Liebert® Liqui-tect® Monitoring SystemUser Manual

Seite 2

IntroductionLiebert® Liqui-tect®6S-Power receptacle (Transformer Module)115VAC power receptacle to power laptop during configuration and diagnostics.

Seite 3 - TABLE OF CONTENTS

Introduction7Liebert® Liqui-tect®1.5 LED IndicatorsThe Liebert Liqui-tect panel’s controller board has LED indicators that show the status of inputs,

Seite 4 - 7.0 SPECIFICATIONS

InstallationLiebert® Liqui-tect®82.0 INSTALLATION2.1 Installation ConsiderationsThe Liebert Liqui-tect panel must be installed indoors and may be moun

Seite 5 - 1.0 INTRODUCTION

Installation9Liebert® Liqui-tect®2.2 Surface-Mounting the Liebert Liqui-tect PanelAfter determining where to place the unit, check to ensure that you

Seite 6 - Liqui-tect

InstallationLiebert® Liqui-tect®10Figure 4 Mounting dimensions2.3 Flush-Mounting the Liebert Liqui-tect PanelThe Liebert Liqui-tect panel may be flush

Seite 7 - 1.3 Typical Sequence

Installation11 Liebert® Liqui-tect®2.3.1 Mounting the PanelNOTICERisk of improper installation. Can cause property damage.Check building plans and oth

Seite 8 - LCD Interlface

InstallationLiebert® Liqui-tect®122.4 Connect Power to the Liebert Liqui-tect PanelThe Liebert Liqui-tect panel requires 24VAC for proper operation. L

Seite 9

Installation13 Liebert® Liqui-tect®2.4.2 Input and Output Power Connections - Large EnclosureInput Power ConnectionsTo connect electrical power to the

Seite 10

Connections and ConfigurationLiebert® Liqui-tect®143.0 CONNECTIONS AND CONFIGURATIONInput and output connections to the Liebert® Liqui-tect® panel may

Seite 11 - TX RXRX TX

Connections and Configuration15 Liebert® Liqui-tect®3.1 Connecting Leak Detection Cable InputsThe leak detection cable inputs are found on the lower r

Seite 13 - 2.2.1 Mounting the Panel

Connections and ConfigurationLiebert® Liqui-tect®163.1.2 Connecting Leak Detection Cable to the Connection CableThe connection cable has a black fitti

Seite 14

Connections and Configuration17 Liebert® Liqui-tect®3. Once the cable passes the test, lay it in the pattern desired. Pay special attention to the fol

Seite 15 - 2.3.1 Mounting the Panel

Connections and ConfigurationLiebert® Liqui-tect®183.2 Connecting Alarm OutputsThe Zone 1 and Zone 2 alarm outputs, found in the top right corner of t

Seite 16 - 24V Power

Connections and Configuration19 Liebert® Liqui-tect®3.4 RS422 Liebert SiteScan® Web ConnectorThe Liebert Liqui-tect panel will interface with Liebert’

Seite 17 - Input Power Connections

Overview of MenusLiebert® Liqui-tect®204.0 OVERVIEW OF MENUSThe Liebert Liqui-tect panel displays the Opening Screen at startup, as shown in Figure 14

Seite 18 - * Recommended

View Status Options21 Liebert® Liqui-tect®5.0 VIEW STATUS OPTIONS The View Status menu allows any user to view the status of cables in both zones, an

Seite 19

View Status OptionsLiebert® Liqui-tect®225.1 View Cable Status The Cable Status screens display the overall status of the cable connected to each of t

Seite 20

View Status Options23 Liebert® Liqui-tect®5.2 View Alarm HistoryThe Alarm History Log contains up to 100 records of alarms that have occurred. Records

Seite 21

View Status OptionsLiebert® Liqui-tect®245.3 View Zone TrendThe Zone Trend Log contains up to 288 records that are recorded at regular intervals (ever

Seite 22 - 3.2 Connecting Alarm Outputs

System and Control Options25 Liebert® Liqui-tect®6.0 SYSTEM AND CONTROL OPTIONS The System and Control menu allows you to configure the Liebert Liqui-

Seite 23

iTABLE OF CONTENTS1.0 INTRODUCTION1.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 24 - 4.0 OVERVIEW OF MENUS

System and Control OptionsLiebert® Liqui-tect®26Figure 16 shows the main options available from the System & Control menu.Figure 16 Menu overview

Seite 25 - 5.0 VIEW STATUS OPTIONS

System and Control Options27 Liebert® Liqui-tect®6.2 Setup System - OverviewThe Setup System screen displays six options that allow you to configure z

Seite 26 - 5.1 View Cable Status

System and Control OptionsLiebert® Liqui-tect®286.3.1 Identify the Zone as ConnectedTo make use of the zone ZN1, you must specify it as Connected (Y).

Seite 27 - 5.2 View Alarm History

System and Control Options29 Liebert® Liqui-tect®6.3.4 Auto CalibrationThe auto calibration feature is designed to allow compensation for the resistan

Seite 28 - 5.3 View Zone Trend

System and Control OptionsLiebert® Liqui-tect®306.3.6 Set Up Sensitivity for Contamination Detection Each zone may be set up with a sensitivity level

Seite 29 - 6.1 Login

System and Control Options31 Liebert® Liqui-tect®6.5 Setup System - Setup Alarm OutputsThe Liebert Liqui-tect panel has six alarm outputs—three types

Seite 30

System and Control OptionsLiebert® Liqui-tect®326.5.1 Specify Longest Cable LengthYou may specify the length of the longest cable connected to either

Seite 31 - 6.2 Setup System - Overview

System and Control Options33 Liebert® Liqui-tect®Following are some similarities and differences between Latched and Unlatched alarms.Liebert Liqui-te

Seite 32 - 6.3.3 Change Units Label

System and Control OptionsLiebert® Liqui-tect®346.7 Setup System - Setup MapmodeMapping involves measuring the exact location of various points along

Seite 33 - 6.3.4 Auto Calibration

System and Control Options35 Liebert® Liqui-tect®6.7.1 View Last MapThe View Last Map option allows you to review the mapped points from the last mapp

Seite 34

ii6.5 Setup System - Setup Alarm Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316.5.1 Specify Longest

Seite 35

System and Control OptionsLiebert® Liqui-tect®366.8 Setup System - Setup System InfoThe Setup System Info options allow users to:• Change Password—use

Seite 36

System and Control Options37 Liebert® Liqui-tect®6.8.2 Change Date & Time/Automatic Daylight Saving TimeThe Liebert Liqui-tect panel has a built-i

Seite 37 - Unlatched Alarms Only

System and Control OptionsLiebert® Liqui-tect®386.9 Reset Latched AlarmsThe Reset Latched Alarms menu allows you to clear any leak or fault alarms tha

Seite 38

System and Control Options39 Liebert® Liqui-tect®6.10 Clear Alarm HistoryThe Clear Alarm History menu allows you to delete all records from the Alarm

Seite 39 - 6.7.1 View Last Map

System and Control OptionsLiebert® Liqui-tect®406.11 Clear Zone TrendThe Clear Zone Trend menu allows you to delete all records from the Zone Trend Lo

Seite 40 - Change the Password

Specifications41 Liebert® Liqui-tect®7.0 SPECIFICATIONSTable 13 Liebert Liqui-tect Panel specificationsPower RequirementsSmall Enclosure Large Enclosu

Seite 41 - 6.8.3 Factory Defaults

SpecificationsLiebert® Liqui-tect®42

Seite 43 - 6.10 Clear Alarm History

While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disc

Seite 44 - 6.11 Clear Zone Trend

Introduction1Liebert® Liqui-tect®1.0 INTRODUCTIONThe Liebert Liqui-tect Monitoring System is the ultimate in leak detection and retrofitting capabilit

Seite 45

IntroductionLiebert® Liqui-tect®21.2 Outside Enclosure OverviewThe enclosure for the Liebert Liqui-tect panel’s controller board comes in two sizes:•T

Seite 46 - Specifications

Introduction3Liebert® Liqui-tect®1.3 Typical SequenceFigure 3 shows a typical sequence of how the Liebert Liqui-tect Monitoring System functions after

Seite 47

IntroductionLiebert® Liqui-tect®41.4 Controller Board OverviewThe Liebert Liqui-tect panel’s controller board, as shown below, has connectors for two

Seite 48 - Locations

Introduction5Liebert® Liqui-tect®Table 1 Controller board componentsItem Description More InformationA-Power On/Off LED Indicates when power is suppli