How to Assign a MODBUS Address Parameters • 11
LOP Lowest operating pressure (PA4 to P20 bar/ psi)
If the suction pressure comes down to this value, a low pressure alarm is
signaled with Low Pressure alarm LED (related to PrM parameter).
PHY Pressure alarm hysteresis (0.1 to 5.0 bar/ 1 to 72 PSI)
Alarm hysteresis to disable alarm signaling.
dML delta MOP-LOP (0 to 100%)
When a MOP alarm occurs, the valve will close at the dML percentage
every one second until the MOP alarm is active. When LOP occurs, the
valve will open at the dML percentage every one second until LOP
alarm is active.
MSH Maximum superheat alarm (LSH to 32.0°C/ LSH to 176°F)
When the superheat exceeds this value, a high superheat alarm is sig-
naled after interval SHd.
LSH Lowest superheat alarm (0.0 to MSH°C/ 32 to MSH°F)
When the superheat goes down to this value, a low superheat alarm is
signaled after interval SHd.
SHy Superheat alarm hysteresis (0.0 to 25.5°C/ 1 to 77°F)
Hysteresis for superheat alarm deactivation.
SHd Superheat alarm activation delay (0 to 255 sec)
When a superheat alarm occurs, the time SHd has to pass before signal-
ing alarm.
FrC Fast-recovery constant (0 to 100 sec)
Increases the integral time when SH is below the setpoint. If FrC = 0,
fast-recovery function is disabled.
DISPLAY
Lod Local display Display: (SH, PEr, P1, P2)
SH = superheat; PEr = valve opening percentage; P1 = value of temper-
ature measured; P2 = pressure measured by P2 probe;
CF Temperature measurement units (°C to °F)
°C = Celsius degree; °F = Fahrenheit degree
CAUTION! By changing the measurement unit, the regulation parame-
ters have to be changed correctly.
PMU Pressure measurement units (bAr, PSI)
bAr = bar; PSI = psi
CAUTION! By changing the measurement unit, the regulation parame-
ters have to be changed correctly.
rES Resolution (only °C) (dE to in)
Whether a whole number or decimal point is used in temperature reading
PrM Pressure visualization mode (rEL to AbS)
rEL = relative pressure; AbS = absolute pressure
All pressure parameters depend on this parameter.
CLP Cooling percentage (Read only)
Displays the percentage of time during which the cooling call was active
in the time interval defined by parameter CLt.
tP1 Temperature probe value (Read only)
Shows the temperature probe value from P1.
PPr Pressure probe value (Read only)
Shows the pressure probe value. The value depends on PrM.
tP2 Temperature from P2 Shows the temperature obtained from conversion of pressure value.
Code Description Function
Table 8-1 - List of Parameters