Emerson Site Manager Installationsanleitung Seite 41

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 130
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 40
Installation Guide AMS Suite: Intelligent Device Manager
NOVEMBER 2013
41
Only the following PROFIBUS DP and HART I/O modules are supported:
Siemens
The Siemens System Interface lets you use AMS Device Manager to communicate
with HART devices on a Siemens PCS 7 Control Network. An AMS Device Manager
Server Plus or Client SC station must be installed on the same station as the Siemens
PCS 7 ES/MS Station. The AMS Device Manager Network Configuration utility is used
to configure the Siemens System Interface.
The Siemens System Interface requires that:
The Siemens Network is licensed.
A Siemens System v7 with SP1 or higher is installed on the ES / MS Station and
the DeviceCom interface is accessible from the AMS Device Manager.
Siemens PCS 7 project file is copied from the live system.
Manufacturer Description / Module Type Notes
STAHL PROFIBUS DP I.S.1 type 9440 Supports up to 16 connected I/O
modules
STAHL HART Analog Input type 9461
HART Analog Output type
9466
Supports up to 8 connected HART
instruments
STAHL ISpac HART Multiplexer type
9192
Configurations possible for up to 32
connected HART devices. Up to 128
RS485 addresses (ISpac multiplexers)
are possible on a single RS485
segment
Seitenansicht 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 129 130

Kommentare zu diesen Handbüchern

Keine Kommentare