R122H, R222, R232A, and R232E Series
LP-Gas Regulators
2
Specications
Specications and Tables 1 and 2 list the specications for these regulators. Contact the factory if the regulator is to be
used on any service other than LP-Gas, natural gas, or air. The following information is located on the spring case: type
number, orice size, spring range, and date of manufacture.
Integral Two-stage Regulator
The Type R232A integral two-stage regulator contains
a non-adjustable rst stage regulator on the inlet. The
second stage provides 11-inches w.c. / 27 mbar outlet
pressure. The second
stage portion has a high capacity
internal relief valve construction. The rst stage does not
have an internal relief valve. The regulators are painted
GRAY with a BLACK CAP.
Integral Two psig Service Regulator
The Type R232E integral two psig service regulator
contains a non-adjustable rst stage regulator on the
inlet. The second stage provides 2 psig / 0.14 bar outlet
pressure. The second stage portion has a high capacity
internal relief valve construction. The rst stage does
not have an internal relief valve. The regulators are
painted GRAY with a WHITE CAP.
First Stage Regulators
Type R122H regulators are designed for high pressure
(pounds per square inch) vapor service. These
regulators have high capacity internal relief valves.
When used on rst stage service, the Type R122H regulator
reduces container pressure to approximately 10 psig /
0.69 bar inlet pressure to a second stage regulator. On nal
stage service the regulator reduces container pressure for a
high pressure burner. The regulator is painted RED.
1. In the event the R222 Series malfunctions during a Maximum Emergency Inlet Pressure condition these inlet pressures and the R222 Series relief performance will limit downstream
pressure to 2 psi / 0.14 bar or less.
2. Product has passed Fisher testing for lockup, relief start-to-discharge and reseal down to -40ºF / -40ºC.
Pressure Taps Size Restriction
1/8 NPT: #54 / 0.055-inch Drill on outlet and inlet
Orice Sizes
R122H Series: 0.15-inch / 3.8 mm
R222 Series: 0.14-inch / 3.6 mm
R232A and R232E Series: 0.193-inch / 4.9 mm
Wide Open C
g
for Relief Sizing
R122H Series: 23
R222 Series: 18
R232A and R232E Series: 19
Maximum Allowable Inlet Pressure
R122H, R232A, and R232E Series:
250 psig / 17.2 bar
R222 Series: 10 psi / 0.69 bar
Maximum Emergency Inlet Pressure
R122H, R232A, and R232E Series:
250 psig / 17.2 bar
R222 Series
(1)
: 75 psi / 5.2 bar when used with a
Fisher
®
Type R122H or R622H rst stage regulator.
40 psi / 2.8 bar when used with any other rst
stage regulator.
Temperature Capabilities
R122H, R222, R232A, and R232E Series:
-20 to 160°F / -29 to 71°C
(2)
Pressure Registration
Internal
Outlet Pressure Standard Setpoint
R122H Series: 10 psi / 0.69 bar
R222 Series: Second Stage: 11-inches w.c. / 27 mbar
R232A Series: First Stage: approximately 9 psig /
0.62 bar at 100 psig / 6.9 bar, 50 SCFH / 1.42 Nm
3
/h
Second Stage: 11-inches w.c. / 27 mbar
R232E Series: 9 psig / 0.62 bar at 100 psig /
6.9 bar, 50 SCFH / 1.42 Nm
3
/h
Second Stage: 2 psig / 0.14 bar
Outlet Pressure Spring Ranges
R122H Series: 10 psig / 0.69 bar +/- 1 psig / 0.07 bar
(non-adjustable)
R222 Series: Second Stage: 9.5 to 13-inches w.c. /
24 to 32 mbar
R232A Series: First
Stage: non-adjustable
Second
Stage: 10.2 to 13-inches w.c. / 25 to 32 mbar
R232E Series: First Stage: non-adjustable
Second Stage: 1 to 2.2 psig / 0.07 to 0.15 bar
Approximate Weights
R122H Series: 1.2 lbs / 544 grams
R222 Series: 1.4 lbs / 635 grams
R232A and R232E Series with POL:
1.9 lbs / 865 grams
R232A and R232E Series with NPT tting:
1.5 lbs / 671 grams