Type 92W
2
1. The pressure/temperature limits in this Instruction Manual, or any applicable code or standard limitations, must not be exceeded.
Specications
Main Valve Body Sizes and End Connection Styles
BODY SIZE,
NPS (DN)
END CONNECTION STYLE AND RATING
(1)
Cast Iron Body Steel Body
1, 1-1/2, and 2 NPT NPT
1, 1-1/2, 2, 2-1/2,
3, and 4
(25, 40, 50, 65,
80, and 100)
Flat-faced CL125B
or raised-faced
CL250B anged
Raised-faced CL150,
CL300, or CL600 anged
Maximum Inlet and Pilot Supply Pressure
(1)
Cast Iron Main Valve and Pilot: 250 psig
(17,2 bar) or body rating limit, whichever is lower
Steel Main Valve and Pilot: 300 psig (20,7 bar)
or body rating limit, whichever is lower
Maximum Differential Pressure
(1)
150 psig (10,3 bar) or body rating limit, whichever
is lower
Minumum Differential Pressure
(1)
20 psig (1,4 bar)
Outlet (Control) Pressure Ranges
See Table 1
Maximum Outlet Pressures
(1)
See Table 2
Maximum Allowable Loading Pressure for Pilot with
Tapped Spring Case
(1)
Combination of pilot control spring setting and spring
case loading pressure must not exceed 150 psig
(10,3 bar) for Type 6492H pilot or 25 psig (1,7 bar)
for Type 6492L pilot
Main Valve Port Diameters and Flow Coefcients
BODY SIZE,
NPS (DN)
PORT DIAMETER
REGULATING
CAPACITIES
K
m
Inches mm
1 (25)
1-1/2 (40)
2 (50)
7/8
1-1/8
1-29/64
22,2
28,6
36,9
10
20
35
0.62
0.62
0.62
2-1/2 (65)
3 (80)
4 (100)
1-5/8
2-1/16
2-3/8
41,3
52,4
60,3
48
66
78
0.71
0.71
0.71
Maximum Material Temperature Capabilities
(1)
Cast Iron Construction: 406°F (208°C)
Steel Construction: 500°F (260°C)
Pressure Registration
External through downstream control line
Downstream Control Line Connection
NPS 1, 1-1/2, or 2 (DN 25, 40, or 50) Body Size:
1/4 NPT female in main valve cylinder spacer
NPS 2-1/2, 3, or 4 (DN 65, 80, or 100) Body Size:
1/4 NPT female in pilot body
Pilot Spring Case Vent
1/8-inch (3,18 mm) drilled hole (standard pilot) or
1/4 NPT female tapping for pressure loading service
(optional pilot)
Approximate Weights
BODY SIZE,
NPS (DN)
END CONNECTION
APPROXIMATE WEIGHTS
Pounds kg
1 (25)
1-1/2 (40)
NPT or anged
NPT or anged
32
44
14
20
2 (50)
NPT
Flanged
55
67
25
30
2-1/2 (65)
3 (80)
4 (100)
Flanged
Flanged
Flanged
90
115
165
41
52
75
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices to prevent service conditions from
exceeding those limits.
Additionally, the pilot could be broken
off the main valve by physical damage,
causing personal injury and property
damage due to escaping liquid. To avoid
such injury and damage, install the
regulator in a safe location where it is
protected from physical damage.
Liquid pressure control systems should
be designed using good engineering
practices to eliminate quick starting or
stopping of the ow stream, which can
produce water hammer. .
1. Only personnel qualied through training and
experience should install, operate, and maintain
a Type 92W regulator. Before installation, make
sure that there is no damage to, or debris in, the
regulator. Also make sure that all tubing and piping
are clean and unobstructed.
CAUTION
Kommentare zu diesen Handbüchern