Guide Specifications
24
2.6.2 Evaporator Coil
The evaporator coil shall be A-frame design with off-
set orientation and have ____sq. ft. (m
2
) face area,
three rows deep. It shall be constructed of rifled cop-
per tubes and aluminum fins and have a maximum
face velocity of ____ ft. per minute (m/s) at ____ CFM
(CMH). A stainless steel condensate drain pan shall
be provided.
2.6.2.1 Polymeric Coating (Optional)
The coil shall be coated with a high performance poly-
meric coating process to provide corrosion resistance
within 2 to 12 pH range.
2.6.3 R-22 Refrigerant
The system shall be designed for use with R-22
refrigerant.
2.6.3 R-407C Refrigerant
The system shall be designed for use with R-407C
refrigerant, which meets the EPA clean air act for
phase-out of HCFC refrigerants.
2.7 iCOM
Microprocessor Control
With Small Graphic Display
The iCOM unit control shall be factory-set for
Intelligent Control which uses “fuzzy logic” and
“expert systems” methods. Proportional and Tunable
PID shall also be user selectable options. Internal
unit component control shall include the following:
Compressor Short Cycle Control - Prevents
compressor short-cycling and needless compres-
sor wear.
System Auto Restart - The auto restart fea-
ture will automatically restart the system after a
power failure. Time delay is programmable.
Sequential Load Activation - On initial star-
tup or restart after power failure, each opera-
tional load is sequenced with a minimum of one
second delay to minimize total inrush current.
Hot Water/Econ-O-Coil Flush Cycles - Hot
water reheat coils and Econ-O-Coils are periodi-
cally flushed to prevent a buildup of contami-
nants.
Predictive Humidity Control - calculates the
moisture content in the room and prevents
unnecessary humidification and dehumidifica-
tion cycles by responding to changes in dew
point temperature.
The iCOM control shall be compatible with all
Liebert remote monitoring and control devices.
Options are available for BMS interface via MODbus,
Jbus, BACNet, Profibus and SNMP.
The iCOM control processor shall be microprocessor
based with a 128x64 dot matrix graphic front monitor
display and control keys for user inputs mounted in
an ergonomic, aesthetically pleasing housing. The
display & housing shall be viewable while the unit
panels are open or closed. The controls shall be menu
driven. The display shall be organized into three
main sections: User Menus, Service Menus and
Advanced Menus. The system shall display user
menus for: active alarms, event log, graphic data,
unit view/status overview (including the monitoring
of room conditions, operational status in % of each
function, date and time), total run hours, various
sensors, display setup and service contacts. A
password shall be required to make system changes
within the service menus. Service menus shall
include: setpoints, standby settings (lead/lag), timers/
sleep mode, alarm setup, sensor calibration,
maintenance/wellness settings, options setup,
system/network setup, auxiliary boards and
diagnostics/service mode. A password shall be
required to access the advanced menus which include
the factory settings and password menus.
The User Menus Shall be Defined as Follows:
Active Alarms: Unit memory shall hold the 200
most recent alarms with time and date stamp for
each alarm.
Event Log: Unit memory shall hold the 400 most
recent events with id number, time and date stamp
for each event.
Graphic Data View: Eight graphic records shall be
available: return air temperature, return air humid-
ity, supply air temperature, outdoor temperature and
four custom graphs.
Unit View - Status Overview: Simple or Graphical
“Unit View” summary displays shall include temper-
ature and humidity values, active functions (and per-
cent of operation) and any alarms of the host unit.
Total Run Hours: Menu shall display accumulative
component operating hours for major components
including compressors, Econ-O-Coil (FC), fan motor,
humidifier and reheat.
Various Sensors: Menu shall allow setup and dis-
play of optional custom sensors. The control shall
include four customer accessible analog inputs for
sensors provided by others. The analog inputs shall
accept a 4 to 20 mA signal. The user shall be able to
change the input to 0 to 5VDC or 0 to 10VDC if
desired. The gains for each analog input shall be pro-
grammable from the front display. The analog inputs
shall be able to be monitored from the front display.
Display Setup: Customer shall pre-select the
desired grouping of display languages at the time of
the order from the following choices:
Group 1: English, French, Italian, Spanish,
German
Group 2: English, Russian, Greek
Group 3: English, Japanese, Chinese, Arabic
Service Contacts: Menu shall allow display of local
service contact name and phone number.