5. INSTALLATION
Refer to the INSTALLATION MANUAL for a description of the XWEB-EVO interfaces and electrical
connections. A paper copy of it is included in the XWEB-EVO package and an electronic copy is provided by
the CD attached to the package, or from the Dixell website in the ‘ResourcesProduct Literature’ section.
5.1 CONTROLLER INSTALLATION PROCEDURE
XWEB-EVO has two RS485 serial ports that the line for the controller devices need to be connected to. Most
Dixell controller devices are supplied with RS485 serial outputs, to connect the instrument to XWEB-EVO
without requiring an external module or connecting cable. To check whether this feature is provided, read
through the characteristics of the controller in the device manual. Nonetheless, some Dixell devices cannot
be supplied with RS485 serial outputs directly but through small external converters: XJRS485 or XJ485.
With this device it is possible to convert the output - of the controller - from 5-wire "TTL" to 2-wire "485". If
you need to use the TTL/485 converter, be careful to:
Keep the TTL cable away from any source of electromagnetic disturbance
Connect each XJ485 module to the instrument by the TTL cable supplied with the module
Mark the polarity of output 485, which needs to be observed when the instruments are connected to
the network
Below is a list of operational tips to achieve the best result in terms of reliability of the instrument network,
with RS485 serial connection:
The serial line cable can be 2-wire plus shielding, with a minimum section of 0.5 sq mm (ex.
BELDEN 8772). This cable is recommended for its technical characteristics and because it maintains
the quality of the electrical signal;
The serial line cable must reach all of the instrument's stations: check the system's floor plan and the
various distances that the cable needs to cover;
The serial line cable can reach a maximum length of 1 km
Match the polarity marked on the instrument with the polarity of the cable leading to the serial;
Do not set up any branches on the line:
Correct connection
Incorrect connection