CSB400 Series
17
!
WARNING
In the case of a downstream line break,
numerous factors affect the capability to
evacuate gas from the pipeline. These
factors include the distance of pipe to the
break, the diameter of the pipe, size of the
break and the number of restrictions, such
as valves, elbows and bends, downstream
of the regulator and/or slam-shut device.
Due to these factors additional protections
should be installed to stop ow in the
event of a line break.
Shutdown
Installation arrangements may vary, but in any
installation it is important that the valves be opened
or closed slowly and that the outlet pressure be vented
before venting inlet pressure to prevent damage caused
by reverse pressurization of the regulator. The following
steps apply to the typical installation as indicated.
1. Open valves downstream of the regulator.
2. Slowly close the upstream shut-off valve.
3. Inlet pressure should automatically be released
downstream as the regulator opens in response to
the lowered pressure underside of the diaphragm.
4. Close outlet shut-off valve.
Dow Corning
®
is a mark owned by Dow Corning Corporation.
Figure 11. CSB400 Series Regulator Assembly
APPLY LUBRICANTS (L) / SEALANT (S)
(1)
:
L1 = DOW CORNING
®
33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
L2 = ANTI-SEIZE LUBRICANT
S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Lubricants and sealant must be selected such that they meet the temperature requirements.
ERAA04154
S1
L1
L1
22
L1
21
L1
27
35
74
L2
25
L1
75
L1
77
L1
19
20
19
55
10
14
13
18
11
L2
96
100
L2
65
L2
60
L1
62
L2
L2
38
95
51
8
7
5
6
4
TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS
TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS
TORQUE:
1.7 TO 3.4 N•m /
15 TO 30 INCH-POUNDS
TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
Kommentare zu diesen Handbüchern