Configuration and Use ManualMMI-20019043, Rev AAMarch 2012Micro Motion® Model 2700 Transmitters withAnalog OutputsConfiguration and Use Manual
Getting Started2 Micro Motion® Model 2700 Transmitters with Analog Outputs
Status alarms and Status Alarm SeverityTable 5-2: Alarm code Status message Default severity Notes Configurable?A001 EEPROM Error (Core Pro-cessor)F
Status alarms and Status Alarm Severity (continued)Table 5-2: Alarm code Status message Default severity Notes Configurable?A031 Low PowerFaultAppli
Status alarms and Status Alarm Severity (continued)Table 5-2: Alarm code Status message Default severity Notes Configurable?A114 mA Output 2 FixedIn
-Message-Date• Sensor parameters-Sensor Serial Number-Sensor Material-Sensor Liner Material-Sensor Flange Type5.6.1 Configure DescriptorDisplayNot ava
5.6.3 Configure DateDisplayNot availableProLink II ProLink > Configuration > Device > DateProLink III Device Tools > Configuration > In
5.6.5 Configure Sensor MaterialDisplayNot availableProLink II ProLink > Configuration > Sensor > Sensor MatlProLink III Device Tools > Con
5.6.7 Configure Sensor Flange TypeDisplayNot availableProLink II ProLink > Configuration > Sensor > FlangeProLink III Device Tools > Confi
6 Integrate the meter with the controlsystemTopics covered in this chapter:•Configure the transmitter channels•Configure the mA output•Configure the f
PostrequisitesFor each channel that you configured, perform or verify the corresponding input or outputconfiguration. When the configuration of a chan
• If you plan to configure an output to report a concentration measurement processvariable, ensure that the concentration measurement application is c
1 Before you beginTopics covered in this chapter:•About this manual•Transmitter model code•Communications tools and protocols•Additional documentation
Options for mA Output Process Variable (continued)Table 6-1: Process variable LabelDisplay ProLink II ProLink III Field CommunicatorConcentration me
ProcedureSet LRV and URV as desired.• LRV is the value of mA Output Process Variable represented by an output of 4 mA. Thedefault value for LRV depend
Default values for Lower Range Value (LRV) and Upper Range Value (URV)(continued)Table 6-2: Process variable LRV URVConcentration 0% 100%Baume 0 10S
Example: Cutoff interactionConfiguration:• mA Output Process Variable = Mass Flow Rate• Frequency Output Process Variable = Mass Flow Rate• AO Cutoff
NoteAdded Damping is not applied if the mA output is fixed (for example, during loop testing) or if the mAoutput is reporting a fault. Added Damping i
Result: A change in the mass flow rate will be reflected in the mA output over a time periodthat is greater than 3 seconds. The exact time period is c
Options for mA Output Fault Action and mA Output Fault Level (continued)Table 6-4: Option mA output behaviormA Output Fault LevelNoneTracks data for
OverviewFrequency Output Process Variable controls the variable that is reported over the frequencyoutput.PrerequisitesIf you plan to configure the ou
Options for Frequency Output Process Variable (continued)Table 6-5: Process variableLabelDisplay ProLink II ProLink III Field Communica-torNet mass
6.3.3 Configure Frequency Output Scaling MethodDisplay OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET FO > FO SCALEProLink II ProLin
Communications tools, protocols, and related informationTable 1-1: Communica-tions tool Supported protocols Scope In this manual For more informatio
NNumber of pulses per flow unit, as configured in the receiving deviceThe resulting Frequency Factor must be within the range of the frequency output
The ON signal may be the high voltage or 0.0 V, depending on Frequency Output Polarity.Interaction of Frequency Output Maximum Pulse Width and Frequen
NoteFor some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will notimplement the fault action until the time
•Discrete Output Polarity•Discrete Output Fault ActionRestrictionBefore you can configure the discrete output, you must configure a channel to operate
Options for Discrete Output Source (continued)Table 6-9: OptionLabelConditionDiscrete out-put voltageDisplay ProLink II ProLink IIIField Commu-nicat
Configure Flow Switch parametersDisplay OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > CONFIG FL SWProLink II • ProLink > Co
6.4.2 Configure Discrete Output PolarityDisplay OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > DO POLARProLink II ProLink >
Typical discrete output circuitFigure 6-1: A. 24 V (Nom)B.3.2 KΩC. Out+D. Out−6.4.3 Configure Discrete Output Fault ActionDisplayNot availableProL
ProcedureSet Discrete Output Fault Action as desired.The default setting is None.Options for Discrete Output Fault ActionOptions for Discrete Output F
6.5.1 Configure a basic eventDisplayNot availableProLink II ProLink > Configuration > EventsProLink III Device Tools > Configuration > Eve
Additional documentation and resources (continued)Table 1-2: Topic DocumentTransmitter installationMicro Motion Model 1700 and Model 2700 Transmitte
OverviewAn enhanced event is used to provide notification of process changes and, optionally, toperform specific transmitter actions if the event occu
Options for Enhanced Event ActionOptions for Enhanced Event ActionTable 6-12: Action LabelDisplay ProLink II ProLink III Field CommunicatorStandardN
6.6 Configure digital communicationsThe digital communications parameters control how the transmitter will communicateusing digital communications.You
2. Ensure Loop Current Mode (mA Output Action) is configured appropriately.Options DescriptionEnabledThe primary mA output reports process data as con
LabelDescriptionProLink II ProLink IIIField Communi-catorPrimary Variable Source (PrimaryVariable)PVThe transmitter sends the primaryvariable (PV) in
Options for HART variablesOptions for HART variablesTable 6-13: Process variable Primary Varia-ble (PV)SecondaryVariable (SV)Third Variable(TV)Fourt
Options for HART variables (continued)Table 6-13: Process variable Primary Varia-ble (PV)SecondaryVariable (SV)Third Variable(TV)Fourth Varia-ble (Q
6.6.2 Configure HART/RS-485 communicationsDisplay OFF-LINE MAINT > OFF-LINE CONFG > COMMProLink II ProLink > Configuration > Device > D
6.6.3 Configure Modbus/RS-485 communicationsDisplay OFF-LINE MAINT > OFF-LINE CONFG > COMMProLink II ProLink > Configuration > Device >
4. Set Parity, Stop Bits, and Baud Rate as appropriate for your network.5. Set Floating-Point Byte Order to match the byte order used by your Modbus h
Before you begin6 Micro Motion® Model 2700 Transmitters with Analog Outputs
OverviewDigital Communications Fault Action specifies the values that will be reported via digitalcommunications if the transmitter encounters an inte
CAUTION!If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set DigitalCommunications Fault Action to None. If you
Integrate the meter with the control system134 Micro Motion® Model 2700 Transmitters with Analog Outputs
7 Completing the configurationTopics covered in this chapter:•Test or tune the system using sensor simulation•Back up transmitter configuration•Enable
Option Required valuesSinePeriodMinimumMaximum4. For density, set Wave Form as desired and enter the required values.Option Required valuesFixedFixed
• All mass flow rate, temperature, and density values shown on the display orreported via outputs or digital communications• The mass total and mass i
7.3 Enable write-protection on the transmitterconfigurationDisplay OFF-LINE MAINT > CONFIG > LOCKProLink II ProLink > Configuration > Devi
8 Set up the Weights & MeasuresapplicationTopics covered in this chapter:•Weights & Measures application•Set up the Weights & Measures app
MetrologicalsecurityMetrological security protects the transmitter from all changes thatwould affect measurement. This includes changes to configurati
3. Set Approval to the appropriate regulatory agency for your application.Option DescriptionNTEPRegulatory agency for the U.S.A. and CanadaOIMLRegulat
2 Quick startTopics covered in this chapter:•Power up the transmitter•Check flowmeter status•Make a startup connection to the transmitter•Characterize
FVZ is a diagnostic variable that monitors the zero value over a period of 3 minutes.It must be read during meter commissioning to comply with MID req
8.3 Set up the Weights & Measures applicationusing ProLink IIIWhen your transmitter is set up to comply with OIML or NTEP requirements, and thetra
“Digital communications” refers to any method that uses Modbus or HARTcommunications to interact with the transmitter. This includes ProLink II, ProLi
9. Install the physical seal.ImportantIn most installations, the physical seal is a wire seal that must be installed by a certifiedWeights & Measu
Set up the Weights & Measures application146 Micro Motion® Model 2700 Transmitters with Analog Outputs
Part IIIOperations, maintenance, andtroubleshootingChapters covered in this part:•Transmitter operation•Operate the transmitter with the Weights &
Operations, maintenance, and troubleshooting148 Micro Motion® Model 2700 Transmitters with Analog Outputs
9 Transmitter operationTopics covered in this chapter:•Record the process variables•View process variables•View transmitter status using the status LE
9.2 View process variablesDisplay Scroll to the desired process variable. If AutoScroll is enabled, you can wait until the proc-ess variable is displa
Transmitter display featuresFigure 9-1: ABCDEFGHA. Status LEDB.Display (LCD panel)C. Process variableD. Scroll optical switchE. Optical switch indic
1. Wait approximately 10 seconds for the power-up sequence to complete.Immediately after power-up, the transmitter runs through diagnostic routines an
9.3 View transmitter status using the status LEDThe status LED shows the current alarm condition of the transmitter. The status LED islocated on the f
PrerequisitesOperator access to the alarm menu must be enabled (default setting). If operator access tothe alarm menu is disabled, you must use anothe
Using the display to view and acknowledge the status alarmsFigure 9-2: SEE ALARMYesScroll and Select simultaneously for 4 secondsACK ALLYesEXITSelec
Postrequisites• To clear the following alarms, you must correct the problem, acknowledge thealarm, then power-cycle the transmitter: A001, A002, A010,
9.4.3 View and acknowledge alerts using ProLink IIIYou can view a list containing all alerts that are active, or inactive and have beenunacknowleged.
• To refresh the list of active or unacknowledged alarms, press Service Tools > Alerts >Refresh Alerts.9.4.5 Alarm data in transmitter memoryThe
OverviewTotalizers keep track of the total amount of mass or volume measured by the transmittersince the last totalizer reset. Inventories keep track
1. Scroll until the word TOTAL appears in the lower left corner of the display.ImportantBecause all totalizers are started or stopped together, it doe
9.7 Reset totalizersDisplay See Section 9.7.1.ProLink II ProLink > Totalizer Control > Reset Mass TotalProLink > Totalizer Control > Reset
3. Scroll until RESET appears beneath the current totalizer value.4. Select.5. Select again to confirm.6. Scroll to EXIT.7. Select.• To reset the volu
2.3 Make a startup connection to the transmitterFor all configuration tools except the display, you must have an active connection to thetransmitter t
OverviewWhen you reset an inventory, the transmitter sets its value to 0. It does not matterwhether the inventory is started or stopped. If the invent
10 Operate the transmitter with theWeights & Measures applicationTopics covered in this chapter:•Operate the transmitter when the Weights & Me
• You cannot stop totalizers while the tranmitter is secured.• You cannot reset inventories while the transmitter is secured.10.1.1 Approved methods t
The display is able to show a maximum of eight characters, including the decimal point.For all totalizer values configured as display variables, the p
Transmitter outputs and process data when Approvals=OIMLTable 10-4: Function Transmitter statusUnsecured SecuredOutputs mA output behavior Performs
Available actions when Approvals=NTEP (continued)Table 10-5: Function Transmitter statusUnsecured SecuredOutputs set to Last Meas-ured ValueAllowed
Available actions when Approvals=OIML (continued)Table 10-6: Function Transmitter statusUnsecured SecuredSmart Meter Verification Outputs set to Con
The controls are not accessible in any other way.10.2.1 Switch between secured and unsecured mode usingProLink IIPrerequisitesBefore switching to unse
1. Make a service port connection to your transmitter.2. Choose Device Tools > Configuration > Weights & Measures.3. Set Software Security t
10.4 Replacing the core processor in a Weights &Measures installationIn a Weights & Measures installation, replacing the core processor requir
2.4 Characterize the flowmeter (if required)DisplayNot availableProLink II • ProLink > Configuration > Device > Sensor Type• ProLink > Con
Operate the transmitter with the Weights & Measures application172 Micro Motion® Model 2700 Transmitters with Analog Outputs
11 Measurement supportTopics covered in this chapter:•Options for measurement support•Use Smart Meter Verification•Zero the flowmeter•Validate the met
11.2.1 Smart Meter Verification requirementsTo use Smart Meter Verification, the transmitter must be paired with an enhanced coreprocessor, and the Sm
Smart Meter Verification has an output mode called Continuous Measurement that allows thetransmitter to keep measuring while the test is in progress.
Option DescriptionLast ValueDuring the test, all outputs will go to their configured fault action. The testwill run for approximately 140 seconds.Whil
Smart Meter Verification flowchart: Running a test using the displayRunning a Smart Meter Verification test using the displayFigure 11-2: OUTPUTSARE
You may need to wait a few seconds while ProLink II synchronizes its database withthe transmitter data.2. Review the information presented on the scre
PostrequisitesView the test results and take any appropriate actions.Run a Smart Meter Verification test using theField Communicator1. Navigate to the
• Current flowmeter identification data• Current flow and density configuration parameters• Current zero values• Current process values for mass flow
Smart Meter Verification flowchart: Viewing test results using the displayViewing Smart Meter Verification test results using the displayFigure 11-4:
• Older curved-tube sensors (all sensors except T-Series): see Figure 2-1• Newer curved-tube sensors (all sensors except T-Series): see Figure 2-2• Ol
View test result data using ProLink II1. Choose Tools > Meter Verification > Run Meter Verification and click View Previous Test Resultsand Prin
FailThe test result is not within the specification uncertainty limit. Micro Motionrecommends that you immediately repeat the meter verification test.
Manage scheduled test execution using the display1. Navigate to the Smart Meter Verification menu.Smart Meter Verification – Top-level menuFigure 11-5
Smart Meter Verification flowchart: Scheduling test execution using the displayScheduling Smart Meter Verification test execution using the displayFig
4. To disable scheduled execution:• To disable execution of a single scheduled test, set Hours Until Next Run to 0.• To disable recurring execution, s
• The zero is required by site procedures.• The stored zero value fails the Zero Verification procedure.PrerequisitesBefore performing a field zero, e
2. Navigate to OFFLINE MAINT > ZERO > CAL ZERO and select CAL/YES?.Dots traverse the display while flowmeter zero is in progress.3. Read the zer
3. Click Calibrate Zero.4. Modify Zero Time, if desired.Zero Time controls the amount of time the transmitter takes to determine its zero-flow referen
a. Allow the flowmeter to warm up for at least 20 minutes after applying power.b. Run the process fluid through the sensor until the sensor temperatur
11.3.4 Zero the flowmeter using the Field CommunicatorZeroing the flowmeter establishes a baseline for process measurement by analyzing thesensor&apos
Safety messagesSafety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefullybefore procee
Tag on older straight-tube sensor (T-Series)Figure 2-3: Tag on newer straight-tube sensor (T-Series)Figure 2-4: Density calibration parameters (D1
11.4 Validate the meterDisplay OFF-LINE MAINT > CONFG > UNITS > MTR FProLink II ProLink > Configuration > FlowProLink III Device Tools
Procedure1. Determine the meter factor as follows:a. Use the flowmeter to take a sample measurement.b. Measure the same sample using the reference dev
MeterFactorVolume1MeterFactorDensity=NoteThe following equation is mathematically equivalent to the first equation. You may usewhichever version you p
• If LD Optimization is enabled on your meter, disable it. To do this, choose ProLink >Configuration > Sensor and ensure that the checkbox is no
PostrequisitesIf you disabled LD Optimization before the calibration procedure, re-enable it.11.5.2 Perform a D1 and D2 density calibration using ProL
D1 and D2 density calibration using ProLink IIIFigure 11-8: Enter density of D1 fluidD1 calibrationClose shutoff valve downstream from sensorFill se
• Before performing the calibration, record your current calibration parameters. If thecalibration fails, restore the known values.RestrictionFor T-Se
11.6 Perform a D3 and D4 density calibration (T-Series sensors only)For T-Series sensors, the optional D3 and D4 calibration could improve the accurac
D3 or D3 and D4 density calibration using ProLink IIFigure 11-10: Enter density of D3 fluidCalibration in Progress light turns greenCalibration in P
- Minimum difference of 0.1 g/cm3 between the density of the D4 fluid and thedensity of the D3 fluid. The density of the D4 fluid must be greater than
If your sensor tag does not show a DT or TC value, enter the last 3 digits of the densitycalibration factor. In the sample tag, this value is shown as
• For D3 density calibration, the D3 fluid must meet the following requirements:- Minimum density of 0.6 g/cm3- Minimum difference of 0.1 g/cm3 betwee
D3 or D3 and D4 density calibration using the Field CommunicatorFigure 11-12: Enter density of D3 fluidDensity Calibration Complete messageCalibrati
ImportantConsult Micro Motion before performing a temperature calibration. Under normal circumstances,the temperature circuit is stable and should not
Temperature calibration using ProLink IIIFigure 11-14: Enter temperature of low-temperature fluidTemperature Offset calibrationWait until sensor ach
Measurement support206 Micro Motion® Model 2700 Transmitters with Analog Outputs
12 TroubleshootingTopics covered in this chapter:•Status LED states•Status alarms•Flow measurement problems•Density measurement problems•Temperature m
12.1 Status LED statesThe status LED on the transmitter indicates whether or not alarms are active. If alarms areactive, view the alarm list to identi
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA003 No Sensor Response The transmitter is no
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA005 Mass Flow Rate Overrange The sensor is s
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA008 Density Overrange The sensor is signalin
• Review the troubleshooting suggestions for flow measurement issues. See Section 12.3.2.6 Verify the zeroVerifying the zero helps you determine if th
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA010 Calibration Failure This alarm is typica
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA016 Sensor RTD Failure The sensor RTD is sig
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA019 RAM Error (Transmitter) Power to the tra
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA026 Sensor/Transmitter Communi-cations Failu
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA031 Low Power The core processor on the sens
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA100 mA Output 1 Saturated The calculated mA
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA110 Frequency Output Saturated The calculate
Status alarms and recommended actions (continued)Table 12-2: Alarm code Description Recommended actionsA117 Density Overrange (Petrole-um)1. Check y
12.3 Flow measurement problemsFlow measurement problems and recommended actionsTable 12-3: Problem Possible causes Recommended actionsFlow indicatio
Flow measurement problems and recommended actions (continued)Table 12-3: Problem Possible causes Recommended actionsErratic non-zero flowrate when f
3. If the zero verification procedure fails:a. Confirm that the sensor is completely blocked in, that flow has stopped, and thatthe sensor is complete
12.4 Density measurement problemsDensity measurement problems and recommended actionsTable 12-4: Problem Possible causes Recommended actionsInaccura
12.5 Temperature measurement problemsTemperature measurement problems and recommended actionsTable 12-5: Problem Possible causes Recommended actions
12.6 Milliamp output problemsMilliamp output problems and recommended actionsTable 12-6: Problem Possible causes Recommended actionsNo mA output • W
Milliamp output problems and recommended actions (continued)Table 12-6: Problem Possible causes Recommended actionsmA output consis-tently out of ra
Frequency output problems and recommended actionsTable 12-7: Problem Possible causes Recommended actionsNo frequency output • Stopped totalizer• Pro
For more information on using sensor simulation using ProLink II, see Section 7.1.12.9 Check power supply wiringIf the power supply wiring is damaged
PrerequisitesYou will need the installation manual for your transmitter.Procedure1. Before opening the wiring compartments, disconnect the power sourc
Follow appropriate procedures to ensure that loop testing will not interfere with existingmeasurement and control loops.Procedure1. Test the mA output
c. At the transmitter, activate Select.d. Scroll to and select SET OFF.e. Verify the signal at the receiving device.f. At the transmitter, activate Se
i. Click UnFix mA.2. Test the frequency output(s).NoteIf the Weights & Measures application is enabled on the transmitter, it is not possible tope
3. If the zero verification procedure fails:a. Confirm that the sensor is completely blocked in, that flow has stopped, and thatthe sensor is complete
Procedure1. Test the mA output(s).a. Choose Device Tools > Diagnostics > Testing > mA Output 1 Test or Device Tools >Diagnostics > Test
f. Click UnFix.12.12.4 Perform loop tests using the Field CommunicatorTipLoop tests are not required. However, Micro Motion recommends performing a lo
b. Read the frequency signal at the receiving device and compare it to thetransmitter output.c. Choose End.3. Test the discrete output(s).a. Press Ser
12.14 Check the HART communication loopIf you cannot establish or maintain HART communications, the HART loop may be wiredincorrectly.PrerequisitesYou
Procedure1. Set HART Address as appropriate for your HART network.The default address is 0. This is the recommended value unless the transmitter is in
• For the relevant status alarms, change the setting of Alarm Severity to Ignore.3. If there are no active fault conditions, continue troubleshooting.
The Flow Direction parameter interacts with actual flow direction to affect flow values, flowtotals and inventories, and output behavior. For the simp
12.26 Check the drive gainExcessive or erratic drive gain may indicate any of a variety of process conditions, sensorproblems, or configuration proble
Possible causes and recommended actions for erratic drive gain(continued)Table 12-9: Possible cause Recommended actionsPolarity of pick-off reversed
Possible causes and recommended actions for low pickoff voltage(continued)Table 12-10: Possible cause Recommended actionsNo tube vibration in sensor
Part IIConfiguration and commissioningChapters covered in this part:•Introduction to configuration and commissioning•Configure process measurement•Con
12.28.1 Check the sensor coilsChecking the sensor coils can identify electrical shorts.RestrictionThis procedure applies only to 9-wire remote-mount t
a. Leave the terminal blocks disconnected.b. Remove the lid of the junction box.c. Testing one terminal at a time, place a DMM lead on the terminal an
a. Remove the core processor lid. The core processor is intrinsically safe and can beopened in all environments.b. Check the state of the core process
9-wire remote installation componentsFigure 12-2: TransmitterCore processor4 x cap screws (4 mm)End-capb. Inside the core processor housing, loosen
3. Tighten the screws, torquing to 6 to 8 in-lbs (0.7 to 0.9 N-m).4. Replace the end-cap.ImportantWhen reassembling the meter components, be sure to g
Enhanced core processor LED states (continued)Table 12-14: LED state Description Recommended actionSolid red High-severity alarm Check alarm status.
Integral installation componentsFigure 12-3: Base4 x cap screws (4 mm)Transition ringTransmitterCore processorb. Rotate the transmitter counter-cloc
5. At the core processor, disconnect the 4-wire cable between the core processor andthe transmitter.6. Measure the resistance between core processor t
Troubleshooting250 Micro Motion® Model 2700 Transmitters with Analog Outputs
Appendix AUsing the transmitter displayTopics covered in this appendix:•Components of the transmitter interface•Use the optical switches•Access and us
Configuration and commissioning18 Micro Motion® Model 2700 Transmitters with Analog Outputs
Transmitter interfaceFigure A-1: ABCDEFGHA. Status LEDB.Display (LCD panel)C. Process variableD. Scroll optical switchE. Optical switch indicatorF.
Optical switch indicator and optical switch statesTable A-1: Optical switch indicator State of optical switchesSolid red One optical switch is activ
TipIf you do not know the correct value for Off-Line Password, wait 30 seconds. The passwordscreen will time out automatically and you will be returne
Procedure• To change the value:1. Activate Select until the digit you want to change is active (flashing).Select moves the cursor one position to the
• To exit the menu without saving the displayed value to transmitter memory,activate Scroll and Select simultaneously and hold until the display chang
b. Activate Scroll until the desired character is displayed.c. Activate Select to move the cursor one digit to the left.d. Activate Scroll until the d
Display codes for process variables (continued)Table A-2: Code Definition Comment or referenceFVZ Field verification zero Weights & Measures app
A.5 Codes and abbreviations used in display menusCodes and abbreviations used in display menusTable A-3: Code or abbrevi-ation Definition Comment or
Codes and abbreviations used in display menus (continued)Table A-3: Code or abbrevi-ation Definition Comment or referenceENABLE ALARM Enable alarm m
Codes and abbreviations used in display menus (continued)Table A-3: Code or abbrevi-ation Definition Comment or referenceMASS Mass flowMBUS ModbusMF
3 Introduction to configuration andcommissioningTopics covered in this chapter:•Configuration flowchart•Default values and ranges•Enable access to the
A.6 Menu maps for the transmitter displayOffline menu – top levelFigure A-2: Scroll and Select simultaneously for 4 secondsVEROFF-LINE MAINTSelectSE
Offline menu – version informationFigure A-3: Scroll and Select simultaneously for 4 secondsVERYesVersion infoScrollSelectYesCEQ/ETO info*ScrollCUST
Offline menu – configuration: units and I/OFigure A-4: OFF-LINE MAINTScroll and Select simultaneously for 4 secondsScrollSelectSelectScrollCONFGMASS
Offline menu – configuration: meter factor, display, and digital communicationsFigure A-5: OFF-LINE MAINTScroll and Select simultaneously for 4 seco
Offline menu – alarmsFigure A-6: SEE ALARMScroll and Select simultaneously for 4 secondsACK ALL*YesEXITSelectNoAlarm codeScrollACKYesSelectNoActive/
Offline menu – meter verification: top levelFigure A-7: Scroll and Select simultaneously for 4 secondsENTER METER VERFYScrollRUN VERFY RESULTS READ
Offline menu – meter verification testFigure A-9: OUTPUTSARE YOU SURE/YES?. . . . . . . . . . . . . . . x%PASS VERFY ABORTED VERFYCAUTION VERFYFailA
Offline menu – meter verification resultsFigure A-10: RESULTS READSelectxx L STF%RUNCOUNT xSelectxx HOURSSelectPASSSelectxx R STF%SelectRESULTS MORE
Offline menu – totalizers and inventoriesFigure A-11: RESET(3)SelectScrollSTOP/START(2)RESET YES?Process variable displaySTOP/START YES?ScrollMass t
Offline menu – Simulation (loop testing)Figure A-12: Scroll and Select simultaneously for 4 secondsYesScrollSelectAO SIM FO SIM DO SIMScrollSelectSE
Configuration flowchartFigure 3-1: Integrate device with control systemConfigure device options and preferencesConfigure process measurementConfigur
Offline menu – ZeroFigure A-13: ………………….OFF-LINE MAINTScroll and Select simultaneously for 4 secondsScrollSelectSelectCAL ZEROTroubleshootZERO/YES?C
Appendix BUsing ProLink II with the transmitterTopics covered in this appendix:•Basic information about ProLink II•Connect with ProLink II•Menu maps f
ProLink II messagesAs you use ProLink II with a Micro Motion transmitter, you will see a number of messagesand notes. This manual does not document al
B.2.2 Make a service port connectionCAUTION!If the transmitter is in a hazardous area, do not use a service port connection. Service portconnections r
Connection to service portFigure B-1: AC DEBA. PCB.Signal converterC. Service port terminal 7 (RS-485/A)D. Service port terminal 8 (RS-485/B)E. Tran
CAUTION!If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals.Connecting directly to the transmitter termina
Connection to transmitter terminalsFigure B-2: ACDBA. PCB.Signal converterC. 250–600 Ω resistanceD. Transmitter, with wiring compartment and power s
Connection over local loopFigure B-3: ACDER1R3R2BA. PCB.Signal converterC. Any combination of resistors R1, R2, and R3 as necessary to meet HART com
Connection over multidrop networkFigure B-4: BACDA. Signal converterB. 250–600 Ω resistanceC. Devices on the networkD. Master device5. Start ProLink
Option DescriptionPrimaryUse this setting if no other host is on the network. The Field Communicator is nota host.12. Click Connect.Need help? If an
3.2 Default values and rangesSee Section E.1 to view the default values and ranges for the most commonly usedparameters.3.3 Enable access to the off-l
TipHART connections are not polarity-sensitive. It does not matter which lead you attach towhich terminal.Connection to transmitter terminalsFigure B-
Connection over networkFigure B-6: ACEDBA. PCB.Signal converterC.120-Ω, 1/2-watt resistors at both ends of the segment, if necessaryD. DCS or PLCE.
Option DescriptionSecondaryUse this setting if another HART host such as a DCS is on the network.PrimaryUse this setting if no other host is on the ne
TipUsually, but not always, the black lead is RS-485/A and the red lead is RS-485/B.Connection to transmitter terminalsFigure B-7: ACBA. PCB.Signal
Connection over networkFigure B-8: ACEDBA. PCB.Signal converterC.120-Ω, 1/2-watt resistors at both ends of the segment, if necessaryD. DCS or PLCE.
Need help? If an error message appears:• Verify the Modbus address of the transmitter.• Ensure that you have specified the correct COM port.• Check t
Main menu (continued)Figure B-10: Data Logging*Enable/Disable Custody TransferTools Plug-insProLinkConfigurationOutput LevelsProcess VariablesStatus
Configuration menuFigure B-11: Flow• Flow Direction• Flow Damp• Flow Cal• Mass Flow Cutoff• Mass Flow units• Mass Factor• Dens Factor• Vol Factor• F
Configuration menu (continued)Figure B-12: Temperature• Temp Units• Temp Cal Factor• Temp Damping• External Temperature• External RTDFrequency/Discr
Configuration menu (continued)Figure B-13: ProLink > ConfigurationAdditional configuration optionsDevice• Model• Manufacturer• Hardware Rev•
ContentsPart I Getting StartedChapter 1 Before you begin ...
TipWrite-protecting the transmitter prevents accidental changes to configuration. It does not preventnormal operational use. You can always disable wr
Configuration menu (continued)Figure B-14: ProLink > ConfigurationPolled VariablesPolled Variable 1/2• Polling Control• External Tag• Variabl
Configuration menu (continued)Figure B-15: ProLink > ConfigurationAdditional configuration optionsDisplay• mA1• Var1...Var15• Display Precisi
Configuration menu (continued)Figure B-16: ProLink > ConfigurationTransmitter Options• Volume Flow• Meter Fingerprinting• Cryogenic Moduls Co
Configuration menu (continued)Figure B-17: ProLink > ConfigurationSensor• Sensor s/n• Sensor Model• Sensor Matl• Liner Matl• FlangeAPI Setup•
Configuration menu (continued)Figure B-18: ProLink > ConfigurationSensor Simulation• Enable/disable• Mass flow• Wave form• Fixed value• Perio
Appendix CUsing ProLink III with the transmitterTopics covered in this appendix:•Basic information about ProLink III•Connect with ProLink III•Menu map
ProLink III messagesAs you use ProLink III with a Micro Motion transmitter, you will see a number of messagesand notes. This manual does not document
C.2.2 Make a service port connectionCAUTION!If the transmitter is in a hazardous area, do not use a service port connection. Service portconnections r
Connection to service portFigure C-1: AC DEBA. PCB.Signal converterC. Service port terminal 7 (RS-485/A)D. Service port terminal 8 (RS-485/B)E. Tran
CAUTION!If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals.Connecting directly to the transmitter termina
4 Configure process measurementTopics covered in this chapter:•Configure mass flow measurement•Configure volume flow measurement for liquid applicatio
Connection to transmitter terminalsFigure C-2: ACDBA. PCB.Signal converterC. 250–600 Ω resistanceD. Transmitter, with wiring compartment and power s
Connection over local loopFigure C-3: ACDER1R3R2BA. PCB.Signal converterC. Any combination of resistors R1, R2, and R3 as necessary to meet HART com
Connection over multidrop networkFigure C-4: BACDA. Signal converterB. 250–600 Ω resistanceC. Devices on the networkD. Master device5. Start ProLink
Option DescriptionPrimaryUse this setting if no other host is on the network. The Field Communicator is nota host.12. Click Connect.Need help? If an
TipHART connections are not polarity-sensitive. It does not matter which lead you attach towhich terminal.Connection to transmitter terminalsFigure C-
Connection over networkFigure C-6: ACEDBA. PCB.Adapter, if necessaryC. Signal converterD.120-Ω, 1/2-watt resistors at both ends of the segment, if n
8. Set Master as appropriate.Option DescriptionSecondaryUse this setting if another HART host such as a DCS is on the network.PrimaryUse this setting
b. Connect the leads from the signal converter to terminals 5 (RS-485/A) and 6(RS-485/B).TipUsually, but not always, the black lead is RS-485/A and th
Connection over networkFigure C-8: ACEDBA. PCB.Signal converterC.120-Ω, 1/2-watt resistors at both ends of the segment, if necessaryD. DCS or PLCE.
Need help? If an error message appears:• Verify the Modbus address of the transmitter.• Ensure that you have specified the correct COM port.• Check t
TipIf the measurement unit you want to use is not available, you can define a special measurement unit.Options for Mass Flow Measurement UnitThe trans
Device Tools: Configuration (with Weights & Measures)Figure C-10: Configuration: Process Measurement (with Concentration Measurement)Figure C-11
Configuration: Process Measurement (with Petroleum Measurement)Figure C-12: Configuration: I/OFigure C-13: Using ProLink III with the transmitterC
Configuration: Transmitter DisplayFigure C-14: Configuration: EventsFigure C-15: Using ProLink III with the transmitter314 Micro Motion® Model 270
Configuration: CommunicationsFigure C-16: Configuration: Informational ParametersFigure C-17: Using ProLink III with the transmitterConfiguration
Device Tools: CalibrationFigure C-18: Calibration: Density CalibrationFigure C-19: Using ProLink III with the transmitter316 Micro Motion® Model 2
Calibration: Temperature CalibrationFigure C-20: Device Tools: Configuration TransferFigure C-21: Using ProLink III with the transmitterConfigurat
Diagnostics: TestingFigure C-22: Diagnostics: Meter VerificationFigure C-23: Using ProLink III with the transmitter318 Micro Motion® Model 2700 Tr
Device Tools: TrendingFigure C-24: Using ProLink III with the transmitterConfiguration and Use Manual 319
Using ProLink III with the transmitter320 Micro Motion® Model 2700 Transmitters with Analog Outputs
Appendix DUsing the Field Communicator with thetransmitterTopics covered in this appendix:•Basic information about the Field Communicator•Connect with
Define a special measurement unit for mass flowDisplayNot availableProLink II ProLink > Configuration > Special UnitsProLink III Device Tools &g
If Micro Motion is not listed, or you do not see the required device description, use theField Communicator Easy Upgrade Utility to install the device
Field Communicator connection to transmitter terminalsFigure D-1: ABCA. Field CommunicatorB. 250–600 Ω resistanceC. Transmitter, with wiring compart
Field Communicator connection to multidrop networkFigure D-3: ABCDA. Field CommunicatorB. 250–600 Ω resistanceC. Devices on the networkD. Master dev
On-Line menuFigure D-4: Configure1 Manual Setup2 Alert SetupService Tools1 Alerts2 Variables3 Trends4 Maintenance5 Simulate23Overview1 Check Status2
Overview menuFigure D-5: Identification1 Tag2 Model3 Xmtr Serial Num4 Sensor Serial Num5 Date6 Descriptor7 Message1Revisions1 Universal2 Field Devic
Configure menuFigure D-6: Manual Setup1 Characterize2 Measurements3 Display4 Inputs/Outputs5 Info Parameters21Alert Setup1 I/O Fault Actions2 Alert
Manual Setup menuFigure D-7: Characterize1 Sensor Type2 Sensor Tag ParametersMeasurements1 Flow2 Density3 Temperature4 Update Rate5 LD Optimization6
Manual Setup menu: CharacterizeFigure D-8: On-Line Menu > 2 Configure > 1 Manual Setup > 1 Characterize2121Sens
Manual Setup menu: MeasurementsFigure D-9: On-Line Menu > 2 Configure > 1 Manual Setup > 2 MeasurementsFlow1 F
Manual Setup menu: Measurements (continued)Figure D-10: On-Line Menu > 2 Configure > 1 Manual Setup > 2 Measur
a. 1 lb/sec = 16 oz/secb. Mass Flow Conversion Factor = 1/16 = 0.06254. Set Mass Flow Conversion Factor to 0.0625.5. Set Mass Flow Label to oz/sec.6.
Manual Setup menu: DisplayFigure D-11: On-Line Menu >2 Configure > 1 Manual Setup > 3 DisplayLanguageEnglishGermanFrenchSpanishDisplay Vari
Manual Setup menu: I/OFigure D-12: On-Line Menu >2 Configure > 1 Manual Setup > 4 Inputs/OutputsmA Output1 Primary Variable2 mA Output Sett
Manual Setup menu: I/O (continued)Figure D-13: Discrete Output1 DO Assignment2 DO Polarity3 DO Fault Action4 Flow Switch Source5 Flow Switch Setpoin
Alert Setup menuFigure D-14: On-Line Menu >2 Configure > 2 Alert SetupI/O Fault Action1 MAO Fault Action2 MAO Fault Level3 FO Fault Action4 FO
Service Tools menuFigure D-15: On-Line Menu >3 Service ToolsAlerts1 Refresh AlertsAlert NameAdditional Information Variables1 Variable Summary2
Service Tools menu: VariablesFigure D-16: On-Line Menu >3 Service Tools > 2 VariablesProcess Variables1 Mass Flow Rate2 Volume Flow Rate *3 De
Service Tools menu: Variables (continued)Figure D-17: Outputs1 mA Output (MA0)2 Frequency OutputOn-Line Menu >3 Service Tools > 2 VariablesVar
Service Tools menu: MaintenanceFigure D-18: On-Line Menu >3 Service Tools >4 MaintenanceRoutine Maintenance1 Trim mA Output2 Meter Verificatio
Service Tools menu: SimulateFigure D-19: On-Line Menu >3 Service Tools >5 Simulate1Simulate Outputs1 mA Output Loop Test2 Frequency Output Tes
Appendix EDefault values and rangesE.1 Default values and rangesThe default values and ranges represent the typical factory transmitter configuration.
• In general, lower damping values are preferable because there is less chance of data loss, and lesslag time between the actual measurement and the r
Transmitter default values and ranges (continued)Table E-1: Type Parameter Default Range CommentsDensity units g/cm3Density cutoff 0.2 g/cm30.0 – 0.
Transmitter default values and ranges (continued)Table E-1: Type Parameter Default Range CommentsBase volume time secVolume flow conversion factor 1
Transmitter default values and ranges (continued)Table E-1: Type Parameter Default Range CommentsFault action DownscaleAO fault level – downscale 2.
Transmitter default values and ranges (continued)Table E-1: Type Parameter Default Range CommentsPolarity Active lowDisplay Backlight on/off OnBackl
Default values and ranges346 Micro Motion® Model 2700 Transmitters with Analog Outputs
Appendix FTransmitter components and installationwiringTopics covered in this appendix:•Installation types•Power supply terminals and ground•Input/out
High-temperature flexible conduit installationFigure F-2: High-temperature flexible conduit installations use the same installationinstructions as 4
4-wire remote installation – stainless steel housingFigure F-4: SensorCore processorTransmitter4-wire cable• 9-wire remote – The transmitter and cor
9-wire remote installation typeFigure F-5: TransmitterJunction boxSensor9-wire cable• Remote core processor with remote sensor – A remote core proce
Remote core processor with remote sensor installation typeFigure F-6: Core processorTransmitter4-wire cable9-wire cableSensorJunction boxF.2 Power s
ProcedureSet Mass Flow Cutoff to the value you want to use.The default value for Mass Flow Cutoff is 0.0 g/sec or a sensor-specific value set at thefa
F.3 Input/output (I/O) wiring terminalsI/O wiring terminalsFigure F-8: ABCA. mA/HARTB. Frequency output or discrete outputC. RS-485Transmitter compo
Appendix GNE 53 historyG.1 NE 53 historyDate Version Type ChangeOperating in-struction08/2000 1.x Expansion Added writing of the device tag using Modb
Date Version Type ChangeOperating in-structionThe display start/stop totalizers function can beenabled or disabledPetroleum measurement application im
Date Version Type ChangeOperating in-struction09/2006 5.x Expansion Discrete output assignable as a flow switch 20001715 BDiscrete output fault indica
Date Version Type ChangeOperating in-structionAdjustment The following combinations are not allowed:• mA Output Fault Action = None and DigitalCommuni
IndexAAdded Damping 105Additional Communications Response Delay 130addressHART address 124, 129Modbus address 130air calibration, See calibrat
restore factory configurationusing ProLink II 22using ProLink III 22temperature measurement 50volume flow measurement 29Weights & Measures
polarityconfiguring 118options 118sourceconfiguring 115options 115displayaccessing menu system 253components 251configuring display behavi
using the display 228using the Field Communicator 233maximum pulse width 112polarityconfiguring 110options 110process variableconfiguring
process variableconfiguring 100options 101scaling 102troubleshooting 224, 236mass flow measurementconfiguring 23cutoffconfiguring 27effect
- The frequency output will report the actual flow rate, and the actual flow rate willbe used in all internal processing.• If the mass flow rate drops
using ProLink III 54using the Field Communicator 56polling address, See HART addresspowerpower up 7power supply terminals 351power supply wiri
slave address, See Modbus addressslug flow, See density measurement, slug flowSmart Meter Verificationautomatic execution and schedulingusing ProLink
unsecured, See Weights & Measures applicationUpdate Period 80Update Rateconfiguring 87effect on process measurement 88incompatible functions
*MMI-20019043*MMI-20019043Rev AA2012Micro Motion Inc. USAWorldwide Headquarters7070 Winchester CircleBoulder, Colorado 80301T +1 303-527-5200T +1 800-
ProcedureSet Volume Flow Type to Liquid.4.2.2 Configure Volume Flow Measurement Unit for liquidapplicationsDisplay OFF-LINE MAINT > OFF-LINE CONFG
Options for Volume Flow Measurement Unit for liquid applications (continued)Table 4-3: Unit descriptionLabelDisplay ProLink II ProLink III Field Com
4.5 Configure density measurement ... 454.5.1 Configure
Define a special measurement unit for volume flowDisplayNot availableProLink II ProLink > Configuration > Special UnitsProLink III Device Tools
a. 1 gal/sec = 8 pints/secb. Volume Flow Conversion Factor = 1/8 = 0.12504. Set Volume Flow Conversion Factor to 0.1250.5. Set Volume Flow Label to pi
Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and0 will be used in all internal processing.Example: Cutoff
4.3.1 Configure Volume Flow Type for gas applicationsDisplayNot availableProLink II ProLink > Configuration > Flow > Vol Flow TypeProLink III
ProcedureSet Standard Gas Density to the standard reference density of the gas you are measuring.NoteProLink II and ProLink III provide a guided metho
Options for Gas Standard Volume Measurement UnitTable 4-4: Unit descriptionLabelDisplay ProLink II ProLink III Field Communica-torNormal cubic meter
OverviewA special measurement unit is a user-defined unit of measure that allows you to reportprocess data, totalizer data, and inventory data in a un
4.3.4 Configure Gas Standard Volume Flow CutoffDisplayNot availableProLink II ProLink > Configuration > Flow > Std Gas Vol Flow CutoffProLink
Example: Cutoff interaction with AO Cutoff higher than Gas Standard Volume FlowCutoffConfiguration:• mA Output Process Variable for the primary mA out
4.4.1 Options for Flow DirectionOptions for Flow DirectionTable 4-5: Flow Direction setting Relationship to Flow Direction ar-row on sensorProLink I
5.6.6 Configure Sensor Liner Material ... 975.6.7 Configure Sensor Fl
Effect of Flow Direction on the mA output: Lower Range Value = 0Figure 4-1: Flow Direction = ForwardmA output-x 0 xReverse flow Forward flow20124Flo
• Under conditions of reverse flow or zero flow, the mA output is 4 mA.• Under conditions of forward flow, up to a flow rate of 100 g/sec, the mA outp
Effect of Flow Direction on frequency outputsFlow Direction affects how the transmitter reports flow values via the frequency outputs. Thefrequency ou
Effect of the Flow Direction parameter and actual flow direction on flowvalues reported via digital communicationsTable 4-8: Flow Direction setting
4.5.1 Configure Density Measurement UnitDisplay OFF-LINE MAINT > OFF-LINE CONFG > UNITS > DENSProLink II ProLink > Configuration > Dens
4.5.2 Configure slug flow parametersDisplayNot availableProLink II • ProLink > Configuration > Density > Slug High Limit• ProLink > Config
The default value for Slug High Limit is 5.0 g/cm3. The range is 0.0 to 10.0 g/cm3.3. Set Slug Duration to the number of seconds that the transmitter
OverviewDamping is used to smooth out small, rapid fluctuations in process measurement. DampingValue specifies the time period (in seconds) over which
Interaction between Density Damping and Added DampingIn some circumstances, both Density Damping and Added Damping are applied to the reporteddensity
4.6.1 Configure Temperature Measurement UnitDisplay OFF-LINE MAINT > OFF-LINE CONFG > UNITS > TEMPProLink II ProLink > Configuration >
9.4.3 View and acknowledge alerts using ProLink III ...1569.4.4 View alarms using the Field
OverviewDamping is used to smooth out small, rapid fluctuations in process measurement. DampingValue specifies the time period (in seconds) over which
4.7 Configure the petroleum measurementapplicationThe petroleum measurement application enables Correction for the effect of Temperatureon the volume
Option SetupPolling for tempera-turea. Ensure that the primary mA output has been wired to supportHART polling.b.Choose View > Preferences .c. Enab
5. Set Temperature Source to the method that the transmitter will use to obtaintemperature data.Option DescriptionPoll for external valueThe transmitt
4.7.3 Configure petroleum measurement using theField Communicator1. Choose Online > Configure > Manual Setup > Measurements > Set Up Petro
Option SetupA value written bydigital communica-tionsa. Choose Online > Configure > Manual Setup > Measurements > ExternalPressure/Tempera
API reference tables, associated process fluids, and associated calculation values (continued)Table 4-13: Tablename Process fluid CTL source data Re
• The concentration measurement application must be enabled on your transmitter.• The concentration matrix you want to use must be available on your t
RestrictionThe high and low limit alarms require the enhanced core processor.Example: If Alarm Limit is set to 5%, Enable Temp High is checked, and th
Option SetupA value written bydigital communica-tionsa. Choose View > Preferences .b.Enable Use External Temperature.c. Perform the necessary host
12.3 Flow measurement problems ...22012.4 Density mea
3. Choose Device Tools > Configuration > Process Measurement > Concentration Measurement.4. Set Derived Variable to the derived variable that
RestrictionThe high and low limit alarms require the enhanced core processor.Example: If Extrapolation Alarm Limit is set to 5%, High Extrapolation Li
13. Set Active Matrix to the matrix to be used for measurement.Concentration process variables are now available on the transmitter. You can view andr
d. Choose Online > Configure > Alert Setup > CM Alerts.e. Enable or disable the high and low limit alarms for temperature and density, asdesi
Option SetupPolling for tempera-turea. Ensure that the primary mA output has been wired to supportHART polling.b.Choose Online > Configure > Man
TipIf the standard matrices are not appropriate for your application, you can build a custom matrix orpurchase a custom matrix from Micro Motion.Stand
Derived variables and calculated process variables Table 4-15: Derived VariableDescriptionCalculated process variablesDensity atreferencetempera-tur
Derived variables and calculated process variables (continued)Table 4-15: Derived VariableDescriptionCalculated process variablesDensity atreference
The flow factor is the percent change in the flow rate per PSI. When entering thevalue, reverse the sign.Example:If the flow factor is 0.000004 % per
Option SetupA value written bydigital communica-tionsa. Set Pressure Units to the desired unit.b.Perform the necessary host programming and communicat
B.2.2 Make a service port connection ...275B.2.3 Make a HART/Bell 202
The density factor is the change in fluid density, in g/cm3/PSI. When entering thevalue, reverse the sign.Example:If the density factor is 0.000006 g/
9. If you want to use digital communications, click Apply, then perform the necessaryhost programming and communications setup to write temperature da
Option SetupA user-configuredstatic pressure val-uea. Set Pressure Unit to the desired unit.b.Set Compensation Pressure to the desired value.Polling f
Options for Pressure Measurement UnitTable 4-16: Unit descriptionLabelDisplay ProLink II ProLink III Field Communica-torFeet water @ 68 °FFTH2OFt Wa
Configure process measurement76 Micro Motion® Model 2700 Transmitters with Analog Outputs
5 Configure device options andpreferencesTopics covered in this chapter:•Configure the transmitter display•Enable or disable operator actions from the
The languages available depend on your transmitter model and version.5.1.2 Configure the process variables shown on the displayDisplayNot availablePro
Display variable Process variable assignmentDisplay Variable 10NoneDisplay Variable 11NoneDisplay Variable 12NoneDisplay Variable 13NoneDisplay Variab
OverviewSetting Display Precision determines the precision (number of decimal places) shown on thedisplay. You can set Display Precision independently
5.1.5 Enable or disable automatic scrolling through thedisplay variablesDisplay OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > AUTO SCRLLProLink
Part IGetting StartedChapters covered in this part:•Before you begin•Quick startGetting StartedConfiguration and Use Manual 1
ProcedureEnable or disable Backlight.The default setting is Enabled.5.1.7 Enable or disable Status LED BlinkingDisplayNot availableProLink II ProLink
5.2.1 Enable or disable Totalizer Start/Stop from the displayDisplay OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > TOTALS STOPProLink II ProLin
Restrictions• This parameter does not apply to inventories. You cannot reset inventories from the display.• You cannot use the display to reset all to
Option DescriptionEnabled (default)Operators can use a single display command to acknowledge all alarmsat once.DisabledOperators cannot acknowledge al
3. To require a password for access to the maintenance section of the off-line menuand the Smart Meter Verification menu, enable or disable Off-Line P
5.4.1 Configure Update RateDisplayNot availableProLink II ProLink > Configuration > Device > Update RateProLink III Device Tools > Configu
Effects of Update Rate = SpecialIncompatible features and functionsSpecial mode is not compatible with the following features and functions:• Enhanced
5.4.2 Configure Calculation Speed (Response Time)DisplayNot availableProLink II ProLink > Configuration > Device > Response TimeProLink III D
5.5.1 Configure Fault TimeoutDisplayNot availableProLink II ProLink > Configuration > Analog Output > Last Measured Value TimeoutProLink >
OverviewUse Status Alarm Severity to control the fault actions that the transmitter performs when itdetects an alarm condition.Restrictions• For some
Kommentare zu diesen Handbüchern