Setting up the Host to Reference the I/O Rack
2
7
User Configured
Output
When checked, allows the user to enter a value for this pin which will
be used as the hold value in the event there is a watchdog failure of the
ControlWave. (AO ONLY)
If the power fail timeout has been configured, please see the note on
page 18 for more information.
NOTE: "Hold Last Output" and "User Configured Output" are
mutually exclusive. Either one may be configured for a particular pin,
but NOT both.
When all pins have been configured, click on [Done]. You can then proceed to configure another
board.
Digital Boards (ER_DI32, ER_DO32)
Some fields only appear in the Digital Output (DO) board and are not available for the Digital
Input (DI); these will be noted, below:
Digital Input Board Page