20 Chapter 3 Operating Procedures
Liebert APM Modular UPS User & Installation Manual
Chapter 3 Operating Procedures
This chapter provides detailed operating procedures of the UPS.
All control keys and LED indication mentioned in these procedures are identified in
Chapter 4 Operator Control And
Display Panel
. Audible alarm may sound at various points during these procedures. It can be canceled at any time by
pressing the SILENCE ON/OFF key.
Warning: hazardous mains and battery voltage present behind covers
1. No user-serviceable parts are located behind covers that require a tool for their removal.
2. Only qualified service personnel are authorised to remove such covers.
3.1 Power Switches
As shown in Figure 3-1, opening the UPS front door reveals the power switches, including the input switch, output
switch, maintenance bypass switch (locked) and output distribution switches.
Output distribution switchesOutput distribution switches
Input switch
Output switch
Maintenance bypass
switch (locked)
Figure 3-1 Positions of power switches
3.2 UPS Start-Up Procedures
Before startup, the UPS must be fully installed and commissioned, and the external input breaker must be closed.
Once those general conditions are met, the UPS may be started.