Seitenansicht 71
Reference Manual
300560EN, Rev AA
May 2011
Rosemount 2230
B-4
Appendix B. Product Certifications
B.3.2 Factory Mutual
Canadian Approvals
Certificate of Compliance: 3037177C.
Figure B-2. Factory Mutual
Intrinsic Safety Canadian
Approval Label
I6
FISCO Field Device (Fieldbus Terminals)
Intrinsically Safe for Class I, II, III Division 1, Groups A, B, C, D, E, F and G
Temperature Class T4, Ambient Temperature Limits: -50 °C to +70 °C
Ui=17.5V, Ii=380mA, Pi=5.32W, Ci=2.1nF, Li=1.1µH
Entity (Fieldbus Terminals)
Intrinsically Safe for Class I, II, III Division 1, Groups A, B, C, D, E, F and G
Temperature Class T4, Ambient Temperature Limits: -50 °C to +70 °C
Ui=30V, Ii=300mA, Pi=1.3W, Ci=2.1nF, Li=1.1µH
Install per Control Drawing 9240040-949
Special Conditions of Use
1. The associated apparatus through which the equipment is supplied shall
provide galvanic isolation between the input and output of the associated
apparatus.