NetSure
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
147
3. Select Signal or Register for Input 1.
4. Enter either the register number or choose the equipment, signal type, and signal name. The format for entering a register is
R(x), where x is the number of the register.
5. Setup Input 2 in the same way as Input 1 if it’s not disabled.
6. Enter Param 1 and Param 2 if they are not disabled. The format for entering a parameter is P(x), where x is the value.
7. Select Signal or Register for Output.
8. Enter either the register number or choose the equipment, signal type, and signal name.
9. Click the ADD button in the bottom of the window.
10. Reboot the ACU+. See “Restore Defaults Sub-Menuon page 132.