Installation Drawings
19
Figure 16 Terminal detail drawing, Liebert Module Battery Disconnect
A
B
Notes:
1. All dimensions are in in. (mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring is to be in accordance with national and local electrical codes.
8. Cables from battery system can be connected to either breaker top or bottom busbars.
9. Ground bus shown in factory-installed location, optional gnd
bus mount location located near bottom of cabinet.
Breaker Bottom
Busbars (+/-)
(Note 8)
Breaker Top
Busbars (+/-)
(Note 8)
Ground Bus
(Note 9)
Note 9
DETAIL A
DETAIL B
.00
(0)
11.86
(301)
28.01
(711)
55.28
(1404)
57.87
(1470)
72.74
(1848)
76.86
(1952)
1.75
(44)
1.75
(44)
2.00
(51)
2.00
(51)
.56
(14)
1.75
(44)
1.25
(32)
.56
(14)
.56
(14)