Specications
Specications and Tables 1 and 2 list the specications for these regulators. Contact the factory if the regulator is to be
used on any service other than LP-Gas, natural gas, or air. The following information is located on the spring case: type
number, orice size, spring range, and date of manufacture.
Integral Two-stage Regulator
The Type R232A integral two-stage regulator contains
a non-adjustable rst stage regulator on the inlet. The
second stage provides 11-inches w.c. / 27 mbar outlet
pressure. The second
stage portion has a high capacity
internal relief valve construction. The rst stage does not
have an internal relief valve. The regulators are painted
GRAY with a BLACK CAP.
Integral Two psig Service Regulator
The Type R232E integral two psig service regulator
contains a non-adjustable rst stage regulator on the
inlet. The second stage provides 2 psig / 0.14 bar outlet
pressure. The second stage portion has a high capacity
internal relief valve construction. The rst stage does
not have an internal relief valve. The regulators are
painted GRAY with a WHITE CAP.
First Stage Regulators
Type R122H regulators are designed for high pressure
(pounds per square inch) vapor service. These
regulators have high capacity internal relief valves.
When used on rst stage service, the Type R122H regulator
reduces container pressure to approximately 10 psig /
0.69 bar inlet pressure to a second stage regulator. On nal
stage service the regulator reduces container pressure for a
high pressure burner. The regulator is painted RED.
1. In the event the R222 Series malfunctions during a Maximum Emergency Inlet Pressure condition these inlet pressures and the R222 Series relief performance will limit downstream
pressure to 2 psi / 0.14 bar or less.
2. Product has passed Fisher testing for lockup, relief start-to-discharge and reseal down to -40ºF / -40ºC.
Pressure Taps Size Restriction
1/8 NPT: #54 / 0.055-inch Drill on outlet and inlet
Orice Sizes
R122H Series: 0.15-inch / 3.8 mm
R222 Series: 0.14-inch / 3.6 mm
R232A and R232E Series: 0.193-inch / 4.9 mm
Wide Open C
g
for Relief Sizing
R122H Series: 23
R222 Series: 18
R232A and R232E Series: 19
Maximum Allowable Inlet Pressure
R122H, R232A, and R232E Series:
250 psig / 17.2 bar
R222 Series: 10 psi / 0.69 bar
Maximum Emergency Inlet Pressure
R122H, R232A, and R232E Series:
250 psig / 17.2 bar
R222 Series
(1)
: 75 psi / 5.2 bar when used with a
Fisher
®
Type R122H or R622H rst stage regulator.
40 psi / 2.8 bar when used with any other rst
stage regulator.
Temperature Capabilities
R122H, R222, R232A, and R232E Series:
-20 to 160°F / -29 to 71°C
(2)
Pressure Registration
Internal
Outlet Pressure Standard Setpoint
R122H Series: 10 psi / 0.69 bar
R222 Series: Second Stage: 11-inches w.c. / 27 mbar
R232A Series: First Stage: approximately 9 psig /
0.62 bar at 100 psig / 6.9 bar, 50 SCFH / 1.42 Nm
3
/h
Second Stage: 11-inches w.c. / 27 mbar
R232E Series: 9 psig / 0.62 bar at 100 psig /
6.9 bar, 50 SCFH / 1.42 Nm
3
/h
Second Stage: 2 psig / 0.14 bar
Outlet Pressure Spring Ranges
R122H Series: 10 psig / 0.69 bar +/- 1 psig / 0.07 bar
(non-adjustable)
R222 Series: Second Stage: 9.5 to 13-inches w.c. /
24 to 32 mbar
R232A Series: First
Stage: non-adjustable
Second
Stage: 10.2 to 13-inches w.c. / 25 to 32 mbar
R232E Series: First Stage: non-adjustable
Second Stage: 1 to 2.2 psig / 0.07 to 0.15 bar
Approximate Weights
R122H Series: 1.2 lbs / 544 grams
R222 Series: 1.4 lbs / 635 grams
R232A and R232E Series with POL:
1.9 lbs / 865 grams
R232A and R232E Series with NPT tting:
1.5 lbs / 671 grams