Liebert® IntelliSlot® Modbus RTU, Modbus TCP, BACnet MSTP andBACnet IPReference Guide
Liebert Equipment Compatibility - Compatibility with Liebert EquipmentLiebert® IntelliSlot® Modbus/BACnet 4• Battery Monitoring ProductsAlber BDSU™78-
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 94Table 27 Liebert Challenger 3000™, Liebert Delu
Modbus RTU and Modbus TCP Protocols - Thermal Management Products95 Liebert® IntelliSlot® Modbus/BACnetInverter on Bypass — 40291 1 — Bit 3Standby Fan
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 96Table 28 Liebert DataMate™, Liebert Mini-Mate P
Modbus RTU and Modbus TCP Protocols - Thermal Management Products97 Liebert® IntelliSlot® Modbus/BACnetTable 29 Liebert DataMate™, Liebert Mini-Mate2™
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 98Setpoints (View)Temperature — 40010 1 — —Temp T
Modbus RTU and Modbus TCP Protocols - Thermal Management Products99 Liebert® IntelliSlot® Modbus/BACnetTable 30 Liebert Mini-Mate2™ 8 Ton - Input and
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 100Run Times (View)Compressor 1 Run Hours — 40019
Modbus RTU and Modbus TCP Protocols - Thermal Management Products101 Liebert® IntelliSlot® Modbus/BACnetTable 31 Liebert Atlas Air™, Liebert Atlas PEC
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 102Setpoints (View)Return Air Temperature — 40016
Modbus RTU and Modbus TCP Protocols - Thermal Management Products103 Liebert® IntelliSlot® Modbus/BACnetTable 32 Liebert Atlas Air™, Liebert Atlas PEC
Modbus Communications - Implementation Basics5Liebert® IntelliSlot® Modbus/BACnet2.0 MODBUS COMMUNICATIONS2.1 Implementation BasicsModbus protocol pro
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 104Humidity Low Level — 40290 1 — Bit 4Battery Le
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products105 Liebert® IntelliSlot® Modbus/BACnet3.2 Power Distribution
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 106Alarm PointsDiscrete al
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products107 Liebert® IntelliSlot® Modbus/BACnetTable 34 Liebert Datawa
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 108Table 35 Liebert FPC™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products109 Liebert® IntelliSlot® Modbus/BACnetPanel 4Panel Summary Al
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 110Panel 4 Position 1Branc
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products111 Liebert® IntelliSlot® Modbus/BACnetTable 36 Liebert FPC™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 112Output Power 2 (used on
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products113 Liebert® IntelliSlot® Modbus/BACnetPanel Main Current Ix 3
Modbus Communications - RTU FramingLiebert® IntelliSlot® Modbus/BACnet 62.3.2 Function CodeThe function code field tells the addressed slaves what fun
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 114Panel Main Voltage Vy T
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products115 Liebert® IntelliSlot® Modbus/BACnetPanel 1 Position 1Break
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 116Panel 2 Position 2Break
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products117 Liebert® IntelliSlot® Modbus/BACnetPanel 3 Position 84Brea
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 118Subfeed 1Subfeed Curren
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products119 Liebert® IntelliSlot® Modbus/BACnetSubfeed 64Subfeed Curre
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 120Table 37 Liebert EXC™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products121 Liebert® IntelliSlot® Modbus/BACnetPanel 2 Position 1Branc
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 122Subfeed 1Subfeed Phase
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products123 Liebert® IntelliSlot® Modbus/BACnetTable 38 Liebert EXC™,
Modbus RTU and Modbus TCP Protocols - Thermal Management Products7Liebert® IntelliSlot® Modbus/BACnet3.0 MODBUS RTU AND MODBUS TCP PROTOCOLS3.1 Ther
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 124Panel Main Current Iy 3
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products125 Liebert® IntelliSlot® Modbus/BACnetPanel Main Voltage Vy T
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 126Panel 2 Position 1Break
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products127 Liebert® IntelliSlot® Modbus/BACnetPanel 3 Position 2Break
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 128Panel 4 Position 84Brea
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products129 Liebert® IntelliSlot® Modbus/BACnetSubfeed Current Iy THD
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 130Table 39 Liebert FDC™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products131 Liebert® IntelliSlot® Modbus/BACnetTable 40 Liebert FDC™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 132Panel Main Output Perce
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products133 Liebert® IntelliSlot® Modbus/BACnetTable 41 Liebert EXC™,
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 8Compressor Thermal Overload 2 10043 — 1 Active
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 134Output Undervoltage Uni
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products135 Liebert® IntelliSlot® Modbus/BACnetPhase Loss Voltage and/
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 136Table 42 Liebert® STS™,
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products137 Liebert® IntelliSlot® Modbus/BACnetSource 2 Overload — 402
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 138Table 43 Liebert® STS2™
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products139 Liebert® IntelliSlot® Modbus/BACnetLoadKVA % — 40026 1 — %
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning ProductsLiebert® IntelliSlot® Modbus/BACnet 140Internal Comm Fail — 40
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products141 Liebert® IntelliSlot® Modbus/BACnetLoad Over-current — 402
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 1423.3 UPS SystemsTable 44 Liebert APM™, Liebert NXC™, Liebert NX
Modbus RTU and Modbus TCP Protocols - UPS Systems143 Liebert® IntelliSlot® Modbus/BACnetUser Operation Invalid 10050 — 1 — Active on AlarmPower Sub Mo
Modbus RTU and Modbus TCP Protocols - Thermal Management Products9Liebert® IntelliSlot® Modbus/BACnetFree Cooling Valve Hours Exceeded 10083 — 1 Act
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 144OutputSystem Output Voltage RMS A-N 30419 — 1 — VACSystem Outp
Modbus RTU and Modbus TCP Protocols - UPS Systems145 Liebert® IntelliSlot® Modbus/BACnetTable 46 Liebert APM™, Liebert NXC™, Liebert NXR™ - GlossaryDa
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 146Load Sharing Fault Difference between any phase inverter curre
Modbus RTU and Modbus TCP Protocols - UPS Systems147 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power Factor Phs B The system output power fact
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 148OutputOutput Overload 10050 — 1 Active on AlarmOutput Off Pen
Modbus RTU and Modbus TCP Protocols - UPS Systems149 Liebert® IntelliSlot® Modbus/BACnetTable 48 Liebert APS™ - Input and HoldingData LabelInputRegist
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 150BatteryBattery Time Remaining 30437 — 1 —Units : min Uint 16B
Modbus RTU and Modbus TCP Protocols - UPS Systems151 Liebert® IntelliSlot® Modbus/BACnetSystem Output Apparent Power L1 30473 — 1 100 Units : kVA Uin
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 152Auto Restart — — 40519 1 0 = disabled 1 = enabled Auto Restar
Modbus RTU and Modbus TCP Protocols - UPS Systems153 Liebert® IntelliSlot® Modbus/BACnetBatteryModule 2Module Operating Status 30670 — 1 —0 = Normal
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 10Digital Output Board Not Detected 1 10224 — 1
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 154Table 49 Liebert APS™ - GlossaryData Label Data DescriptionAcc
Modbus RTU and Modbus TCP Protocols - UPS Systems155 Liebert® IntelliSlot® Modbus/BACnetFrame Capacity Total system capacity supported when the maximu
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 156Output Qualification Status output qualification status Power
Modbus RTU and Modbus TCP Protocols - UPS Systems157 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power L2 The system output power on Line 2. Sys
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 158Table 50 Liebert GXT2™ and Liebert GXT3™ - Status and CoilData
Modbus RTU and Modbus TCP Protocols - UPS Systems159 Liebert® IntelliSlot® Modbus/BACnetTable 51 Liebert GXT2™ and Liebert GXT3™ - Input and HoldingDa
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 160Output Current L1 30164 — 1 — AInput Maximum Voltage L1 30180
Modbus RTU and Modbus TCP Protocols - UPS Systems161 Liebert® IntelliSlot® Modbus/BACnetTable 54 Liebert Nfinity® - Status and CoilData DescriptionSta
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 162Table 55 Liebert Nfinity® - Input and HoldingData DescriptionI
Modbus RTU and Modbus TCP Protocols - UPS Systems163 Liebert® IntelliSlot® Modbus/BACnetTable 56 Liebert NX™ - Status and CoilData DescriptionStatus C
Modbus RTU and Modbus TCP Protocols - Thermal Management Products11 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Over Temperature 1 10356 — 1 Ac
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 164DC Bus Balancer Fault 10240 — — — —DC Bus 1 Power Supply Fail
Modbus RTU and Modbus TCP Protocols - UPS Systems165 Liebert® IntelliSlot® Modbus/BACnetTable 57 Liebert NX™ - Input and HoldingData DescriptionInputR
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 166Input Current L1 30154 — 1 — AInput Power Factor L1 30155 — 1
Modbus RTU and Modbus TCP Protocols - UPS Systems167 Liebert® IntelliSlot® Modbus/BACnetTable 58 Liebert NX 225-600kVA UPS - Input and Holding3Data De
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 168OutputSource — 40050 1 —1 = Other2 = None3 = Normal4 = Bypass5
Modbus RTU and Modbus TCP Protocols - UPS Systems169 Liebert® IntelliSlot® Modbus/BACnetDiagnostic Test Failed — 40089 1 — Bit 3Communications Lost —
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 170Table 59 Liebert NXL™ - 60Hz, UL version (Model 40) - Status a
Modbus RTU and Modbus TCP Protocols - UPS Systems171 Liebert® IntelliSlot® Modbus/BACnetBattery Over Temperature 10350 — 1 Active on Warning N+1, 1+N,
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 172Controls Reset Required 10397 — 1 Active on Alarm SCC, N+1, 1+
Modbus RTU and Modbus TCP Protocols - UPS Systems173 Liebert® IntelliSlot® Modbus/BACnetTable 60 Liebert NXL™ - 60Hz, UL version (Model 40) - Input an
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 12EEV Unspecified General Event 10488 — 1 Activ
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 174System Output Pct Power Phase A 30165 — 1 — %N+1, 1+N,1+1, SMS
Modbus RTU and Modbus TCP Protocols - UPS Systems175 Liebert® IntelliSlot® Modbus/BACnetBattery Total Discharge Time 30316 — 1 — hrN+1, 1+N,1+1, SMSBa
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 176Rectifier Active Filter 30340 — 1 —0 = Not Installed1 = Instal
Modbus RTU and Modbus TCP Protocols - UPS Systems177 Liebert® IntelliSlot® Modbus/BACnetBattery Volts for Cabinet 4 30361 — 1 — VDCN+1, 1+N,1+1, SMSBa
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 178Maintenance Isolation Breaker (MIB)30383 — 1 —0 = Open1 = Clos
Modbus RTU and Modbus TCP Protocols - UPS Systems179 Liebert® IntelliSlot® Modbus/BACnetConfiguration Description 30497 — 1 —0 = Single Module System
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 180Sum of MMS Output RMS Currents for Phase B30512 — 1 — Units :
Modbus RTU and Modbus TCP Protocols - UPS Systems181 Liebert® IntelliSlot® Modbus/BACnetBypass Isolation Breaker forModule 1 (BIB1)30537 — 1 —0 = Open
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 182MMS Module Output VoltageStatus30557 — 1 —0 = Fail1 = Marginal
Modbus RTU and Modbus TCP Protocols - UPS Systems183 Liebert® IntelliSlot® Modbus/BACnetMMS Module Total kVA Output 30651 — 1 — Units : kVA SCCMMS Mod
Modbus RTU and Modbus TCP Protocols - Thermal Management Products13 Liebert® IntelliSlot® Modbus/BACnetExternal Condenser TVSS Issue 10655 — 1 Activ
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 184EcoModeSchedule 2Schedule Operation State - ECO Mode30682 — 1
Modbus RTU and Modbus TCP Protocols - UPS Systems185 Liebert® IntelliSlot® Modbus/BACnetTable 61 Liebert NXL™ - 60Hz, UL version (Model 40) - Glossary
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 186Battery Total Discharge Time The cumulative battery discharge
Modbus RTU and Modbus TCP Protocols - UPS Systems187 Liebert® IntelliSlot® Modbus/BACnetInlet Air Temperature The temperature of the inlet air Input
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 188Multiple Fan Failure Multiple fan failure On Generator A gen
Modbus RTU and Modbus TCP Protocols - UPS Systems189 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS Current Phase C The system input RMS current
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 190Table 62 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -
Modbus RTU and Modbus TCP Protocols - UPS Systems191 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Low Fault 10074 — 1 Active on AlarmOutputSystem S
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 192Internal Communications Failure 10176 — 1 Active on AlarmUPS O
Modbus RTU and Modbus TCP Protocols - UPS Systems193 Liebert® IntelliSlot® Modbus/BACnetTable 63 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 14Condenser Fan Issue 1 10723 — 1 Active on Ala
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 194Battery Volts for Cabinet 4 30428 — 1 —Units : VDCUint16Batter
Modbus RTU and Modbus TCP Protocols - UPS Systems195 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Voltage 30465 — 1 —Units : VDCUint16DC Bus Curren
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 196InverterInverter Overload Time Remaining 30510 — 1 —Units : se
Modbus RTU and Modbus TCP Protocols - UPS Systems197 Liebert® IntelliSlot® Modbus/BACnetOutput Wire Configuration 30556 — 1 —0 = Two Wire (single phas
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 198RatingsBypass Nominal Voltage 30576 — 1 —Units : VACUint16Syst
Modbus RTU and Modbus TCP Protocols - UPS Systems199 Liebert® IntelliSlot® Modbus/BACnetModule Output Breaker 30609 — 1 —0 = Open1 = Close2 = Not Inst
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 200Module Output Breaker for Module 3 30646 — 1 —0 = Open1 = Clos
Modbus RTU and Modbus TCP Protocols - UPS Systems201 Liebert® IntelliSlot® Modbus/BACnetMMS UPS Output Source 30665 — 1 —1 = Other2 = Off3 = Normal4 =
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 202Intelligent ParallelingIntelligent Parallel Operation State 30
Modbus RTU and Modbus TCP Protocols - UPS Systems203 Liebert® IntelliSlot® Modbus/BACnetEcoModeSchedule 14Schedule Operation State - ECO Mode 31019 —
Modbus RTU and Modbus TCP Protocols - Thermal Management Products15 Liebert® IntelliSlot® Modbus/BACnetTable 8 Liebert Challenger 3000™, Liebert Chall
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 204Table 64 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) -
Modbus RTU and Modbus TCP Protocols - UPS Systems205 Liebert® IntelliSlot® Modbus/BACnetBattery Time Remaining The calculated available time on batter
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 206DC Bus VoltageThe voltage between the positive and negative te
Modbus RTU and Modbus TCP Protocols - UPS Systems207 Liebert® IntelliSlot® Modbus/BACnetInverter Overload Phase B Inverter is operating with an overlo
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 208MMS Output Power The sum total power of all system output modu
Modbus RTU and Modbus TCP Protocols - UPS Systems209 Liebert® IntelliSlot® Modbus/BACnetProgram Input Contact 04When the signal from [Program Input Co
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 210Sum of MMS Output RMS Currents for Phase CThe sum of the multi
Modbus RTU and Modbus TCP Protocols - UPS Systems211 Liebert® IntelliSlot® Modbus/BACnetSystem Output Power The sum total power of all system output p
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 212Table 65 Liebert PowerSure™ Interactive (before July 2008) - S
Modbus RTU and Modbus TCP Protocols - UPS Systems213 Liebert® IntelliSlot® Modbus/BACnetTable 66 Liebert PowerSure™ Interactive (before July 2008) - I
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 16Return Air Over Temp Threshold 30739 40739 1 10
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 214Table 67 Liebert PowerSure™ Interactive 2 - Status and CoilApp
Modbus RTU and Modbus TCP Protocols - UPS Systems215 Liebert® IntelliSlot® Modbus/BACnetTable 68 Liebert PowerSure™ Interactive 2 - Input and HoldingA
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 216Table 69 Liebert Series 300™ UPS - Status and CoilData Descrip
Modbus RTU and Modbus TCP Protocols - UPS Systems217 Liebert® IntelliSlot® Modbus/BACnetTable 70 Liebert Series 300™ UPS - Input and HoldingData Descr
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 218Bypass Current L2 30210 — 1 — AOutput Voltage L2 30213 — 1 — V
Modbus RTU and Modbus TCP Protocols - UPS Systems219 Liebert® IntelliSlot® Modbus/BACnetTable 71 Liebert Series 600™ UPS - Status and CoilData Descrip
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 220Table 72 Liebert Series 600™ UPS - Input and HoldingData Descr
Modbus RTU and Modbus TCP Protocols - UPS Systems221 Liebert® IntelliSlot® Modbus/BACnetTable 73 Liebert Series 610™ SCC UPS - Status and CoilData Des
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 222Table 74 Liebert Series 610 SCC UPS - Input and HoldingData De
Modbus RTU and Modbus TCP Protocols - UPS Systems223 Liebert® IntelliSlot® Modbus/BACnetTable 75 Liebert HiPulse™, Liebert SICE 7200™- Input and Holdi
Modbus RTU and Modbus TCP Protocols - Thermal Management Products17 Liebert® IntelliSlot® Modbus/BACnetFan Speed 30103 — 1 — %1, 2, 3, 4, 5, 6, 7, 8,
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 224Rectifier Block — 40290 1 — Bit 7Rectifier Current Limit — 402
Modbus RTU and Modbus TCP Protocols - UPS Systems225 Liebert® IntelliSlot® Modbus/BACnetTable 76 Liebert SICE 7200™ - Input and Holding - SSCControlle
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 226Output Undervoltage — 40290 1 — Bit 7Output Waveform Error — 4
Modbus RTU and Modbus TCP Protocols - UPS Systems227 Liebert® IntelliSlot® Modbus/BACnetTable 77 Liebert Npower™ - Input and Holding - IMPController S
Modbus RTU and Modbus TCP Protocols - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 228Equipment Over Temperature — 40290 1 —Bit 0Any of Battery / He
Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products229 Liebert® IntelliSlot® Modbus/BACnet3.4 Battery Monitoring ProductsTable 78 Alber®
Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 230Thermal Runaway Charger Current Level One Even
Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products231 Liebert® IntelliSlot® Modbus/BACnetTable 79 Alber® BDSU™ - Input and HoldingData
Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 232Cell to Cell Temperature Deviation ThresholdSt
Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products233 Liebert® IntelliSlot® Modbus/BACnetCell Temperature Low Global ThresholdString 1
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 18Return Humidity 30130 — 1 10 % RH1, 2, 3, 4, 5,
Modbus RTU and Modbus TCP Protocols - Battery Monitoring ProductsLiebert® IntelliSlot® Modbus/BACnet 234Cell to Ambient Temperature Deviation Threshol
Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products235 Liebert® IntelliSlot® Modbus/BACnetCell TemperatureCell 321 – 36039195-39234 — 1
BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 2364.0 BACNET COMMUNICATIONS4.1 BACnet
BACnet Communications - BACnet Protocol Implementation Conformance Statement237 Liebert® IntelliSlot® Modbus/BACnet4.1.2 Supported ServicesServiceOrig
BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 2384.1.3 Standard Object Types Support
BACnet Communications - BACnet Protocol Implementation Conformance Statement239 Liebert® IntelliSlot® Modbus/BACnet4.1.4 Object PropertiesThe followin
BACnet Communications - BACnet Protocol Implementation Conformance StatementLiebert® IntelliSlot® Modbus/BACnet 240Analog ObjectUnitsPossible values o
BACnet Communications - BACnet Protocol Implementation Conformance Statement241 Liebert® IntelliSlot® Modbus/BACnetBinary Object PropertiesMultistate
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 2424.2 Thermal Management ProductsTable 80 Liebert Challenger 3
BACnet Communications - Thermal Management Products243 Liebert® IntelliSlot® Modbus/BACnetCompressor Hours Exceeded Binary_Value 77 5269_1_1 RD Active
Modbus RTU and Modbus TCP Protocols - Thermal Management Products19 Liebert® IntelliSlot® Modbus/BACnetSupply Air Temperature Sensor Control30262 4026
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 244Free Cooling Valve Hours ExceededBinary_Value 117 5306_1 RD
BACnet Communications - Thermal Management Products245 Liebert® IntelliSlot® Modbus/BACnetFanFan Hours Exceeded Binary_Value 205 5054_1 RD Active on A
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 246High Power Shutdown Binary_Value 268 5121_1 RD Active on Ala
BACnet Communications - Thermal Management Products247 Liebert® IntelliSlot® Modbus/BACnetSystem Events - iCOM DO Board 1Digital Output Board Not Dete
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 248Remote Sensors - Remote Sensor 5Remote Sensor Over Temperatu
BACnet Communications - Thermal Management Products249 Liebert® IntelliSlot® Modbus/BACnetStatic PressureStatic Pressure Sensor Issue Binary_Value 563
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 250Liebert Condensers (Previously called Global Condensers)Cond
BACnet Communications - Thermal Management Products251 Liebert® IntelliSlot® Modbus/BACnetCondenser Supply Refrigerant Under TempBinary_Value 1113 554
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 252Table 82 Liebert Challenger 3000™, Liebert Challenger ITR™,
BACnet Communications - Thermal Management Products253 Liebert® IntelliSlot® Modbus/BACnetAir - Return AirReturn Air Temperature Analog_Value 31 4291_
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 20Maintenance Tracking State 30286 — 1 —0 = off1
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 254HumidityReturn Humidity Analog_Value 60 5028_1 RD Units: % R
BACnet Communications - Thermal Management Products255 Liebert® IntelliSlot® Modbus/BACnetCompressors - Compressor 1Compressor Hours Analog_Value 97 5
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 256Reheat - Electric Reheater 1Electric Reheater Hours Analog_V
BACnet Communications - Thermal Management Products257 Liebert® IntelliSlot® Modbus/BACnetAnalog Inputs 3Analog Input Reading Analog_Value 246 5378_3
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 258Dew Point Set Point Analog_Value 10295 5575_1_deg_F RW Units
BACnet Communications - Thermal Management Products259 Liebert® IntelliSlot® Modbus/BACnetRemote Sensors - Remote Sensor 3Remote Sensor Temperature An
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 260Pump Hours Analog_Value 526 5298_1_2 RW Units: hr 7, 8, 9Pow
BACnet Communications - Thermal Management Products261 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS B-C Analog_Value 1922 4099_3 RD Units: VAC
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 262System Input RMS B-C Analog_Value 1952 4099_6 RD Units: VAC
BACnet Communications - Thermal Management Products263 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode - Full DaysAnalog_Value 534 5551_1_
Modbus RTU and Modbus TCP Protocols - Thermal Management Products21 Liebert® IntelliSlot® Modbus/BACnetExt Loss of Flow - Event Type 30306 40306 1 —0
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 264Liebert Condensers - Condenser 2 Fan 2Condenser Fan Speed An
BACnet Communications - Thermal Management Products265 Liebert® IntelliSlot® Modbus/BACnetTable 84 Liebert Challenger 3000™, Liebert Challenger ITR™,
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 266FanFan Control Mode MultiState_Value 82 5373_1 RW1 = Auto2 =
BACnet Communications - Thermal Management Products267 Liebert® IntelliSlot® Modbus/BACnetSystem Event ConfigurationCustomer Input 1 - Event ControlMu
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 268Ext Over Temperature - Event ControlMultiState_Value 146 509
BACnet Communications - Thermal Management Products269 Liebert® IntelliSlot® Modbus/BACnetClogged Air Filter - Event ControlMultiState_Value 166 5135_
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 270Compressor Low Suction Pressure - Event TypeMultiState_Value
BACnet Communications - Thermal Management Products271 Liebert® IntelliSlot® Modbus/BACnetHigh Return Humidity - Event TypeMultiState_Value 235 5138_1
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 272System EventsSystem Event Acknowledge/ResetMultiState_Value
BACnet Communications - Thermal Management Products273 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Force Max Fan/Cooling - Ext ControlMultiState_Val
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 22Ext Compressor Lockout - Event Type30326 40326
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 274Table 86 Liebert Challenger 3000™, Liebert Challenger ITR™,
BACnet Communications - Thermal Management Products275 Liebert® IntelliSlot® Modbus/BACnetChilled Water Control Valve FailureChilled water valve out o
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 276Compressor HoursOperating hours for compressor since last re
BACnet Communications - Thermal Management Products277 Liebert® IntelliSlot® Modbus/BACnetCondenser Issue - Event Type The event type for the [Condens
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 278Cooling Control TemperatureTemperature value being used for
BACnet Communications - Thermal Management Products279 Liebert® IntelliSlot® Modbus/BACnetDigital Scroll Compressor LoadingPresent digital scroll comp
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 280Ext Air Sensor A Under Temp - Event ControlEnable/disable th
BACnet Communications - Thermal Management Products281 Liebert® IntelliSlot® Modbus/BACnetExt Loss of Air Blower Loss of air blower is detected, as in
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 282Fan Issue - Event ControlEnable/disable the activation of th
BACnet Communications - Thermal Management Products283 Liebert® IntelliSlot® Modbus/BACnetHigh Return Humidity - Event ControlEnable/disable the activ
Modbus RTU and Modbus TCP Protocols - Thermal Management Products23 Liebert® IntelliSlot® Modbus/BACnetCompressor Short Cycle - Event Type 230346 4034
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 284Humidity Proportional Control TypeType of algorithm to use f
BACnet Communications - Thermal Management Products285 Liebert® IntelliSlot® Modbus/BACnetPump State Pump operational state.Pump Unspecified General E
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 286Return Air Under Temp - Event ControlEnable/disable the acti
BACnet Communications - Thermal Management Products287 Liebert® IntelliSlot® Modbus/BACnetSupply Air Under Temp ThresholdThreshold value used in the [
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 288Unit Partial Shutdown An event has occurred requiring some s
BACnet Communications - Thermal Management Products289 Liebert® IntelliSlot® Modbus/BACnetTable 87 Liebert CRV™ - Binary DataController Liebert iCOM®
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 290Remote Sensors 10Remote Sensor Issue Binary_Value 151 5060_1
BACnet Communications - Thermal Management Products291 Liebert® IntelliSlot® Modbus/BACnetUnit Partial Shutdown Binary_Value 237 5112_1 RD Active on A
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 292Table 88 Liebert CRV™ - Analog DataController Liebert iCOM®
BACnet Communications - Thermal Management Products293 Liebert® IntelliSlot® Modbus/BACnetRemote Sensors 1Remote Sensor Temperature Analog_Value 56 5
iTABLE OF CONTENTS1.0 LIEBERT EQUIPMENT COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.1 What’s Ne
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 24Low Return Humidity - Event Type 30366 40366 1
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 294 Condenser Low Noise Mode - Interval Days Analog_Value 287
BACnet Communications - Thermal Management Products295 Liebert® IntelliSlot® Modbus/BACnetTable 89 Liebert CRV™ - Multistate DataController Liebert iC
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 296Event ConfigurationSystem Event Acknowledge/Reset MultiStat
BACnet Communications - Thermal Management Products297 Liebert® IntelliSlot® Modbus/BACnetExt Reheat Lockout - Event Type MultiState_Value 191 5085_1
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 298Table 90 Liebert CRV™ - GlossaryData Label Data DescriptionA
BACnet Communications - Thermal Management Products299 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode Stop Time The time of day at which
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 300Customer Input 3 - Event Type The event type for the [Custo
BACnet Communications - Thermal Management Products301 Liebert® IntelliSlot® Modbus/BACnetFan Hours Exceeded Operating hours for the unit blower fan
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 302Remote Sensor Temperature Calculation Calculation method app
BACnet Communications - Thermal Management Products303 Liebert® IntelliSlot® Modbus/BACnetSystem Operating State Current operating state of the syste
Modbus RTU and Modbus TCP Protocols - Thermal Management Products25 Liebert® IntelliSlot® Modbus/BACnetOutside Air Temperature 30484 — 1 10 deg C2, 3,
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 304Table 91 Liebert HPC™ - Binary DataController Liebert iCOM®
BACnet Communications - Thermal Management Products305 Liebert® IntelliSlot® Modbus/BACnetFluid - Supply (Outlet) FluidSupply Fluid Over Temp Binary_V
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 306Table 92 Liebert HPC™ - Analog DataController Liebert iCOM®
BACnet Communications - Thermal Management Products307 Liebert® IntelliSlot® Modbus/BACnetFree CoolingFree Cooling External Temperature Delta Analog_V
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 308Table 93 Liebert HPC™ - Multistate DataController Liebert iC
BACnet Communications - Thermal Management Products309 Liebert® IntelliSlot® Modbus/BACnetTable 94 Extra NotesNumber Description1This point is support
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 310Customer Input 1 Customer input 1.Customer Input 2 Customer
BACnet Communications - Thermal Management Products311 Liebert® IntelliSlot® Modbus/BACnetPump Hours Threshold Threshold value used in the [Pump Hours
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 312Table 96 Liebert XDP™, Liebert XDC™ - Binary DataController
BACnet Communications - Thermal Management Products313 Liebert® IntelliSlot® Modbus/BACnetXD System 1Ext System Condensation Detected Binary_Value 112
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 26Actual Humidity Set Point 30502 — 1 — % RH2, 3,
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 314Table 97 Liebert XDP™, Liebert XDC™ - Analog DataController
BACnet Communications - Thermal Management Products315 Liebert® IntelliSlot® Modbus/BACnetXD System 1 Temperature Sensor 4Remote Sensor Temperature An
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 316Table 98 Liebert XDP™, Liebert XDC™ - Multistate DataControl
BACnet Communications - Thermal Management Products317 Liebert® IntelliSlot® Modbus/BACnetRefrigerantSupply Refrig Over Temp - Event Control Multistat
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 318CompressorsCompressor 1A State Multistate_Value 91 4665_1 RD
BACnet Communications - Thermal Management Products319 Liebert® IntelliSlot® Modbus/BACnetCircuit 2 Low Suction Pressure - EventTypeMultistate_Value 1
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 320Fan Button Control Multistate_Value 175 5488_2 RW1 = Enabled
BACnet Communications - Thermal Management Products321 Liebert® IntelliSlot® Modbus/BACnetSensor Issue - Event Type Multistate_Value 812 5499_20 RW1 =
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 322Smoke Detected - Event Type Multistate_Value 859 4722_1 RW1
BACnet Communications - Thermal Management Products323 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Temp Out of RangeThe air temperature in the cold
Modbus RTU and Modbus TCP Protocols - Thermal Management Products27 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Temperature 5 30555 — 1 10 deg C2
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 324Compressor 2B Short Cycle - Event ControlEnable/disable the
BACnet Communications - Thermal Management Products325 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor B Temperature Air temperature as measured by
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 326Hot Gas Valve 2 Open Position Hot gas valve 2 open position.
BACnet Communications - Thermal Management Products327 Liebert® IntelliSlot® Modbus/BACnetShutdown - Loss Of PowerSystem lost power. This event become
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 328Supply Refrig Temp Sensor Issue - Event TypeThe event type f
BACnet Communications - Thermal Management Products329 Liebert® IntelliSlot® Modbus/BACnetTable 100 Liebert DataMate™, Liebert Mini-Mate2™ - MM2Contro
BACnet Communications - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 330Table 101 Liebert Mini-Mate2™ 8 Ton - L8TController L8TLiebe
BACnet Communications - UPS Systems331 Liebert® IntelliSlot® Modbus/BACnet4.3 UPS SystemsTable 102 Liebert APM™, Liebert NXC™, Liebert NXR™ - Binary D
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 332Power Sub Module Fault Binary_Value 51 5158_1 RD Active on AlarmBattery Disc
BACnet Communications - UPS Systems333 Liebert® IntelliSlot® Modbus/BACnetSystem Output RMS Current Phs B Analog_Value 57 4205_1 RD Units: A AC Syste
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 28Digital Scroll Compressor Loading 2 30669 — 1 —
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 334Table 105 Liebert APM™, Liebert NXC™, Liebert NXR™ - GlossaryData Label Data
BACnet Communications - UPS Systems335 Liebert® IntelliSlot® Modbus/BACnetLoad Sharing Fault Difference between any phase inverter current of unit and
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 336System Output Pct Power Phase B The system output power on phase B as a perc
BACnet Communications - UPS Systems337 Liebert® IntelliSlot® Modbus/BACnetTable 106 Liebert APS™ - Binary DataData LabelObject Type InstanceObjectName
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 338PowerModule 1Power Module Fan Fault Binary_Value 99 5838_1 RD Active on Ala
BACnet Communications - UPS Systems339 Liebert® IntelliSlot® Modbus/BACnetTable 107 Liebert APS™ - Analog DataData LabelObject Type Instance Object Na
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 340System Output Apparent Power L2 Analog_Value 71 5869_1 RD Units: kVA System
BACnet Communications - UPS Systems341 Liebert® IntelliSlot® Modbus/BACnetTable 108 Liebert APS™ - Multistate DataData LabelObject Type Instance Objec
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 342Auto Restart Minimum Battery Setting MultiState_Value 64 5832_1 RW1 = 0%2 =
BACnet Communications - UPS Systems343 Liebert® IntelliSlot® Modbus/BACnetTable 109 Liebert APS™ - GlossaryData Label Data DescriptionAccumulated Disc
Modbus RTU and Modbus TCP Protocols - Thermal Management Products29 Liebert® IntelliSlot® Modbus/BACnetSystem Input RMS C-N 3 30822 — 1 10 VAC 5System
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 344DC Bus Current The current at the battery input terminals. In charging mode,
BACnet Communications - UPS Systems345 Liebert® IntelliSlot® Modbus/BACnetOutput Load on Maint. Bypass The output power is supplied by the maintenanc
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 346System Output Off The system output is off System Output Pct Power L1 The s
BACnet Communications - UPS Systems347 Liebert® IntelliSlot® Modbus/BACnetTable 110 Liebert NXL™- 60Hz, UL version (Model 40) - Binary DataData LabelO
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 348Battery Self Test Binary_Value 46 4741_1 RD Active on AlarmSMS, 1+N, N+1Mai
BACnet Communications - UPS Systems349 Liebert® IntelliSlot® Modbus/BACnetOutput Amp Over User Limit-Phs A Binary_Value 91 4286_1 RD Active on AlarmS
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 350Input Contact 09 Binary_Value 146 4278_1 RD Active on AlarmSMS, 1+N, N+1, S
BACnet Communications - UPS Systems351 Liebert® IntelliSlot® Modbus/BACnetInput Filter Cycle Lock Binary_Value 192 4755_1 RD Active on AlarmSMS, 1+N,
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 352Table 111 Liebert NXL™ - 60Hz, UL version (Model 40) - Analog DataData Label
BACnet Communications - UPS Systems353 Liebert® IntelliSlot® Modbus/BACnetBattery Volts for Cabinet 8 Analog_Value 45 4155_1_8 RD Units: VDCSMS, 1+N,
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 30Fluid Input Temperature 2 30901 — 1 10 deg C 5F
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 354DC BusDC Bus Voltage Analog_Value 72 4148_1 RD Units: VDCSMS, 1+N, N+1DC Bu
BACnet Communications - UPS Systems355 Liebert® IntelliSlot® Modbus/BACnetEnvironmentInlet Air Temperature Analog_Value 126 4291_1 RD Units: deg CSMS
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 356MultiModuleMulti-module System Output Voltage RMS A-B Analog_Value 177 4801_
BACnet Communications - UPS Systems357 Liebert® IntelliSlot® Modbus/BACnet ModuleList 2MMS Module Total kW Output Analog_Value 226 4861_2 RD Units: k
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 358Table 112 Liebert NXL™ - 60Hz, UL version (Model 40) - Multistate DataData L
BACnet Communications - UPS Systems359 Liebert® IntelliSlot® Modbus/BACnetSystemUPS Module Type MultiState_Value 84 4303_1 RD1 = Single ModuleSystem2
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 360System Status MultiState_Value 91 4123_1 RD1 = Normal Operation2 = StartUp 3
BACnet Communications - UPS Systems361 Liebert® IntelliSlot® Modbus/BACnetMultiModuleModule Output Breaker for Module 1 (MOB1) MultiState_Value 137 48
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 362SCC Event Summary MultiState_Value 156 4855_1 RD1 = None2 = Alarm3 = Fault
BACnet Communications - UPS Systems363 Liebert® IntelliSlot® Modbus/BACnetMMS Module Output Voltage Status MultiState_Value 277 4859_8 RD1 = Fail2 = M
Modbus RTU and Modbus TCP Protocols - Thermal Management Products31 Liebert® IntelliSlot® Modbus/BACnetPump State 2 31110 — 1 —0 = off1 = on8, 9Expect
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 364Table 113 Liebert NXL™ - 60Hz, UL version (Model 40) - GlossaryData Label Da
BACnet Communications - UPS Systems365 Liebert® IntelliSlot® Modbus/BACnetBattery Time Remaining The calculated available time on battery Battery Tot
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 366Continuous Operation - ECO Mode This setting gives the user the ability to E
BACnet Communications - UPS Systems367 Liebert® IntelliSlot® Modbus/BACnetIntelligent Parallel Minimum Redundancy This is the minimum Number of Redund
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 368MMS Module DC Bus Voltage DC bus voltage of this module in a multi-module s
BACnet Communications - UPS Systems369 Liebert® IntelliSlot® Modbus/BACnetMulti-module System Output Voltage RMS A-N Multi-module system output RMS v
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 370SCC Event Summary Summary of any active user alarms or faults on the SCC Sc
BACnet Communications - UPS Systems371 Liebert® IntelliSlot® Modbus/BACnetSystem Output Frequency The system output frequency System Output Low Power
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 372Table 114 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Binary DataDat
BACnet Communications - UPS Systems373 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Low Fault Binary_Value 74 5563_1 RD Active on AlarmOutputSystem
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 32Table 9 Extra notes key to Table 8NumberDescrip
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 374SystemSystem Fan Failure - Redundant Binary_Value 174 4749_1 RD Active on Al
BACnet Communications - UPS Systems375 Liebert® IntelliSlot® Modbus/BACnetIntelligent ParallelingIP Inhibit Binary_Value 251 5567_1 RD Active on Alarm
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 376Table 115 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Analog DataDat
BACnet Communications - UPS Systems377 Liebert® IntelliSlot® Modbus/BACnetDC BusDC Bus Voltage Analog_Value 66 4148_1 RD Units: VDCDC Bus Current Anal
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 378MultiModuleMulti-module System Output Voltage RMS A-B Analog_Value 155 4801_
BACnet Communications - UPS Systems379 Liebert® IntelliSlot® Modbus/BACnetTable 116 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Multistate Dat
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 380SystemUPS Module Type MultiState_Value 87 4303_1 RD1 = Single Module System2
BACnet Communications - UPS Systems381 Liebert® IntelliSlot® Modbus/BACnetConfiguration Description MultiState_Value 91 4751_1 RD1 = Single Module Sys
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 382RatingsInput Isolation Transformer MultiState_Value 109 4266_1 RD1 = Not Ins
BACnet Communications - UPS Systems383 Liebert® IntelliSlot® Modbus/BACnetModule Output Breaker for Module 7 MultiState_Value 147 4842_1 RD1 = Open2 =
Modbus RTU and Modbus TCP Protocols - Thermal Management Products33 Liebert® IntelliSlot® Modbus/BACnetTable 10 Liebert Challenger 3000™, Liebert Chal
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 384ModuleList 1MMS Inter-Module Comm Status MultiState_Value 173 4856_1 RD1 = F
BACnet Communications - UPS Systems385 Liebert® IntelliSlot® Modbus/BACnetECO ModeECO Mode Operation State MultiState_Value 304 5454_1 RW1 = disabled2
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 386Table 117 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—GlossaryData L
BACnet Communications - UPS Systems387 Liebert® IntelliSlot® Modbus/BACnetBattery Volts at Main DisconnectThe voltage between the positive and the neg
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 388ECO Mode Operation State This setting is used to enable or disable ECO Mode.
BACnet Communications - UPS Systems389 Liebert® IntelliSlot® Modbus/BACnetInverter Overload Phase C Inverter is operating with an overload on phase CI
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 390MMS Output Power The sum total power of all system output modulesMMS Overloa
BACnet Communications - UPS Systems391 Liebert® IntelliSlot® Modbus/BACnetProgram Input Contact 03When the signal from [Program Input Contact 03] is a
BACnet Communications - UPS SystemsLiebert® IntelliSlot® Modbus/BACnet 392Sum of MMS Output RMS Currents for Phase AThe sum of the multi-module system
BACnet Communications - UPS Systems393 Liebert® IntelliSlot® Modbus/BACnetSystem Output Pct Pwr (VA) Phs BThe system output apparent power on phase B
iiTable 18 Liebert XDC™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Table 19 Liebe
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 34BMS Timeout PeriodTimeframe within which the Bu
While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disc
Modbus RTU and Modbus TCP Protocols - Thermal Management Products35 Liebert® IntelliSlot® Modbus/BACnetCompressor High Pressure Transducer IssueCompre
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 36Condenser Fan Reversal Requested Request the co
Modbus RTU and Modbus TCP Protocols - Thermal Management Products37 Liebert® IntelliSlot® Modbus/BACnetCooling Control TemperatureTemperature value be
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 38Dig Scroll Comp Over TempDigital scroll compres
Modbus RTU and Modbus TCP Protocols - Thermal Management Products39 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor A Over Temp - Event TypeThe even
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 40Ext Humidifier Lockout - Event ControlEnable/di
Modbus RTU and Modbus TCP Protocols - Thermal Management Products41 Liebert® IntelliSlot® Modbus/BACnetExternal Condenser TVSS IssueThe condenser Tran
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 42Free Cooling Internal Temperature DeltaMinimum
Modbus RTU and Modbus TCP Protocols - Thermal Management Products43 Liebert® IntelliSlot® Modbus/BACnetHumidifier Issue - Event ControlEnable/disable
iiiTable 52 Liebert HiNet™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160Table 53 Liebe
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 44Main Fan Overload Main fan is shut down due to
Modbus RTU and Modbus TCP Protocols - Thermal Management Products45 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor System Average TemperatureAverage
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 46Shutdown - Loss Of Power - Event Type The event
Modbus RTU and Modbus TCP Protocols - Thermal Management Products47 Liebert® IntelliSlot® Modbus/BACnetSystem Operating State Current operating state
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 48Table 11 Liebert CRV™ - Status and CoilControll
Modbus RTU and Modbus TCP Protocols - Thermal Management Products49 Liebert® IntelliSlot® Modbus/BACnetSupply Chilled Water Over Temp 10047 — 1 — Acti
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 50Table 12 Liebert CRV™ - Input and HoldingContro
Modbus RTU and Modbus TCP Protocols - Thermal Management Products51 Liebert® IntelliSlot® Modbus/BACnetRemote Sensor Temperature Module Index 4 30427
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 52Fan Control Sensor 30463 40463 1 —0 = Supply1 =
Modbus RTU and Modbus TCP Protocols - Thermal Management Products53 Liebert® IntelliSlot® Modbus/BACnetCondenser Low Noise Mode Schedule Control 3049
ivTable 82 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert DeluxeSystem/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert P
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 54Table 13 Liebert CRV™ - GlossaryController Lieb
Modbus RTU and Modbus TCP Protocols - Thermal Management Products55 Liebert® IntelliSlot® Modbus/BACnetCondenser Refrigerant Pressure Over Threshold C
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 56Fan Speed Proportional Band Temperature control
Modbus RTU and Modbus TCP Protocols - Thermal Management Products57 Liebert® IntelliSlot® Modbus/BACnetReturn Air Over Temp Threshold Threshold value
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 58Table 14 Liebert HPC™ (Chiller) - Status and Co
Modbus RTU and Modbus TCP Protocols - Thermal Management Products59 Liebert® IntelliSlot® Modbus/BACnetFluidLow Fluid Pressure 10070 — 1 Active on Ala
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 60Table 15 Liebert HPC™ (Chiller) - Input and Hol
Modbus RTU and Modbus TCP Protocols - Thermal Management Products61 Liebert® IntelliSlot® Modbus/BACnetCondensers 4Condenser Fan Speed 30417 — 1 —Unit
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 62EvaporatorsEvaporator Return Fluid Temperature
Modbus RTU and Modbus TCP Protocols - Thermal Management Products63 Liebert® IntelliSlot® Modbus/BACnetSystem OperationsReturn Fluid Temperature 30491
Liebert Equipment Compatibility - What’s New in This Manual1Liebert® IntelliSlot® Modbus/BACnet1.0 LIEBERT EQUIPMENT COMPATIBILITY1.1 What’s New in Th
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 64Table 16 Extra notes key to Table 15NumberDescr
Modbus RTU and Modbus TCP Protocols - Thermal Management Products65 Liebert® IntelliSlot® Modbus/BACnetEvaporator Fluid Freeze - Auto ResetEvaporator
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 66Reheat UtilizationPresent reheating utilization
Modbus RTU and Modbus TCP Protocols - Thermal Management Products67 Liebert® IntelliSlot® Modbus/BACnetTable 18 Liebert XDC™ - Status and CoilControll
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 68Table 19 Liebert XDC™ - Input and HoldingContro
Modbus RTU and Modbus TCP Protocols - Thermal Management Products69 Liebert® IntelliSlot® Modbus/BACnetSystem Status 30422 — 1 —1 = Normal Operation2
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 70Table 20 Liebert XDP™ - Status and CoilControll
Modbus RTU and Modbus TCP Protocols - Thermal Management Products71 Liebert® IntelliSlot® Modbus/BACnetXD System 2Ext System Condensation Detected 100
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 72Table 21 Liebert XDP™ - Input and HoldingContro
Modbus RTU and Modbus TCP Protocols - Thermal Management Products73 Liebert® IntelliSlot® Modbus/BACnetExt Air Sensor B Dew Point Temp 30402 — 1 10 Un
Liebert Equipment Compatibility - Compatibility with Liebert EquipmentLiebert® IntelliSlot® Modbus/BACnet 21.3 Compatibility with Liebert EquipmentTab
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 74Ext Remote Shutdown - Event Type 30458 40458 1
Modbus RTU and Modbus TCP Protocols - Thermal Management Products75 Liebert® IntelliSlot® Modbus/BACnetCold Aisle Under Temp Threshold 30493 40493 1 —
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 76XD System 1 Temperature Sensor 4Remote Sensor T
Modbus RTU and Modbus TCP Protocols - Thermal Management Products77 Liebert® IntelliSlot® Modbus/BACnetXD System 4 Temperature Sensor 4Remote Sensor T
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 78XD System 7 Temperature Sensor 4Remote Sensor T
Modbus RTU and Modbus TCP Protocols - Thermal Management Products79 Liebert® IntelliSlot® Modbus/BACnetXD System 10 Temperature Sensor 4Remote Sensor
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 80XD System 13 Temperature Sensor 4Remote Sensor
Modbus RTU and Modbus TCP Protocols - Thermal Management Products81 Liebert® IntelliSlot® Modbus/BACnetXD System 16 Temperature Sensor 4Remote Sensor
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 82XD System 19 Temperature Sensor 4Remote Sensor
Modbus RTU and Modbus TCP Protocols - Thermal Management Products83 Liebert® IntelliSlot® Modbus/BACnetTable 22 Liebert XDP™ - GlossaryController Lieb
Liebert Equipment Compatibility - Compatibility with Liebert Equipment3Liebert® IntelliSlot® Modbus/BACnet• Power Distribution & Power Conditionin
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 84Ext Remote Shutdown Unit is shut down by a remo
Modbus RTU and Modbus TCP Protocols - Thermal Management Products85 Liebert® IntelliSlot® Modbus/BACnetSmoke Detected Smoke detected.Supply Chilled Wa
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 86Table 23 Liebert DS™ and Liebert PeX™ - Status
Modbus RTU and Modbus TCP Protocols - Thermal Management Products87 Liebert® IntelliSlot® Modbus/BACnetComp 1 Overload 10039 — 1 — —Comp 1 Pumpdown Fa
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 88HW/HG Hrs Exceeded 10087 — 1 — —Hum Hrs Exceed
Modbus RTU and Modbus TCP Protocols - Thermal Management Products89 Liebert® IntelliSlot® Modbus/BACnetTable 24 Liebert DS™ and Liebert PeX™ - Input a
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 90Electrical Heaters #1 Run Hours Threshold 3007
Modbus RTU and Modbus TCP Protocols - Thermal Management Products91 Liebert® IntelliSlot® Modbus/BACnetDaily Low Temp Time 30154 — — — Hh:mmDaily High
Modbus RTU and Modbus TCP Protocols - Thermal Management ProductsLiebert® IntelliSlot® Modbus/BACnet 92Table 25 Liebert XDF™ - Status and CoilControll
Modbus RTU and Modbus TCP Protocols - Thermal Management Products93 Liebert® IntelliSlot® Modbus/BACnetTable 26 Liebert XDF™ - Input and HoldingContro