Safety manual for Fisher® 4660 HighLow
Pressure Pilot for Safety Instrumented System
(SIS) Solutions
When the Fisher 4660 highlow pressure pilot is used in a Safety Instrumented System (SIS) the design process should
follow a safety lifecycle as described in several international standards (IEC61508, ANSI/ISA 84.01, etc.) The following
must be thoroughly reviewed and implemented as part of the safety lifecycle. This is in addition to regular installation
procedures and warnings listed in the latest version of the Fisher 4660 highlow pressure pilot instruction manual
(D200163X012).
WARNING
This instruction manual supplement is not intended to be used as a stand-alone document. It must be used in conjunction
with the following manual:
Fisher 4660 HighLow Pressure Pilot Instruction Manual (D200163X012).
Failure to use this instruction manual supplement in conjunction with above referenced manual could result in personal
injury or property damage. If you have any questions regarding these instructions or need assistance in obtaining this
document, contact your Emerson Process Management sale office.
A. Definitions, Acronyms and Abbreviations
1. FIT  Failure In Time (1x10
9
failures per hour)
2. FMEDA 
Failure Modes, Effects, and Diagnostics Analysis
3. Low Demand Mode  Mode, where the demand interval for operation mode on a safetyrelated system is greater
than twice the proof test interval.
4. PFD
AVG
 average Probability of Failure on Demand
5. SIF  Safety Instrumented Function
6. SIL  Safety Integrity Level
7. SIS  Safety Instrumented System
B. Related Literature
1. D200163X012  Fisher 4660 HighLow Pressure Pilot (Instruction Manual)
2. Exida FMEDA Report for Fisher 4660 HighLow Pressure Pilot  Report no. EPM 12/06089 R001
C. Product/ System Properties
1. The product is a highlow pressure pilot that activates emergency shutdown systems. It can be used with either a
single or dual set point capability to maintain full output pressure when the process is operating within the set point
range.
Instruction Manual Supplement
D103776X012
4660 Pressure Pilot
August 2013
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - (SIS) Solutions

www.Fisher.comSafety manual for Fisher® 4660 HighLowPressure Pilot for Safety Instrumented System(SIS) SolutionsWhen the Fisher 4660 highlow pressur

Seite 2 - Instruction Manual Supplement

Instruction Manual SupplementD103776X0124660 Pressure PilotAugust 201322. The fail safe state for the 4660 pressure pilot is with zero output pressur

Seite 3 - WARNING

Instruction Manual SupplementD103776X0124660 Pressure PilotAugust 201333. A conservative approach is taken in estimating the service interval for the

Seite 4

Instruction Manual SupplementD103776X0124660 Pressure PilotAugust 20134Emerson Process Management Marshalltown, Iowa 50158 USASorocaba, 18087 BrazilCh