CSB400 Series
15
For Type CSB423 with external control lines, use tubing
with an outer diameter of 13 mm / 0.5 inch or larger for
both the primary regulator and Integral True-Monitor™.
Downstream Control Line Installation
with Slam shut
Refer to Figure 10. When installing the Types CS404ET,
CS404EN, CSB424ET, CSB424EN and CSB454EN
regulators, connect downstream control line tubing to
the lower casing of the regulator and run the tubing
downstream of the regulator outlet with a minimum
distance of 4 times the outlet pipe diameter. Connect
a second, separate downstream control line tubing to
the lower casing of the slam shut and run the tubing
downstream of the regulator outlet a minimum distance
of 4 times the outlet pipe diameter.
For Type CSB404 with external control lines, use tubing
with an outer diameter of 9.5 mm / 0.375 inch or larger
for the primary regulator and 6.4 mm / 0.25 inch or larger
for the slam shut.
For Types CSB424 and CSB454 with external control lines,
use tubing with an outer diameter of 13 mm / 0.5 inch or
larger for the primary regulator and 6.4 mm / 0.25 inch or
larger for the slam shut.
Installation with External
Overpressure Protection
If the regulator is used in conjunction with a Type 289H
relief valve, it should be installed as shown in Figure 7.
The outside end of the vent line should be protected
with a rainproof assembly. The Type 289H is typically set
25 mbar / 10 inches w.c. higher than the outlet pressure
setting of the regulator, up to 75 mbar / 30 inches w.c.
outlet pressure. For pressure greater than this, set the
Type 289H 0.05 bar / 0.75 psi higher than the outlet
pressure setting of the regulator.
Vent Line Installation
The CSB400 Series regulators have a 1 NPT screened
vent opening in the spring case. If necessary to vent
escaping gas away from the regulator, install a remote
vent line in the spring case tapping. Vent piping should
be as short and direct as possible with a minimum
number of bends and elbows. The remote vent line
should have the largest practical diameter. Vent piping
on regulators with token relief must be large enough
to vent all relief valve discharge to atmosphere without
excessive backpressure and resulting excessive
pressure in the regulator.
For types with optional Token relief, this low capacity
relief is located in the spring case of the primary
regulator. If necessary to vent escaping gas away, install
a remote vent line in the spring case tapping of the
primary regulator as described above. Periodically check
all vent openings to be sure that they are not plugged
or obstructed.
CSB400 Series outlet pressure ranges are shown in
Table 6. Outlet pressure higher than 0.34 bar / 5 psig
above the setpoint may damage internal parts such as
the diaphragm head and valve disk. The maximum
emergency (casing) outlet pressure is 4.0 bar / 58 psig.
Commissioning
CAUTION
Pressure gauges must always be used to
monitor downstream pressure during Startup.
With the downstream system depressurized, use the
following procedure to start up the regulator.
1. Check to see that all appliances are turned off.
2. Slowly open the upstream shut-off valve.
3. Check inlet and outlet pressure for correct values.
4. Check all connections for leaks.
5. Turn on utilization equipment and recheck
the pressures.
Adjustment
Note
For types that include the Integral
True-Monitor module, refer to the
Instruction Manual for Type TM600
Integral True-Monitor for adjustment and
maintenance of the Integral True-Monitor.
For the types that include the slam-shut
module, refer to the Instruction Manual for
Type VSX4 slam shut for adjustment and
maintenance of the slam shut.