Europe, Middle East, and Africa Document Only
Type EZR
13
B24B
Figure 13. Type EZR Maintenance Schematic
SYMPTOMS CAUSE ACTIONS
If outlet pressure is increases Internal leak
Control the regulator valve plug
Control the regulator seat
Control the pilot
or contact after-sales
If inlet pressure decreases External leak
Locate and repair leak
or contact after-sales
If inlet pressure is stable The regulator is tightshut
Increase the set point until tripping occurs
(without exceeding the outlet limits)
If the slam shut valve plug will not close Operation faulty
Control the release relay
Control the slam shut valve plug
or contact after-sales
If the slam shut valve plug closes Operation correct
Observe the evolution of the outlet pressure (control tightness)
If the outlet pressure is stable The valve plug is tightshut Purge the outlet side of the regulator
Observe the evolution of the outlet pressure (control tightness)
If the outlet pressure increases Internal leak
Control the slam shut valve plug
Control the slam shut seat
Control the bypass
or contact after-sales
If the outlet pressure is stable Valve plug is tightshut
Table 13. Troubleshooting for Type EZR Regulator