ROC364 Instruction Manual
3-27 Input and Output Modules Rev Jun/05
3.5.12 RTD Input Module
The RTD module is similar in operation to an AI module and uses the same troubleshooting and repair
procedures. The RTD module can accommodate two-wire, three-wire, or four-wire RTDs. If two-wire
RTDs are used, terminals B and C must be connected together. If any of the input wires are broken or
not connected, ROCLINK configuration software indicates the “Raw A/D Input” value is either at
minimum (less than 800) or maximum (greater than 4000) as follows:
An open at terminal A gives a maximum reading.
An open at terminal B gives a minimum reading.
An open at terminal C gives a minimum reading.
To verify the operation of the RTD module:
1. Disconnect the RTD and connect a jumper between terminals B and C of the RTD module.
2. Connect an accurate resistor or decade resistance box with a value to give a low end reading
across terminals A and B. The resistance value required can be determined by the temperature-
to-resistance conversion chart for the type of RTD being used.
3. Use ROCLINK configuration software to verify that the Raw A/D Input value changed and
reflects the Adjusted A/D 0% value.
4. Change the resistance to reflect a high temperature as determined by the temperature-to-
resistance conversion chart.
5. Verify that the Raw A/D Input value changed and reflects the Adjusted A/D 100% value.
3.5.13 HART Interface Module
The HART Interface Module provides the source for the HART devices and uses two test procedures to
verify correct operation.
Verify HART Integrity of Loop Power on page 3-27.
Verify HART Communications on page 3-28.
3.5.13.1 Verify HART Integrity of Loop Power
Equipment Required: Multimeter
1. Measure voltage between terminals A and B to verify channel 1.
2. Measure voltage between terminals A and C to verify channel 2.
3. The voltage read in both measurements should reflect the value of +T less the voltage drop of the
HART devices. Zero voltage indicates an open circuit in the I/O wiring, a defective HART
device, or a defective module.