Programming the Audible Alarm Feature
Main Menu / Settings / Alarm Setting / Alarm Param / Alarm Voice.
•
When a new alarm occurs, the audible alarm sounds.
Press any key to silence the audible alarm.
•
Disables the audible alarm.
•
3 minutes / 10 minutes / 1 hour / 4 hours:
When a new
alarm occurs, the audible alarm sounds. The audible
alarm automatically silences after the selected time
period.
none.
Adding, Deleting, and Modifying Users
none.
Refer to “User Information Settings Sub-Menu” on page 129.
Assigning Severity Level to Alarms
Main Menu / Settings / Alarm Setting / Alm Severity.
Configuration / Signal Information Modification / select entry from
“Query Device Type” list / select “Alarm Signal” from “Signal Type”
list / select entry from “New Level” list / press “Set”.
Assigning Relays to Alarms
Main Menu / Settings / Alarm Setting / Alarm Relay.
Configuration / Alarm Relays / select entry from “Standard
Equipment” list / select entry from “New Relay Number” list / press
“Modify”.
Changing the Names of Items Displayed in the LCD and Web-
Interface Menus
Only relay names and digital input names are recommended
to be changed for troubleshooting purposes.
none.
Configuration / Equipment Info Modification.
Configuration / Signal Information Modification.
Viewing Alarms
Main Menu / Status / Active Alarms.
Active alarms are listed in the lower right window pane. If the
window pane is collapsed, click the "arrow" icon to expand the
alarm list.
Clearing Rectifier Lost, Rectifier Communication Fail,
Converter Lost, Converter Communication Fail, and All
Converter Comm Fail Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Main Menu / Manual / Rectifier / All Rect Ctrl.
Main Menu / Manual / Converter / All Conv Ctrl.
Device Information / Rectifier Group / Control Tab.
Device Information / Converter Group / Control Tab.
Clearing SMTemp Lost and SMTemp Probe Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Main Menu / Manual / SMTemp / SMTemp Group.
Main Menu / Manual / SMTemp / SMTemp #.
Device Information / SM Temp Group / Control Tab.
Device Information / SM Temp Group / SM Temp # / Control Tab.
Clearing Battery Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Main Menu / Manual / Batt Group.