Operation
CONTROL SYSTEM
A. Screw Compressor Control And Operation
1. Starting, Stopping and Restarting the Compressor.
Before the screw compressor unit may start, certain
conditions must be met. All of the safety setpoints
must be in a normal condition, and the suction pres-
sure must be above the low suction pressure setpoint
to assure that a load is present. When the “On-Off”
switch or “Manual-Auto” button is pressed, the oil
pump will start. When sufficient oil pressure is built
up and the compressor capacity control and volume
ratio slide valves are at or below 10%, the compressor
unit will start.
If the compressor is in the automatic mode, it will
now load and unload and vary the volume ratio in
response to the system demands.
Stopping the compressor unit can be accomplished
a number of ways. Any of the safety setpoints will
stop the compressor unit if an abnormal operating
condition exists. The compressor unit “On-Off” or
stop button will turn the compressor unit off as will
the low pressure setpoint. If any of these conditions
turns the compressor unit off, the slide valve motors
will immediately energize to drive the slide valves
back to 5% limit. The control motors will be de-
energized when the respective slide valve moves back
below 5%. If there is a power failure, the compressor
unit will stop. If the manual start on power failure
option is selected (see appropriate Microprocessor
Instruction Manual), restarting from this condition is
accomplished by pushing the reset button to insure
positive operator control. If the auto start on power
failure option is selected (see appropriate Micropro-
cessor Instruction Manual), the compressor unit will
start up after a waiting period. With both options,
the compressor slide valves must return below their
respective 5% limits before the compressor unit can
be restarted.
2. Slide Valve Control Actuators
Capacity and volume ratio control of the screw com-
pressor is achieved by movement of the respective
slide valves, actuated by electric motors.
SLIDE VALVE ACTUATOR LOCATION:
VSG 401 CCW
When viewing the compressor from the discharge
end (opposite the drive end), the upper motor is
for capacity control. The command shaft turns (see
Table 1) to decrease the capacity to 10% and reverses
to increase the capacity to 100%. The lower motor is
for volume ratio control. The command shaft turns
(see Table 1) to reduce the volume ratio to 2.0, and
reverses to increase the volume ratio to 5.0.
Actuation of the electric motors can be done manu-
ally or automatically. To actuate the motors manu-
ally, place the desired mode selector in the manual
position and push the manual Increase or Decrease
buttons. In the automatic mode, the microproces-
sor determines the direction to actuate the electric
motors. However, in the automatic mode, there is an
“On” and “Off” time for the capacity control motor.
The “On” time is the time in which the slide valve
moves, and the “Off” time is the time in which the
system is allowed to stabilize before another change
in slide valve position.
Note:
Optical Actuators CAN NOT
be manually rotated.
SLIDE VALVE ACTUATOR LOCATION:
VSG 501 CW Thru VSG 701 CW
View Capacity
View Volume
Ratio
View Volume
Ratio
View Capacity