3
Regular operation below the maximum pressure
limitations does not preclude the possibility of damage
from external sources or debris in the line. The
regulator should be inspected for damage after any
overpressure condition.
Startup
The regulator is factory set at approximately
the midpoint of the spring range or the pressure
requested, so an initial adjustment may be required
to give the desired results. With proper installation
completed and relief valves properly adjusted, slowly
open the upstream and downstream shutoff valves.
!
WARNING
Figure 1. Spring-Loaded Type 630 Regulator - Low-Pressure Construction
0X00119-F

To change the outlet pressure, remove the closing
cap or loosen the locknut and turn the adjusting
screw clockwise to increase outlet pressure or
counterclockwise to decrease pressure. Monitor
the outlet pressure with a test gauge during the
adjustment. Replace the closing cap or tighten the
locknut to maintain the desired setting.



















3 to 8
6 to 17
15 to 22
20 to 35
27 to 50
(0,21 to 0,55)
(0,41 to 1,1)
(1,0 to 1,5)
(1,4 to 2,4)
(1,9 to 3,5)
0W019227022
0W019127022
0W019027022
0Y066427022
1J146927142
Relief Pressure Setting Plus
Maximum Allowable Build-up of
25 psig (1,7 bar)
75 (5,2)

30 to 70
50 to 95
75 to 175
150 to 250
(2,0 to 4,8)
(3,5 to 6,5)
(5,2 to 12,1)
(10,4 to 17,3)
0W019127022
0W019027022
0Y066427022
1J146927142
Relief Pressure Setting Plus
Maximum Allowable Build-up of
250 psig (17 bar)
550 (38,0)
1. Leakage or bursting of pressure-containing parts may occur if inlet pressure exceeds these values.
Table 3. Outlet Pressure Ranges