Event Message Help Text 113
16.0 EVENT MESSAGE HELP TEXT
Key:
ALL CAPS = event message displayed in the Event Display panel in the lower left corner of the LCD display.
Indented text = help text shown in the Display Panel in the lower right corner of LCD display.
BOLD = commands that are sent through the RS-232 port.
S1 SCR SHORT
Source 1 SCR Short.
One or more of the SCRs for Source 1 has shorted. Transferring between sources has been inhibited.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contiguous
United States contact Liebert Global Services, if available in your area. For international areas not covered by Liebert
Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already
full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
S2 SCR SHORT
Source 2 SCR Short.
One or more of the SCRs for Source 2 has shorted. Transferring between sources has been inhibited.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already
full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
S1 SCR OPEN
Source 1 SCR Open.
One or more SCRs on Source 1 is open. Transferring between sources has been inhibited.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contiguous
United States contact Liebert Global Services, if available in your area. For international areas not covered by Liebert
Global Services, the Liebert authorized distributor can provide technical support.
STS2 output has been transferred to Source 2.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already
full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
Seitenansicht 124
1 2 ... 120 121 122 123 124 125 126 127 128 129 130 ... 149 150

Kommentare zu diesen Handbüchern

Keine Kommentare

Unify Telefony uživatelské příručky

Začínající na L

Klepnutím na abecedu níže přejděte na úplný seznam modelů začínajících tímto písmenem

Modely Typ Dokumentu
L30250-F600-A733
Datový list   Unify optiPoint 420 standard, 6 stránky
L30250-F600-C187
Datový list   Unify OpenStage 30 T Lava, 8 stránky