the pilot
spring case.
Body Sizes, End Connection Styles, and
Pressure Ratings
(1)
See Table 1
Maximum Inlet and Outlet (Casing) Pressures
(1)
1500 psig / 103 bar
Maximum Emergency (Design Casing Pressure)
(1)
1500 psig / 103 bar
Maximum Operating Differential Pressure
(1)
Main Valve: 1500 psid / 103 bar d
Pilot (Between loading pressure in pilot and
loading sense pressure): 1233 psid / 85.0 bar d
Outlet Pressure Ranges
See Table 2
Minimum Differential Pressures
(1)
TYPE
MAIN VALVE
BODY SIZE
MINIMUM DIFFERENTIAL
For 90% Capacity For 100% Capacity
NPS DN psid bar d psid bar d
EZH
1 25 15.2 1.1 15.7 1.1
2 50 12.0 0.83 13.8 0.95
3 80 10.6 0.73 12.8 0.88
4 100 15.8 1.1 16.4 1.1
Pressure Registration
External
Pilot Connections
1/4 NPT
Temperature Capabilities
(1)
Nitrile (NBR) Version:
-20 to 180ºF / -29 to 82ºC
Fluorocarbon (FKM) Version:
0 to 180ºF / -18 to 82ºC
(2)
Options
Pre-piped Pilot Supply
Travel Indicator
1. The pressure/temperature limits in this Instructional Manual and any applicable standard or code limitation should not be exceeded.
2. Type PRX Fluorocarbon (FKM) elastomer is limited to 0°F / -18°C.