Emerson CP200 Datenblatt Seite 22

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 21
Bulletin 71.1:CP200
22
Table 20. CP200 Series Internal Registration Flow Capacities for 7 psig / 0.48 bar Setpoint
with 1% ABS Pressure Factor Accuracy (PFM Approved)
ACCURACY
SETPOINT + / - 1% ABS SET RANGE
PART NUMBER /
COLOR
7 psig -0.22 psi 0.22 psi 5 to 10 psig
GE39890X012 /
Black Stripe
0.48 bar -15 mbar 15 mbar 0.34 to 0.69 bar
CAPACITIES IN SCFH / Nm
3
/h OF 0.6 SPECIFIC GRAVITY NATURAL GAS
Inlet Pressure
Orice Size, Inch / mm
3/16 / 4.8 1/4 / 6.4 3/8 / 9.5 1/2 / 13
SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h
psig bar Body Size: 3/4 NPT
10 0.69 140 3.8
15 1.0 740 19.8 1100 29.5 1900 50.9 1900 50.9
20 1.4 1000 26.8 1700 45.6 2900 77.7 2700 72.4
25 1.7 1100 29.5 2100 56.3 3300 88.4 3500 93.8
30 2.1 1300 34.8 2300 61.6 3700 99.2 3600 96.5
40 2.8 1600 42.9 2900 77.7 4200 113
50 3.4 1900 50.9 3400 91.1 4500 121
60 4.1 2200 59.0 3700 99.2 4600 123
80 5.5 2900 77.7 4000 107
100 6.9 3400 91.1 3200 85.8
125 8.6 3900 105
psig bar Body Size: 1 NPT
10 0.69 240 6.4 600 16.1 650 17.4
15 1.0 580 15.5 1500 40.2 2100 56.3 3200 85.8
20 1.4 970 26.0 1900 50.9 3500 93.8 4700 126
25 1.7 1100 29.5 2300 61.6 4200 113 4800 129
30 2.1 1300 34.8 2600 69.7 5000 134 5500 147
40 2.8 1600 42.9 3200 85.8 6100 163
50 3.4 2000 53.6 3800 102 6700 180
60 4.1 2200 59.0 4400 118 7700 206
80 5.5 2900 77.7 5400 145
100 6.9 3200 85.8 6600 177
125 8.6
psig bar Body Size: 1-1/4 NPT
10 0.69 380 10.2
15 1.0 770 20.6 980 26.3 1900 50.9 2100 56.3
20 1.4 980 26.3 1600 42.9 3400 91.1 4100 110
25 1.7 1100 29.5 2100 56.3 3700 99.2 4600 123
30 2.1 1300 34.8 2300 61.6 3900 105 4600 123
40 2.8 1600 42.9 2900 77.7 4800 129
50 3.4 2000 53.6 3500 93.8 4000 107
60 4.1 2300 61.6 3900 105 3500 93.8
80 5.5 3000 80.4 3900 105
100 6.9 3500 93.8 3900 105
125 8.6 4300 115
Shaded areas indicate values that are limited due to boost effects.
Blank areas indicate where maximum operating inlet pressure for a given orice size is exceeded.