NOTES
1. All switching devices are to be suitable for switching low current 24VDC. Minimum
recommended wire size is 18AWG stranded copper with 300V insulation.
All wiring and devices are field-supplied except where noted. See installation manual for
detailed installation procedures.
2. The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to 1A.
3. Multiple normally open (N.O.) REPO switches may be paralleled.
Multiple normally closed (N.C.) REPO switches may be connected in series. All lamps (if used)
are connected in parallel.
4. The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.
5. Customer alarms 1 through 4 are normally open (indicates alarm on contact closure). Customer
alarm 5 is normally closed (indicates alarm on contact opening).
6. For Liebert SiteScan connection, use #22 AWG shielded cable maximum distance 1000ft (300m).