Guide Specifications
23
2.4 Humidifier
A humidifier shall be factory-installed inside the
unit. Bypass air slots shall be included to enable
moisture to be absorbed into the air stream. The
humidifier capacity shall be ____lb./hr (kg/hr). The
humidifier shall be removable from the front of the
cabinet.
2.4.1 Infrared Humidifier
The humidifier shall be of the infrared type consist-
ing of high intensity quartz lamps mounted above
and out of the water supply. The humidifier pan shall
be stainless steel and arranged to be removable with-
out disconnecting high voltage electrical connections.
The complete humidifier section shall be pre-piped,
ready for field connection to water supply. The
humidifier shall be equipped with an automatic
water supply system and shall have an adjustable
water-overfeed to prevent mineral precipitation. A
high-water detector shall shut down the humidifier to
prevent overflowing. A factory-provided air-gap shall
prevent backflow of the humidifier supply water.
2.4.1 Steam Generating Canister Humidifier
A canister-type steam canister shall be factory-
installed in the cooling unit and shall be controlled by
the microprocessor control system. It shall be com-
plete with disposable canister, all supply and drain
valves, steam distributor and electronic controls. The
need to change canister shall be indicated on the
microprocessor control panel. The humidifier shall be
designed to operate with water conductivity from
200-500 micromhos. An air-gap within the humidifier
assembly shall prevent backflow of the humidifier
supply water.
2.5 Reheat
The environmental control unit shall include a fac-
tory-installed reheat to control temperature during
dehumidification.
2.5.1 3-Stage Electric Reheat
The electric reheat coils shall be low watt density,
304/304 stainless steel fin tubular construction, pro-
tected by thermal safety switches, shall be ____ kW
(____ BTUH) controlled in three stages. The reheat
elements shall be removable from the front of the
cabinet.
2.5.1 SCR Electric Reheat
The electric reheat coils shall be low watt density,
304/304 stainless steel fin tubular construction, pro-
tected by thermal safety switches, ____ kW (____
BTUH) controlled by multiple pulses to achieve tight
temperature control. The reheat elements shall be
removable from the front of the cabinet.
2.5.1 Hot Water Reheat
The hot water reheat coil shall have copper tubes and
aluminum fins with a capacity of ____ BTUH (kW)
when supplied with ____ °F (°C) entering water tem-
perature at ____ GPM (l/s) flow rate. Maximum pres-
sure drop shall be ____ psi (kPa). The hot water
reheat control system shall be factory pre-piped with
a two-way modulating control valve and cleanable
Y-strainer.
2.6 Dual Refrigeration System
Each unit shall include two (2) independent refriger-
ation circuits and shall include hot gas mufflers
(semi-hermetic compressors units only), liquid line
filter driers, refrigerant sight glass with moisture
indicator, externally equalized expansion valves and
liquid line solenoid valves. Compressors shall be
located outside the airstream and shall be removable
and serviceable from the front of the unit.
2.6.1 Scroll Compressors
The compressor shall be scroll-type. The compressor
shall be suction gas cooled motor, vibration isolators,
thermal overloads, automatic reset high pressure
switch with lockout after three failures, rotalock ser-
vice valves, pump down low pressure transducer, suc-
tion line strainer and a maximum operating speed of
3500 RPM.
2.6.1 Digital Scroll Compressors
(28-53kW models only)
The compressor shall be scroll-type with a variable
capacity operation capability. Compressor solenoid
valve shall unload the compressor and allow for vari-
able capacity operation. The compressor shall be suc-
tion gas cooled motor, vibration isolators, thermal
overloads, automatic reset high pressure switch with
lockout after three failures, rotalock service valves,
pump down low pressure transducer, suction line
strainer, and a maximum operating speed of
3500 RPM.
2.6.1.1 Crankcase Heaters (Optional)
The compressors shall include crankcase heaters,
powered from the indoor unit electric panel.