Emerson Bristol ControlWave ExpressPAC Bedienerhandbuch Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 96
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)
Revised Mar-2011 Installation 2-9
2.2.2 Grounding the Housing
The ControlWave ExpressPAC enclosure includes a ground lug that
accommodates up to a #4 AWG wire size. Once you install the unit, run
a ground wire between the enclosure’s ground lug and a known good
Earth ground. For more information on grounding see the ControlWave
Grounding Supplement (S1400CW):
Additional grounding guidelines include:
Use stranded copper wire (#4 AWG) to earth ground, and keep the
length as short as possible.
Clamp or braze the ground wire to the ground bed conductor
(typically a stranded copper AWG 0000 cable installed vertically or
horizontally).
Using a high-wattage soldering iron, tin the ground wire with solder
before you insert it into the chassis ground.
Run the ground wire so that any routing bend in the cable has a
minimum radius of 12-inches below ground and 8-inches above
ground.
Seitenansicht 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 95 96

Kommentare zu diesen Handbüchern

Keine Kommentare