Emerson VSG & VSSG Spezifikationen Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 100
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
11
Alarm and Shutdown Readings
1. Low Gas Suction Temperature - This point protects
the compressor from suction gas entering the com-
pressor at too low of a temperature, and is activated
by a direct reading from the suction temperature
RTD located in the suction “T”.
2. High Gas Discharge Temperature - This point pro-
tects the compressor against high gas tem-
perature at the discharge of the unit, and is activated
by a direct reading from the RTD located in the
compressor discharge manifold.
3. Low Oil Separator Start Temperature - This point
protects the compressor from starting with low oil
temperature in the separator, and is activated by a
direct reading from the RTD located in the bottom
of the oil separator.
4. Low Oil Separator Run Temperature - Similar to
the Low Oil Separator Start Temperature described
above, however this point only becomes active after
a predetermined period of running time, and uses a
higher setpoint.
5. Low Oil Injection Temperature - This point protects
the compressor from running with cold oil being
injected into the screw housing, and is activated by
a direct reading from the RTD located in the oil injec-
tion line. This point is bypassed for a predetermined
period of time after starting to allow the unit time
to start and warm up.
6. High Oil Injection Temperature - This point protects
the compressor from running with hot oil being
injected into the screw housing, and is activated
by a direct reading from the RTD located in the oil
injection line.
7. Low Suction Pressure - This point protects the
compressor from drawing low suction pressure and
is activated by a direct reading from the suction pres-
sure transducer, which reads the pressure from a tap
located in the suction stop/check valve housing.
8. High Discharge Pressure - This point protects the
compressor from developing high discharge pres-
sure and is activated by a direct reading from the
discharge pressure transducer, which reads the
pressure from a tap located in the oil separator. In
addition to this alarm and shutdown, the compressor
package is ultimately protected from damage due to
over pressurization by at least one discharge pressure
relief valve located on the oil separator. The purpose
of this safety setpoint is to allow for a lower setpoint
to conform to a process requirement, and to prevent
the relief valve from opening.
9. Prelube Oil Pressure - This point acts as a permissive
to start the compressor, and protects against the
compressor starting with no oil lubrication. If, during
a start sequence, the prelube oil pressure fails to rise
above 4.0 PSID, the compressor will fail to start. The
prelube oil pressure is a calculated value obtained
by subtracting the discharge pressure reading from
the oil manifold pressure (oil filter outlet pressure)
reading.
10. Low Oil Pressure - This point protects the com-
pressor from running with insufficient lubrication
pressure, and becomes active after a predetermined
period of running, usually sixty seconds. The oil pres-
sure is a calculated value obtained by subtracting the
suction pressure from the oil manifold pressure (oil
filter outlet pressure) reading, which results in the
actual pressure under which the oil is entering the
screw housing.
11. High Running Oil Filter Differential Pressure - This
point alerts operators to clogging oil filters. When
the oil filters develop a high differential pressure
while running at normal operating temperatures,
it is an indication that they are becoming dirty and
must be changed. An alarm initially warns of dirty
filters; if the situation worsens before the filters are
changed a shutdown will stop the compressor.
The control system for the VSG compressor must protect the
machine from damage caused by running outside of normal
operating conditions by providing operators with alarms
when operating parameters have reached an abnormal
condition, and by automatically stopping the compressor
before these conditions can cause a unit failure. Pressures
and temperatures of the process gas and the oil, as well as
motor amperage and slide positions must all be continuously
monitored to ensure the compressor is operating properly.
In most cases, the safety setpoints described above
will have settings which are dictated by process
requirements, and not necessarily mechanical con-
straints of the compressor. Process pressures and
temperatures may vary considerably depending
on the application of the compressor, and the VSG
compressor is designed to work well in a broad range
of applications.. For this reason, it is impractical
to suggest “initial” setpoints to fit all applications.
Instead, minimum and maximum values for each
safety setpoint are provided, while precise settings
for the safety setpoints must be derived for each
installation.
Seitenansicht 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 99 100

Kommentare zu diesen Handbüchern

Keine Kommentare