Emerson 15-90kW Betriebsanweisung Seite 6

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 56
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 5
Introduction
Liebert
®
IntelliSlot
Unity
Card 2
1.0 INTRODUCTION
This Liebert IntelliSlot Unity platform delivers enhanced communication and control of AC Power,
Power Distribution and Thermal Management products. The platform communicates with Emerson
Network Power
®
software tools and services, including Trellis
®
, LIFE
Technology, Liebert SiteScan
Web
and Liebert Nform
®
.
The platform includes the Liebert IntelliSlot Unity-DP
and Liebert IntelliSlot Unity LIFE
cards.
Each card employs the Emerson Protocol to monitor and manage a wide range of operating
parameters, alarms and notifications about the power, distribution and Thermal Management
equipment. The cards also communicate with Building Management Systems and Network
Management Systems.
Figure 1 Liebert IntelliSlot Unity-DP card features
1.1 Protocols
Each card supports the Emerson Protocol, Remote Service Delivery Protocol and HTTP Web by
default.
The Liebert IntelliSlot Unity-DP supports selecting two third-party protocols; the Liebert IntelliSlot
Unity LIFE card supports the default protocols only (Emerson Protocol, Remote Service Delivery
Protocol and HTTP Web).
Available protocols are
BACnet IP—BACnet over Internet Protocol
BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over a
RS-485 serial network (also known as BACnet MSTP RS-485)
Modbus RTU—Modbus Remote Terminal Unit (RTU) communication protocol over a RS-485
serial network (also known as Modbus RTU RS-485)
Modbus TCP—Modbus Transmission Control Protocol over Internet Protocol (also known as
Modbus TCP/IP)
•SNMP
YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
Activity
Link
485
IS-UNITY-DP
Liebert Sensor Network
(future release)
RJ-45-Ethernet—HTTP; Modbus TCP;
BACnet IP; SNMPv1, v2c, v3;
Emerson Protocol
Reset
Button
(Reboot or
reset to
factory
defaults)
BACnet MSTP
Modbus RTU
YDN23
Micro-USB AB
(future release)