Step 5: Verify configuration
Use any HART-compliant master to communicate with and verify configuration of
the 3051S.
Field Communicator user interface
Fast Key Sequences vary with the Device Driver Revision. The Traditional Interface
Fast Key Sequences apply to DD Rev. 8 or older and they can be found on page 16
The Device Dashboard Fast Key Sequences apply to DD Rev. 9 or newer and they
can be found on page 17.
Figure 13. Traditional Interface - Device Revision 6 or 7 and DD Revision 7
Figure 14. Device Dashboard - Device Revision 7 and DD Revision 9
A check () indicates the basic configuration parameters. At a minimum, these
parameters should be verified as part of the configuration and startup procedure.
SAVE
3051:PT 93207
Online
1 Device setup
2 PV 0.00 mbar
3 Analog Output 4.000 mA
4 PV LRV 0.00 mbar
5 PV URV 370.00 mbar
SAVE
3051:PT 93207
Online
1 Overview
2 Configure
3 Service Tools
4801_QIG_RevMA.fm Page 15 Wednesday, May 6, 2015 1:15 PM