Revision B.33 2/25/2011
Liebert Monitoring Group – Development
Page 2 of 149
Revision Level Updates:
Added: revision level update chart, HiPulse support, and NPower support
Revised NPower definition
Added support for HiMod LNA
Revised Modbus explanation (Hi Byte / Lo Byte)
Corrected NPower table (typing error)
Added support for DataMate
Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate
Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal
Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for
MM2
Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2.
Track issue 3576 – Make BacNet points consistent with Modbus Points.
Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and
GXT
Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for BACNet
and Modbus addressing on STS-2.
Added Remote shutdown alarm to LAM. Added Note about Alarms “BACNet auto
discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is
for units with or without PDU. Changed breaker status register for STS2 from bits1-8
to 0-7.
Added XDC Unit. Added control point note for units with on/off control as follows: Bit
0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these
registers as spares.
Corrected revision level and date in header on this document.
SMS – Added Scale factor for kVA & kW. Revised note on page 1 to state module
type rather than “SS2000 Hardware”.
Series 610 UPS – added note that Series 610 is the same as series 600. SC4-SM4
changed “Bypass Breaker Closed” alarm from “Bypass Breaker Open”. Added note to
LAM that iCOM w/native IGM also applies.
Nfinity UPS (pnf), Nx (pnx), STS-2 (st2) – deleted status and setpoint points that are
not displayed in SiteScan. XDC, XDP added scale factor notes for Ref, Fluid and CW
temps.
PMP – Local Alarm #1 was Load Alarm, Added Local Alarm #2, Corrected Modbus
addressing from 40290:04 to 40290:07
AC8 – Added Unit tables to reference library
MM2 – Corrected entire table due to MS Word problems.
Corrected major MS Word formatting problems throughout document.
Added iCOM DS unit for 2mb modules (small version), SM3 corrected reversed
Modbus addressing for kW & kVA. Noted that pages for Series 600 UPS also apply
to series 610.
Corrected alarm info for Npower (IMP) unit.
Corrected revision number in page header B.30 from B.9. Changed XDP unit
description on page 53 from XD. Corrected miscellaneous document formatting
errors. Added WDU definition back in document from accifental deletion.
Added local Alarms 2,3 &4 for MM2, L00 & LSM. Local alrm 3=High Water for MM2
Clarified LAM/iCOM program usage and added iCOM 16mb version. Added
examples and notes sections. Removed discontinued modules.
Removed General Alarm from iCOM_DS. Added Hi Water Humidifier Pan to L8T.
Moved Generator Disconnected from Alarm to Status in NX unit.