www.Fisher.comFisherr i2P-100 Electro‐Pneumatic TransducerContentsIntroduction 1...Scope of Manual 1...
Instruction ManualD103198X012i2P-100 TransducerJuly 201410Table 7. Hazardous Area Classifications—ATEXCertificate Certification Obtained Entity Rating
Instruction ManualD103198X012i2P-100 TransducerJuly 201411MountingWhen a transducer is ordered as part of a control valve assembly, the factory mounts
Instruction ManualD103198X012i2P-100 TransducerJuly 201412Figure 5. Dimensions and Connections58.7(2.31)22.3(0.88)75.2(2.96)55.7(2.19)33.3(1.31)67.8(2
Instruction ManualD103198X012i2P-100 TransducerJuly 201413MOUNTING BRACKETi2P‐100 TRANSDUCERREGULATORPIPENIPPLE2.5 INCHCHAMFER 45_ to 27/64 DIA1/4‐18
Instruction ManualD103198X012i2P-100 TransducerJuly 201414NoteIf the i2P‐100 transducer is used in a valve assembly with a positioner, no hook‐up for
Instruction ManualD103198X012i2P-100 TransducerJuly 201415 WARNINGSelect wiring and/or cable glands that are rated for the environment of use (such a
Instruction ManualD103198X012i2P-100 TransducerJuly 201416For intrinsically safe areas, current monitoring during operation must be with a meter appro
Instruction ManualD103198X012i2P-100 TransducerJuly 2014171. Remove electronics module cover (cover adjacent to conduit entry, see figure 3 and 4).CA
Instruction ManualD103198X012i2P-100 TransducerJuly 201418Figure 11. Fisher i2P‐100 Transducer SchematicCOILZEROANDSPAN CIRCUITDC CURRENTINPUT SIGNALP
Instruction ManualD103198X012i2P-100 TransducerJuly 201419D Remove electrical power before removing either housing cap. Personal injury or property da
Instruction ManualD103198X012i2P-100 TransducerJuly 20142CAUTIONDropping or rough handling of the transducer can cause damage to the converter module
Instruction ManualD103198X012i2P-100 TransducerJuly 2014203. If a filter/regulator is used, ensure that it is working correctly. If not, ensure the d
Instruction ManualD103198X012i2P-100 TransducerJuly 2014213. Electrically calibrate the unit using the procedure in the Calibration section of this m
Instruction ManualD103198X012i2P-100 TransducerJuly 2014221. Assemble the inner valve spring (key 35) onto the body plug (key 32) and fit the valve p
Instruction ManualD103198X012i2P-100 TransducerJuly 201423Figure 13. Fisher i2P‐100 Transducer AssemblyNOTE: APPLY LUBRICANT/SEALANT/ADHESIV
Instruction ManualD103198X012i2P-100 TransducerJuly 201424Figure 14. Fisher i2P‐100 Relay Assembly30C2258‐BNOTE: APPLY LUBRICANT/SEALANT/ADHES
Instruction ManualD103198X012i2P-100 TransducerJuly 201425Key DescriptionMounting PartsNoteContact your Emerson Process Management sales office for i2
Instruction ManualD103198X012i2P-100 TransducerJuly 201426Loop Schematics/NameplatesFigure 15. CSA Loop SchematicGE07471_BFigure 16. Typical CSA/FM Ap
Instruction ManualD103198X012i2P-100 TransducerJuly 201427Figure 17. FM Loop SchematicGE07470_BFigure 18. Typical ATEX/IECEx Approval NameplateATEX IN
Instruction ManualD103198X012i2P-100 TransducerJuly 201428Scan or click the QR codeto calculate pneumaticenergy savings.Scan or click the QR code to f
Instruction ManualD103198X012i2P-100 TransducerJuly 20143Table 1. SpecificationsInput SignalAvailable as standard with 4‐20 mA.User configurable by di
Instruction ManualD103198X012i2P-100 TransducerJuly 20144Table 1. Specifications (continued)Electrical Housing:When Remotely Vented No Remote VentingC
Instruction ManualD103198X012i2P-100 TransducerJuly 20145Table 3. Maximum Steady-State Flow Rate (Air)SUPPLY PRESSURE OUTPUT PRESSURESTEADY STATEFLOW
Instruction ManualD103198X012i2P-100 TransducerJuly 20146 WARNINGTo avoid personal injury or property damage from the sudden release of pressure, air
Instruction ManualD103198X012i2P-100 TransducerJuly 20147Hazardous Area Classifications and Special Instructions for “Safe Use” andInstallation in Haz
Instruction ManualD103198X012i2P-100 TransducerJuly 20148FMSpecial Conditions of UseIntrinsically Safe, Explosion-proof, Type n, Non‐incendive, Dust‐I
Instruction ManualD103198X012i2P-100 TransducerJuly 20149Special Conditions for Safe UseIntrinsically Safe1. Before putting in service, the user shal