Compressor Timer Setpoints
The compressor restart options (Hot Starts or
Anti-Recycle Timers) are selected from the
Setup screen. One additional Anti-Recycle
Timer that can be selected from the Setup screen
is the Modified Anti-Recycle Timer.
· Modified Anti-Recycle Timer – Normally, this
anti-recycle timer will function as a True Anti-
Recycle Timer. However, if the operator presses
the stop button, or if a failure occurs, the anti-
recycle timer switches functions and acts as an
accumulative type anti-recycle timer. It will al-
low the compressor to restart when the accumu-
lated runtime and the present off time meets or
exceeds the setting of this timer.