Enable Communication Protocols
15 Liebert
®
IntelliSlot
Unity
Card
Figure 9 BACnet IP settings
Configure BACnet MSTP Protocol
Contact your system administrator if you are uncertain about the settings.
1. Select Unity Tab > Protocols > BACnet MSTP.
2. Click on Edit and enter a user name and password if required.
3. Set the BACnet MSTP Node ID. The ID default is 1.
4. Set the BACnet MSTP Data Rate.
5. Set the BACnet MSTP Max Master Address.
6. Set the BACnet MSTP Max Info Frames. The default is 8.
7. Click Save to confirm the changes or click on Cancel to discard them.
8. Restart the card to activate the changes.
a. Select Unity Tab > Support.
b. Enable the commands.
c. Click on Restart.