Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Page 31 of 146
SiteScan Availability Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Control Points (Set)
Unit On / Off 40349 349 BC01_x Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint 40350 350 BC02_x
Temperature Tolerance 40350 350 BC02_x Multiply desired value by 1000
Humidity Setpoint 40351 351 BC03_x
Humidity Tolerance 40351 351 BC03_x Multiply desired value by 1000
Reheat Lockout 40349 349 BC01_x Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout 40349 349 BC01_x Bit 4 on=HL off Bit 5 on=HL on
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status