Rosemount 5300 Series
Specifications
General
Product Rosemount 5300 Series Guided Wave Radar;
Model 5301, Liquid Level or Interface Transmitter (interface available for fully submerged
probe).
Model 5302 Liquid Level and Interface Transmitter.
Model 5303 Solids Level Transmitter.
Measurement Principle Time Domain Reflectometry (TDR).
Reference Conditions Single standard probe, 77°F (25°C) in water and ambient pressure.
Microwave Output Power Nominal 300 µW, Max. 45 mW.
CE-mark Complies with applicable directives (EMC, ATEX).
Start-up Time < 40 s
Measuring Performance
Reference Accuracy ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is greatest.
(1)
Repeatability ± 0.04 in. (1 mm).
Ambient Temperature Effect ± 0.008 in. (0.2 mm) /°K or ± 30 ppm/°K of measured value, whichever is greatest.
Update Interval < 1 per second.
Measuring Range 16 in. (0.4 m) to 164 ft (50 m). See page 11 for further information.
Display / Configuration / Communication
Integral Display The integral digital display can toggle between: level, distance, volume, internal temperature,
interface distance, interface level, peak amplitudes, interface thickness, percentage of range,
analog current out. Note! The display cannot be used for configuration purposes.
Output Variables All models: Level, Distance to Level, Volume, Level Rate, Signal Strength, Internal
Temperature, Analog Output Current
(2)
and % of Range
(2)
,
Model 5301 (in addition to the above for the case with fully submerged probe): Interface
Level and Interface Distance.
Model 5302 (in addition to the above): Interface Level, Interface Level Rate, Interface
Distance, Upper Volume, Lower Volume and Upper Product Thickness.
Output Units Level, Interface and Distance: ft, inches, m, cm or mm.
Level Rate: ft/s, m/s, in./min, m/h.
Volume: ft
3
, inch
3
, US gals, Imp gals, barrels, yd
3
, m
3
or liters.
Temperature: °F and °C.
Configuration Tools HART
®
: Rosemount RadarMaster, Rosemount 375 Field Communicator, AMS Suite or any
other DD (Device Description) compatible host system.
F
OUNDATION™ fieldbus: Rosemount RadarMaster, Rosemount 375 Field Communicator,
DeltaV
®
or any other DD (Device Description) compatible host system.
FOUNDATION™ fieldbus Blocks Resource block, 3 Transducer blocks, 6 AI blocks, PID block, ISEL block, SGCR block,
ARTH block, and OS block.
FOUNDATION™ fieldbus Class (Basic or Link
Master)
Link Master (LAS).
FOUNDATION™ fieldbus Block Execution Time AI-block: 30 ms. PID-block: 40 ms.
ARTH-, ISEL-, OSPL-block: 65 ms. CHAR-block: 75 ms.
FOUNDATION™ fieldbus Instantiation No.
Conforming FOUNDATION™ fieldbus ITK 5.0.
FOUNDATION™ fieldbus PlantWeb
®
Alert
Support
Yes.
Damping 0-60 s (2 s, default value).