8 Series 3000 Transmitters and Discrete Controllers
Hazardous area classifications
UL and CSA
Contact Micro Motion for UL Division 2 entity parameters
Model 3300
Class I, Div. 2, Groups A, B, C, D when installed in a
suitable enclosure.
Model 3350
Class I, Div. 2, Groups A, B, C, and D (standard housing).
Model 3500
Class I, Div. 2, Groups A, B, C, D when installed in a
suitable enclosure. Provides non-incendive sensor
outputs for use in Class I, Div. 2, Groups A, B, C, D, or
intrinsically safe sensor outputs for use in Class I, Div. 1,
Groups C and D; Class II, Div. 1, Groups E, F, and G.
Model 3700
Class I, Div. 2, Groups A, B, C, and D (standard housing).
Provides non-incendive sensor outputs for use in Class I,
Div. 2, Groups A, B, C, D, or intrinsically safe sensor
outputs for use in Class I, Div. 1, Groups C and D;
Class II, Div. 1, Groups E, F, and G.
CENELEC
Model 3300
CENELEC Zone 2 when properly installed in a suitable
enclosure. Zone 2 certificate per prEN 50 021 (1996).
Model 3350
CENELEC Zone 1 EEx de [ib] IIB/C T4
Model 3500
Safe area only, when properly installed in a suitable
enclosure. Can be connected to sensor in CENELEC
[EEx ib] IIB/C area.
Model 3700
CENELEC Zone 1 EEx de [ib] IIB/C T4
Model 3100 accessory
Relay packs
Three relays
Solid state, SPST
Rated at 24–250 VAC, 40 mA to 5 A; or 0–70 VDC, 5 A
Energized by discrete outputs
IP65(NEMA 4X) enclosure (optional)
UL and CSA approvals
Class I, Div. 2, Groups A, B, C, and D
CENELEC approvals
Suitable for installation in Zone 2, complying with
ATEX Directive (94/9/EC) for Group II, Category 3G,
according to CENELEC standard prEN 50021:1998 and
marked as:
EEx n V II T4
KEMA 97 ATEX4940X
Ambient temperature –20 to 60°C
Additional, installation-specific requirements are
described in detail in the instructions that are shipped with
the Model 3100 accessory.
Series 3000 functional specifications
continued